CFM, STATIC PRESSURE, AND POWER - ALTITUDE AND TEMPERATURE CORRECTIONS

The information below should be used to assist in application of product when being applied at altitudes at or exceeding 1000 feet above sea level.

The air flow rates listed in the standard blower performance tables are based on standard air at sea level. As the altitude or temperature increases, the density of air decreases. In order to

TABLE 10: ALTITUDE CORRECTION FACTORS

use the indoor blower tables for high altitude applications, certain corrections are necessary.

A centrifugal fan is a "constant volume" device. This means that, if the rpm remains constant, the CFM delivered is the same regardless of the density of the air. However, since the air at high altitude is less dense, less static pressure will be generated and less power will be required than a similar application at sea level. Air density correction factors are shown in Table 10 and Figure 11.

AIR TEMP

 

 

 

 

ALTITUDE (FEET)

 

 

 

 

 

0

1000

2000

3000

4000

5000

6000

7000

8000

9000

10000

 

40

1.060

1.022

0.986

0.950

0.916

0.882

0.849

0.818

0.788

0.758

0.729

50

1.039

1.002

0.966

0.931

0.898

0.864

0.832

0.802

0.772

0.743

0.715

60

1.019

0.982

0.948

0.913

0.880

0.848

0.816

0.787

0.757

0.729

0.701

70

1.000

0.964

0.930

0.896

0.864

0.832

0.801

0.772

0.743

0.715

0.688

80

0.982

0.947

0.913

0.880

0.848

0.817

0.787

0.758

0.730

0.702

0.676

90

0.964

0.929

0.897

0.864

0.833

0.802

0.772

0.744

0.716

0.689

0.663

100

0.946

0.912

0.880

0.848

0.817

0.787

0.758

0.730

0.703

0.676

0.651

The examples below will assist in determining the airflow performance of the product at altitude.

Example 1: What are the corrected CFM, static pressure, and BHP at an elevation of 5,000 ft. if the blower performance data is 6,000 CFM, 1.5 IWC and 4.0 BHP?

Solution: At an elevation of 5,000 ft the indoor blower will still deliver 6,000 CFM if the rpm is unchanged. However, Table 10 must be used to determine the static pressure and BHP. Since no temperature data is given, we will assume an air temperature of 70°F. Table 10 shows the correction factor to be 0.832.

Corrected static pressure = 1.5 x 0.832 = 1.248 IWC

Corrected BHP = 4.0 x 0.832 = 3.328

Example 2: A system, located at 5,000 feet of elevation, is to deliver 6,000 CFM at a static pressure of 1.5". Use the unit

blower tables to select the blower speed and the BHP requirement.

Solution: As in the example above, no temperature information is given so 70°F is assumed.

The 1.5" static pressure given is at an elevation of 5,000 ft. The first step is to convert this static pressure to equivalent sea level conditions.

Sea level static pressure = 1.5 / .832 = 1.80"

Enter the blower table at 6000 sCFM and static pressure of 1.8". The rpm listed will be the same rpm needed at 5,000 ft.

Suppose that the corresponding BHP listed in the table is 3.2. This value must be corrected for elevation.

BHP at 5,000 ft = 3.2 x .832 = 2.66

24

Unitary Products Group

Page 24
Image 24
York WR300, WR240 warranty Altitude Correction Factors, AIR Temp Altitude Feet

WR240, WR300 specifications

The York WR300 and WR240 are advanced water-cooled screw chillers that embody innovation, efficiency, and sustainability. These chillers are part of York’s renowned product line and are designed for a variety of commercial applications, ranging from large office buildings to industrial processes.

One of the standout features of the WR300 and WR240 models is their energy efficiency. Both units utilize the latest in variable-speed drive technology, which allows for precise control of the compressor speed based on the cooling demand. This results in lower energy consumption, especially in part-load conditions, making the chillers not only eco-friendly but also cost-effective over their lifespan.

The WR300 is designed to provide cooling capacities of up to 300 tons, while the WR240 offers capacities of up to 240 tons. These substantial capacities make them suitable for larger applications where dependable cooling is essential. The units are compact in design, allowing for flexible installation options, even in properties with space constraints.

Another key characteristic of the York WR chillers is their advanced refrigerant technology. Utilizing R-134a refrigerant, these chillers comply with global environmental standards and regulations, contributing to reduced greenhouse gas emissions. This makes the WR300 and WR240 not only high-performing but also aligned with a sustainable future.

The chillers are equipped with a robust control system that enhances operational performance and reliability. Features such as the advanced York YZ controller facilitate remote monitoring and diagnostics, allowing facility managers to optimize chiller performance and enhance maintenance processes. This advanced control capability minimizes downtime and maximizes productivity.

Noise reduction is also a significant consideration with these units. The WR series incorporates sound-dampening technology, making it an ideal choice for installations in noise-sensitive environments, such as schools or hospitals.

Furthermore, the construction of these chillers emphasizes durability and ease of maintenance. The components are engineered to withstand harsh operating conditions, and the design allows for straightforward access to key components, thereby simplifying service tasks.

In summary, the York WR300 and WR240 chillers stand out due to their energy efficiency, advanced refrigerant technology, robust control systems, and durability. These features make them ideal solutions for modern HVAC needs, supporting businesses while prioritizing environmental stewardship.