345094-YTG-D-0108

HEATING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION

OUTDOOR UNIT MODEL NO.

YZH03611

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

FC/MC62D + MV12D

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AIR TEMP.

AIR TEMP.

 

 

 

 

 

ID CFM

 

 

 

 

ENTERING

ENTERING

 

 

 

 

 

 

 

 

 

 

 

 

759

 

 

809

 

 

859

 

OUTDOOR

INDOOR

 

 

 

 

 

 

 

 

 

 

MBTUH

 

KW

C.O.P.

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

UNIT

COIL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

60

31.2

 

1.8

4.9

31.5

1.8

5.1

31.8

1.8

5.3

60

 

 

 

 

 

 

 

 

 

 

 

70

30.7

 

2.1

4.2

30.9

2.1

4.4

31.2

2.0

4.5

 

 

 

 

 

 

 

 

 

 

 

 

 

80

30.2

 

2.4

3.7

30.4

2.3

3.8

30.5

2.3

3.9

 

 

 

 

 

 

 

 

 

 

 

 

 

60

23.5

 

1.7

4.1

23.6

1.6

4.2

23.7

1.6

4.4

47

 

 

 

 

 

 

 

 

 

 

 

70

23.1

 

1.9

3.5

23.1

1.9

3.6

23.2

1.8

3.7

 

 

 

 

 

 

 

 

 

 

 

 

 

80

22.7

 

2.2

3.1

22.7

2.1

3.2

22.7

2.0

3.2

 

 

 

 

 

 

 

 

 

 

 

 

 

60

19.4

 

1.6

3.6

19.5

1.5

3.7

19.6

1.5

3.8

40

 

 

 

 

 

 

 

 

 

 

 

70

19.2

 

1.8

3.1

19.3

1.8

3.2

19.4

1.7

3.3

 

 

 

 

 

 

 

 

 

 

 

 

 

80

19.0

 

2.0

2.7

19.1

2.0

2.8

19.1

2.0

2.9

 

 

 

 

 

 

 

 

 

 

 

 

 

60

14.0

 

1.5

2.8

14.0

1.4

2.9

14.1

1.4

2.9

30

 

 

 

 

 

 

 

 

 

 

 

70

14.0

 

1.7

2.4

14.0

1.6

2.5

14.1

1.6

2.6

 

 

 

 

 

 

 

 

 

 

 

 

 

80

13.9

 

1.9

2.2

14.0

1.8

2.2

14.0

1.8

2.3

 

 

 

 

 

 

 

 

 

 

 

 

 

60

7.6

 

1.3

1.7

7.6

1.3

1.7

7.7

1.3

1.8

17

 

 

 

 

 

 

 

 

 

 

 

70

7.8

 

1.5

1.5

8.0

1.5

1.6

8.2

1.5

1.6

 

 

 

 

 

 

 

 

 

 

 

 

 

80

8.1

 

1.7

1.4

8.4

1.7

1.4

8.7

1.7

1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

60

5.3

 

1.3

1.2

6.0

1.3

1.4

6.7

1.3

1.5

10

 

 

 

 

 

 

 

 

 

 

 

70

6.5

 

1.5

1.2

7.0

1.5

1.4

7.5

1.5

1.5

 

 

 

 

 

 

 

 

 

 

 

 

 

80

7.6

 

1.7

1.3

8.0

1.7

1.4

8.3

1.7

1.5

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.

LOW CFM

Air Handler

Coil

MBH

KW

COP

AV36

-

1.00

0.98

1.02

AV/SV48

-

1.00

0.97

1.03

MV16C

FC/MC43C

1.00

0.97

1.03

MV16C

FC/MC48C

1.00

0.97

1.03

MV12D

FC/MC48D

1.00

1.00

1.00

MV12D

FC/MC60D

1.00

1.00

1.00

Variable Speed

Coil

T.C.

S.C.

KW

Furnace

 

 

 

 

P(C,V)8*B16

FC/MC/PC43B

1.00

0.97

1.03

P(C,V)8*C16

FC/MC/PC43C

0.96

0.96

1.04

P(C,V)8*C20

FC/MC/PC43C

1.00

0.97

1.03

P(C,V)9*B12

FC/MC/PC43B

1.00

0.97

1.03

P(C,V)9*C16

FC/MC/PC43C

1.00

0.97

1.03

P(C,V)9*C20

FC/MC/PC43C

1.00

0.97

1.03

P(C,V)8*C16

FC/MC/PC48C

0.96

0.97

1.03

P(C,V)8*C20

FC/MC/PC48C

1.00

0.98

1.02

P(C,V)9*C16

FC/MC/PC48C

1.00

0.98

1.02

P(C,V)9*C20

FC/MC/PC48C

1.00

0.97

1.03

P(C,V)9*D20

FC/MC/PC48D

1.00

0.97

1.03

P(C,V)8*C16

FC/PC60C

0.96

0.97

1.03

P(C,V)8*C20

FC/PC60C

1.00

0.98

1.02

P(C,V)9*C16

FC/PC60C

1.00

0.98

1.02

P(C,V)9*C20

FC/PC60C

1.00

0.97

1.03

P(C,V)9*D20

FC/MC/PC60D

1.00

0.97

1.03

P(C,V)8*C20

FC/MC62D

1.00

0.98

1.02

P(C,V)9*C20

FC/MC62D

1.00

0.97

1.03

P(C,V)9*D20

FC/MC62D

1.00

0.97

1.03

P(C,V)8*C16

HC42

0.96

0.97

1.03

P(C,V)8*C20

HC42

1.00

0.98

1.02

P(C,V)9*C16

HC42

1.00

0.98

1.02

P(C,V)9*C20

HC42

1.00

0.97

1.03

22

Unitary Products Group