TYPICAL INSTALLATION

 

MINIMUM 24” SERVICE

 

48” OVERHEAD

ACCESS CLEARANCE

THERMOSTAT

ON ONE SIDE

CLEARANCE

 

 

 

 

WEATHERPROOF

 

 

DISCONNECT

 

 

SWITCH

 

 

 

NEC CLASS 1 WIRING

10” CLEARANCE

 

TO FURNACE OR

AROUND PERIMETER

 

AIR HANDLER

 

 

TERMINAL BLOCK

 

 

NEC CLASS 2 WIRING

 

 

TO INDOOR COIL

NOTE:

 

 

ALL OUTDOOR WIRING

CONTROL

 

 

 

MUST BE WEATHERPROOF.

ACCESS

SEAL OPENING(S) WITH

 

 

PANEL

PERMAGUM OR EQUIVALENT

 

 

TYPICAL FIELD WIRING

ALL FIELD WIRING TO BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES

THERMOSTAT

R

B or C

Y

O

W

L or X

G

 

 

1 FIELD

2

T

INSTALLED

 

2

JUMPER

E

 

 

 

1 JUMPER TERMINALS E AND W TO HEAT

ON FIRST STAGE DURING EMERGENCY HEAT.

INDOOR UNIT

LOW VOLTAGE TERMINAL BLOCK 3,4 IN AIR HANDLER WITH ELECTRIC HEAT

R

C

Y

O

W2

G

W1

BK

DEHUMIDIFICATION CONTROL CONNECTION (Humidistat* Jumper must be removed)

OUTDOOR UNIT

DEFROST

CONTROL

RED

R

 

 

 

CONTACTOR

BLK

 

C

 

 

 

 

 

YEL

Y

T2

T1

 

 

 

ORG

O

 

M

 

 

 

BRN

W

L2

L1

 

 

 

 

PUR

X/L

 

 

WHT W1/66

 

 

5GRY CC

 

 

GND.

SCREW

2 TERMINAL NOT USED ON ALL THERMOSTATS.

POWER WIRING

24V CONTROL WIRING (NEC CLASS 2)

GND.

LUG

CIRCUIT BREAKER***

POWER WIRING

208/230-1-60

230-1-50

3CHECK THE LOW VOLTAGE TERMINAL BLOCK ON THE INDOOR UNIT FOR THE ACTUAL ARRANGEMENT OF THE TERMINALS.

4CONNECT POWER WIRING TO TERMINAL BLOCK 3TB ON UNITS WITHOUT ELECTRIC HEAT OR CIRCUIT BREAKER. 5GRAY FOR USE WITH OPTIONAL OUTDOOR THERMOSTAT KITS.

Johnson Controls Unitary Products

19

Page 19
Image 19
York YHJD18 warranty Typical Installation