York YZH024 THRU 060 warranty Physical and Electrical Data, YTG-D-0108, Model, request

Models: YZH024 THRU 060

1 28
Download 28 pages 29.2 Kb
Page 2
Image 2

345094-YTG-D-0108

Physical and Electrical Data

MODEL

 

YZH02411

YZH03611

 

YZH04811

YZH06011

 

 

 

 

 

 

Unit Supply Voltage

 

 

208-230V, 1φ, 60Hz

 

 

 

 

 

 

 

Normal Voltage Range 1

 

 

 

187 to 252

 

Minimum Circuit Ampacity

18.2

23.6

 

29.2

34.8

 

 

 

 

 

 

Max. Overcurrent Device Amps 2

30

40

 

50

60

Min. Overcurrent Device Amps 3

20

25

 

30

35

Multi-stage Compressor

 

Yes

Yes

 

Yes

Yes

 

 

 

 

 

 

 

Compressor Type

 

Scroll

Scroll

 

Scroll

Scroll

 

 

 

 

 

 

 

Compressor Amps

Rated Load

12.3

16.6

 

21.1

25.6

 

 

 

 

 

 

Locked Rotor

52

82

 

96

118

 

 

 

 

 

 

 

 

 

Crankcase Heater

 

No

No

 

No

No

 

 

 

 

 

 

 

Fan Motor Amps

Rated Load

2.8

2.8

 

2.8

2.8

 

 

 

 

 

 

 

Fan Diameter Inches

 

24

24

 

24

24

 

 

 

 

 

 

 

 

Rated HP

1/3

1/3

 

1/3

1/3

Fan Motor

 

 

 

 

 

 

Nominal RPM

685

685

 

685

685

 

 

 

 

 

 

 

 

Nominal CFM

2,940

2,666

 

3,376

3,332

 

 

 

 

 

 

 

 

Face Area Sq. Ft.

23.58

23.58

 

23.58

23.58

Coil

 

 

 

 

 

 

Rows Deep

2

2

 

2

2

 

 

 

 

 

 

 

 

Fins / Inch

16

16

 

14

14

 

 

 

 

 

 

 

Liquid Line Set OD (Field Installed)

3/8

3/8

 

3/8

3/8

 

 

 

 

 

 

Vapor Line Set OD (Field Installed)

3/4

3/4

 

7/8

7/8

 

 

 

 

 

 

Unit Charge (Lbs. - Oz.) 4

14 - 12

12 - 7

 

12 - 13

14 - 8

Charge Per Foot, Oz.

 

0.62

0.62

 

0.67

0.67

 

 

 

 

 

 

 

Operating Weight Lbs.

 

275

275

 

280

315

 

 

 

 

 

 

 

1.Rated in accordance with ARI Standard 110, utilization range “A”.

2.Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.

3.Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection .

4.The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing. For tubing lengths other than 15 feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.

 

 

 

 

All dimensions are in inches. They are subject to change

 

 

 

 

without notice. Certified dimensions will be provided upon

 

 

 

 

request.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Dimensions

 

Refrigerant

 

 

 

 

 

 

Unit

 

 

Connection

 

 

 

 

 

 

 

 

(Inches)

 

 

 

 

 

 

 

Model

 

 

 

Service Valve Size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

 

B

 

C

Liquid

Vapor

 

 

 

A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

024

39-1/2

 

42

 

34

 

3/4”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

036

39-1/2

 

42

 

34

3/8”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

048

39-1/2

 

42

 

34

7/8”

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C

B

 

060

39-1/2

 

42

 

34

 

 

 

 

 

 

 

 

 

 

VAPOR

3-1/8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LIQUID

6-1/2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2-3/8

 

 

 

 

 

 

 

 

 

 

 

 

 

2

Unitary Products Group

Page 2
Image 2
York YZH024 THRU 060 warranty Physical and Electrical Data, YTG-D-0108, Model, request