HEATING CAPACITY - With High Efficiency Motor Furnaces (Continued)
MODEL | FURNACE | COIL1 |
|
|
| ARI HEATING2 |
|
|
| ||
MODEL | MODEL |
| 47F |
|
|
|
| 17F |
| HSPF | |
|
|
| MBH | COP | KW |
| MBH |
| COP | KW | STD |
| T*(8,L)X*C16 | FC/PC60C | 47.0 | 3.46 | 3.98 |
| 32.8 |
| 2.28 | 4.22 | 8.00 |
| T*9X*C16 | FC/PC60C | 47.0 | 3.46 | 3.98 |
| 32.8 |
| 2.28 | 4.22 | 8.00 |
| T*(8,L)X*C20 | FC/MC/PC60D | 47.0 | 3.48 | 3.96 |
| 32.8 |
| 2.28 | 4.22 | 8.00 |
| T*9X*C20 | FC/PC60C | 47.0 | 3.48 | 3.96 |
| 32.6 |
| 2.30 | 4.15 | 8.00 |
| T*9X*D20 | FC/MC/PC60D | 46.5 | 3.50 | 3.89 |
| 32.2 |
| 2.32 | 4.07 | 8.10 |
| T*9X*D20 | FC/MC62D | 47.5 | 3.54 | 3.93 |
| 32.6 |
| 2.30 | 4.15 | 8.00 |
| T*(8,L)X*C16 | UC60C | 47.5 | 3.58 | 3.89 |
| 32.6 |
| 2.34 | 4.08 | 8.10 |
| T*(8,L)X*C20 | UC60D | 47.0 | 3.64 | 3.78 |
| 32.0 |
| 2.40 | 3.91 | 8.10 |
| T*9X*C16 | UC60C | 47.5 | 3.58 | 3.89 |
| 32.6 |
| 2.34 | 4.08 | 8.00 |
| T*9X*C20 | UC60C | 47.5 | 3.60 | 3.87 |
| 32.6 |
| 2.34 | 4.08 | 8.10 |
| T*9X*D20 | UC60D | 46.5 | 3.60 | 3.79 |
| 32.0 |
| 2.38 | 3.94 | 8.10 |
| (Y*9C/T*9V)*D20 | FC/MC/PC60D | 47.5 | 3.38 | 4.12 |
| 30.4 |
| 2.38 | 3.74 | 8.50 |
| (Y*9C/T*9V)*D20 | FC/MC62D | 48.0 | 3.44 | 4.09 |
| 30.2 |
| 2.40 | 3.69 | 8.50 |
YHJD48S41S1 | Y*(8,L)C*C16 | FC/PC60C | 47.5 | 3.40 | 4.09 |
| 30.4 |
| 2.40 | 3.71 | 8.50 |
Y*(8,L)C*C20 | FC/PC60C | 47.5 | 3.46 | 4.02 |
| 30.2 |
| 2.42 | 3.66 | 8.60 | |
|
|
| |||||||||
| (Y*9C/T*9V)*C16 | FC/PC60C | 48.0 | 3.38 | 4.16 |
| 30.6 |
| 2.38 | 3.77 | 8.50 |
| (Y*9C/T*9V)*C20 | FC/PC60C | 48.0 | 3.38 | 4.16 |
| 30.6 |
| 2.38 | 3.77 | 8.50 |
| (Y*9C/T*9V)*D20 | HC60 | 48.0 | 3.48 | 4.04 |
| 30.4 |
| 2.44 | 3.65 | 8.50 |
| Y*(8,L)C*C16 | HD60 | 47.0 | 3.22 | 4.28 |
| 30.2 |
| 2.24 | 3.95 | 8.40 |
| Y*(8,L)C*C20 | HD60 | 47.0 | 3.24 | 4.25 |
| 30.0 |
| 2.28 | 3.86 | 8.40 |
| (Y*9C/T*9V)*C16 | HD60 | 47.5 | 3.18 | 4.38 |
| 30.2 |
| 2.24 | 3.95 | 8.40 |
| (Y*9C/T*9V)*C20 | HD60 | 47.5 | 3.18 | 4.38 |
| 30.2 |
| 2.24 | 3.95 | 8.40 |
| (Y*9C/T*9V)*D20 | HD60 | 47.5 | 3.20 | 4.35 |
| 30.2 |
| 2.24 | 3.95 | 8.40 |
| Y*(8,L)C*C16 | UC60C | 47.5 | 3.46 | 4.02 |
| 30.2 |
| 2.42 | 3.66 | 8.50 |
| Y*(8,L)C*C20 | UC60C | 47.5 | 3.52 | 3.95 |
| 30.0 |
| 2.46 | 3.57 | 8.60 |
| (Y*9C/T*9V)*C16 | UC60C | 48.0 | 3.44 | 4.09 |
| 30.4 |
| 2.42 | 3.68 | 8.50 |
| (Y*9C/T*9V)*C20 | UC60C | 48.0 | 3.44 | 4.09 |
| 30.4 |
| 2.42 | 3.68 | 8.50 |
| (Y*9C/T*9V)*D20 | UC60D | 48.0 | 3.44 | 4.09 |
| 30.2 |
| 2.42 | 3.66 | 8.50 |
| T*(8,L)X*C20 | FC/MC62D | 56.5 | 3.60 | 4.60 |
| 32.6 |
| 2.46 | 3.88 | 8.10 |
| T*9X*D20 | FC/MC62D | 56.5 | 3.44 | 4.81 |
| 34.0 |
| 2.34 | 4.26 | 8.00 |
YHJD60S41S1 | (Y*9C/T*9V)*D20 | FC/MC/PC60D | 55.5 | 3.30 | 4.93 |
| 35.0 |
| 2.40 | 4.27 | 8.50 |
| Y*(8,L)C*C20 | FC/MC62D | 55.5 | 3.42 | 4.76 |
| 34.6 |
| 2.44 | 4.16 | 8.60 |
| (Y*9C/T*9V)*C20 | FC/MC62D | 56.0 | 3.36 | 4.88 |
| 35.0 |
| 2.40 | 4.27 | 8.60 |
1.Rated CFM same as for cooling.
2.Heating MBH based on ARI standards of 70° DB entering indoor air, 72% RH outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.
3.Variable speed furnaces have B.O.D (Blower on Delay) standard.
CP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period.
— = Not Applicable.
Johnson Controls Unitary Products | 17 |