![Manual background](/images/new-backgrounds/34931/3493139x1.webp)
HEATING PERFORMANCE DATA - LOW CFM
OUTDOOR UNIT MODEL NO. | YZE02411 |
|
|
|
|
|
|
|
| ||
INDOOR COIL MODEL NO. | FC/MC/PC36B + MV12B |
|
|
|
|
|
| ||||
AIR TEMP. | AIR TEMP. |
|
|
|
|
| ID CFM |
|
|
|
|
ENTERING | ENTERING |
|
|
|
|
|
|
|
|
|
|
|
| 550 |
|
| 600 |
|
| 650 |
| ||
OUTDOOR | INDOOR |
|
|
|
|
|
|
|
|
|
|
MBTUH |
| KW | C.O.P. | MBTUH | KW | C.O.P. | MBTUH | KW | C.O.P. | ||
UNIT | COIL |
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| 60 | 23.4 |
| 1.6 | 4.3 | 23.5 | 1.5 | 4.5 | 23.7 | 1.5 | 4.8 |
60 |
|
|
|
|
|
|
|
|
|
|
|
70 | 21.7 |
| 1.8 | 3.6 | 22.1 | 1.7 | 3.8 | 22.5 | 1.7 | 4.0 | |
|
|
|
|
|
|
|
|
|
|
|
|
| 80 | 20.1 |
| 2.0 | 3.0 | 20.7 | 1.9 | 3.2 | 21.4 | 1.9 | 3.4 |
|
|
|
|
|
|
|
|
|
|
|
|
| 60 | 19.5 |
| 1.5 | 3.8 | 19.5 | 1.4 | 4.0 | 19.6 | 1.4 | 4.1 |
47 |
|
|
|
|
|
|
|
|
|
|
|
70 | 18.8 |
| 1.7 | 3.2 | 18.9 | 1.7 | 3.3 | 19.0 | 1.6 | 3.4 | |
|
|
|
|
|
|
|
|
|
|
|
|
| 80 | 18.1 |
| 2.0 | 2.7 | 18.3 | 1.9 | 2.8 | 18.4 | 1.9 | 2.9 |
|
|
|
|
|
|
|
|
|
|
|
|
| 60 | 16.8 |
| 1.4 | 3.5 | 16.7 | 1.3 | 3.6 | 16.7 | 1.3 | 3.8 |
40 |
|
|
|
|
|
|
|
|
|
|
|
70 | 15.7 |
| 1.6 | 2.9 | 16.0 | 1.6 | 3.0 | 16.2 | 1.5 | 3.2 | |
|
|
|
|
|
|
|
|
|
|
|
|
| 80 | 14.6 |
| 1.8 | 2.4 | 15.2 | 1.8 | 2.5 | 15.8 | 1.7 | 2.7 |
|
|
|
|
|
|
|
|
|
|
|
|
| 60 | 15.4 |
| 1.3 | 3.4 | 15.4 | 1.3 | 3.5 | 15.5 | 1.3 | 3.6 |
30 |
|
|
|
|
|
|
|
|
|
|
|
70 | 14.4 |
| 1.5 | 2.8 | 14.4 | 1.5 | 2.9 | 14.5 | 1.4 | 3.0 | |
|
|
|
|
|
|
|
|
|
|
|
|
| 80 | 13.3 |
| 1.6 | 2.4 | 13.4 | 1.6 | 2.4 | 13.5 | 1.6 | 2.5 |
|
|
|
|
|
|
|
|
|
|
|
|
| 60 | 12.3 |
| 1.4 | 2.5 | 12.3 | 1.4 | 2.6 | 12.4 | 1.4 | 2.7 |
17 |
|
|
|
|
|
|
|
|
|
|
|
70 | 10.7 |
| 1.6 | 1.9 | 10.9 | 1.6 | 2.0 | 11.1 | 1.6 | 2.1 | |
|
|
|
|
|
|
|
|
|
|
|
|
| 80 | 9.2 |
| 1.8 | 1.5 | 9.5 | 1.8 | 1.5 | 9.8 | 1.8 | 1.6 |
|
|
|
|
|
|
|
|
|
|
|
|
| 60 | 10.5 |
| 1.4 | 2.2 | 10.7 | 1.4 | 2.3 | 10.8 | 1.3 | 2.4 |
10 |
|
|
|
|
|
|
|
|
|
|
|
70 | 9.4 |
| 1.5 | 1.8 | 9.6 | 1.5 | 1.9 | 9.8 | 1.5 | 2.0 | |
|
|
|
|
|
|
|
|
|
|
|
|
| 80 | 8.3 |
| 1.6 | 1.5 | 8.5 | 1.6 | 1.6 | 8.8 | 1.6 | 1.6 |
|
|
|
|
|
|
|
|
|
|
|
|
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor section.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
Air Handler | Coil | MBH | KW | COP |
AV24 | – | 1.00 | 1.00 | 1.00 |
AV36 | – | 1.00 | 1.00 | 1.00 |
MV12B | FC/MC30B | 1.00 | 1.00 | 1.00 |
MV12B | FC/MC35B | 1.00 | 1.00 | 1.00 |
MV12B | FC/MC36B | 1.00 | 1.00 | 1.00 |
MV12B | FC/MC42B | 1.00 | 1.00 | 1.00 |
MV16C | FC/MC35C | 1.00 | 1.00 | 1.00 |
MV16C | FC/MC42C | 1.00 | 1.00 | 1.00 |
Variable Speed | Coil | T.C. | S.C. | KW | |
Furnace | |||||
|
|
|
| ||
|
|
|
|
| |
PV8*A12 | FC/MC/PC30A | 0.95 | 0.96 | 0.99 | |
PV9*A12 | FC/MC/PC30A | 0.95 | 0.96 | 0.99 | |
P(C,V)9*B12 | FC/MC/PC30B | 0.95 | 0.96 | 0.99 | |
PV9*A12 | FC/MC/PC32A | 0.95 | 0.96 | 0.99 | |
P(C,V)9*B12 | FC/MC/PC35B | 0.95 | 0.96 | 0.99 | |
PV8*A12 | FC/MC/PC36A | 0.95 | 0.96 | 0.99 | |
PV9*A12 | FC/MC/PC36A | 0.95 | 0.96 | 0.99 | |
P(C,V)9*B12 | FC/MC/PC36B | 0.95 | 0.96 | 0.99 | |
P(C,V)9*B12 | FC/MC/PC42B | 0.95 | 0.96 | 0.99 | |
P(C,V)9*B12 | HC30 | 0.96 | 0.96 | 1.00 | |
P(C,V)9*B12 | HC36 | 0.95 | 0.96 | 0.99 | |
P(C,V)9*B12 | HD36 | 0.95 | 0.96 | 0.99 | |
PV8*A12 | UC30A | 0.95 | 0.96 | 0.99 | |
P(C,V)9*B12 | UC30B | 0.95 | 0.96 | 0.99 | |
PV8*A12 | UC36A | 0.95 | 0.96 | 0.99 | |
P(C,V)9*B12 | UC36B | 0.95 | 0.96 | 0.99 | |
P(C,V)9*B12 | UC42B | 0.95 | 0.96 | 0.99 |
20 | Johnson Controls Unitary Products |