345094-YTG-D-0108

COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION

OUTDOOR UNIT MODEL NO.

YZH03611

 

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

FC/MC62D + MV12D

 

 

 

 

 

 

 

 

 

 

 

CONDENSER

ID CFM

 

 

796

 

 

 

 

846

 

 

 

 

896

 

 

ENTERING AIR

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

 

T.C.

26.3

27.5

27.3

30.5

33.5

26.9

28.0

27.7

30.9

34.1

27.4

28.4

28.1

31.3

34.7

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

26.3

23.9

20.3

20.4

16.7

26.9

25.0

20.9

21.0

17.1

27.4

26.1

21.6

21.6

17.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W.

1.0

1.0

1.0

1.0

1.1

1.0

1.0

1.0

1.0

1.1

1.0

1.0

1.0

1.0

1.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

25.2

26.0

25.9

28.9

32.0

25.7

26.4

26.3

29.3

32.5

26.3

26.7

26.6

29.7

33.0

75

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

25.2

23.6

19.8

19.8

16.1

25.7

24.4

20.4

20.5

16.5

26.3

25.2

21.0

21.1

16.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W.

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

1.2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

24.1

24.5

24.5

27.4

30.5

24.6

24.8

24.8

27.8

30.8

25.2

25.0

25.1

28.1

31.2

85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

24.1

23.2

19.3

19.3

15.5

24.6

23.8

19.9

19.9

15.9

25.2

24.3

20.5

20.5

16.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W.

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

1.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

23.0

22.9

23.0

25.9

28.9

23.5

23.1

23.3

26.2

29.2

24.0

23.4

23.6

26.5

29.5

95

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

23.0

22.9

18.7

18.8

15.0

23.5

23.1

19.3

19.4

15.3

24.0

23.4

19.9

20.0

15.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W.

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

21.4

21.3

20.8

23.6

26.6

21.8

21.6

21.1

23.8

26.8

22.3

21.9

21.3

24.1

27.0

105

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

21.4

21.3

17.9

18.0

14.2

21.8

21.6

18.4

18.6

14.5

22.3

21.9

18.9

19.2

14.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W.

1.8

1.8

1.8

1.8

1.9

1.8

1.8

1.8

1.8

1.9

1.8

1.8

1.8

1.8

1.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

19.8

19.7

18.7

21.3

24.3

20.2

20.1

18.9

21.5

24.5

20.6

20.4

19.1

21.8

24.7

115

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

19.8

19.7

17.1

17.3

13.4

20.2

20.1

17.5

17.9

13.8

20.6

20.4

17.9

18.5

14.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W.

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

2.1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T.C.

18.2

18.2

16.5

19.1

22.0

18.6

18.6

16.7

19.2

22.1

19.0

19.0

16.9

19.4

22.3

125

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S.C.

18.2

18.2

16.4

16.5

12.6

18.6

18.6

16.6

17.1

13.0

19.0

19.0

16.9

17.7

13.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K.W.

2.3

2.3

2.3

2.3

2.3

2.3

2.3

2.3

2.3

2.3

2.3

2.3

2.3

2.3

2.3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.

LOW CFM

 

 

 

 

 

 

 

 

 

Air Handler

Coil

T.C.

S.C.

KW

 

 

 

 

 

AV36

-

0.98

0.97

0.97

AV/SV48

-

1.01

1.04

0.98

MV16C

FC/MC43C

0.97

0.93

0.95

MV16C

FC/MC48C

0.98

0.95

0.96

MV12D

FC/MC48D

0.97

0.91

0.96

MV12D

FC/MC60D

0.97

0.93

0.97

Variable Speed

Coil

T.C.

S.C.

KW

Furnace

 

 

 

 

P(C,V)8*B16

FC/MC/PC43B

0.96

0.92

0.95

P(C,V)8*C16

FC/MC/PC43C

0.93

0.84

0.94

P(C,V)8*C20

FC/MC/PC43C

0.96

0.93

0.94

P(C,V)9*B12

FC/MC/PC43B

0.96

0.93

0.94

P(C,V)9*C16

FC/MC/PC43C

0.97

0.93

0.97

P(C,V)9*C20

FC/MC/PC43C

0.97

0.94

0.95

P(C,V)8*C16

FC/MC/PC48C

0.94

0.86

0.95

P(C,V)8*C20

FC/MC/PC48C

0.97

0.94

0.95

P(C,V)9*C16

FC/MC/PC48C

0.98

0.94

0.97

P(C,V)9*C20

FC/MC/PC48C

0.98

0.95

0.95

P(C,V)9*D20

FC/MC/PC48D

0.98

0.95

0.96

P(C,V)8*C16

FC/PC60C

0.95

0.87

0.96

P(C,V)8*C20

FC/PC60C

0.98

0.96

0.96

P(C,V)9*C16

FC/PC60C

0.98

0.95

0.97

P(C,V)9*C20

FC/PC60C

0.98

0.96

0.96

P(C,V)9*D20

FC/MC/PC60D

0.97

0.95

0.96

P(C,V)8*C20

FC/MC62D

0.97

0.94

0.96

P(C,V)9*C20

FC/MC62D

0.98

0.95

0.96

P(C,V)9*D20

FC/MC62D

0.98

0.95

0.96

P(C,V)8*C16

HC42

0.93

0.85

0.94

P(C,V)8*C20

HC42

0.96

0.93

0.95

P(C,V)9*C16

HC42

0.97

0.93

0.97

P(C,V)9*C20

HC42

0.98

0.94

0.95

14

Unitary Products Group

Page 14
Image 14
York YZH024 THRU 060 warranty Indoor Coil Model no, FC/MC62D + MV12D