Baldor ID101F50-E manual Installation

Page 17

Caution: Separate over-current protection may be required by the National Electrical Code. The installer of this equipment is responsible for complying with the National Electrical Code and any applicable local codes which govern such practices as wiring protection, grounding, disconnects, and other current protection.

The inverter is self protected from normal AC line transients and surges. Additional external protection may be required if high energy transients are present on the incoming power source. These transients could be caused by sharing a power source with arc welding equipment, large motors being started across the line, or other industrial equipment requiring large surge currents. To prevent inverter damage due to power source disturbances the following should be considered:

1.Connect the inverter on a feeder line separate from those supplying large inductive loads.

2.Supply power to the inverter through a suitably sized isolation transformer. When using an isolation transformer to power the inverter, always switch the power off and on between the transformer secondary and the inverter input to avoid spikes at the inverter when power is removed from the primary side.

3.Supply power to the inverter through a suitably sized line reactor. Line reactors serve several purposes:

4.

A.Minimize voltage spikes from the power line that may cause the inverter to trip on over-voltage.

B.Minimize voltage harmonics from the inverter to the power line.

C.Provide additional short circuit capability at the inverter.

2-4 Installation

Image 17
Contents MN710 Series Inverter Control Installation and Operating ManualTable of Contents Level One Parameter Adjustments Min Output Frequency Appendix a Section General Information Limited WarrantySafety Notice General Information Nema SpecificationsElectronic Potentiometer Operator Keypad Fault ConditionsAnalog Outputs Relay OutputsAmps Volts RatingsCatalog No Input Output General Information Location and Mounting Section InstallationTerminal Access Cover Removal Terminal and Jumper Locations Wiring ConsiderationsInstallation Rated Input Input Fuses Catalog No Wire Size and Protection DevicesBreaker Fast Time AWG Cu Acting Delay Main Circuit Wiring AC Power Connections Motor Connections Typical Connections for M-Contactor ContactorAnalog Command Inputs Logic WiringExternal Trip Connection Analog OutputOpto Isolated Inputs Jumper J19 Selections Jumper J19 Input SelectionSelection Of Operation Mode And Connection Diagrams Function Wire Run/Stop ConnectionsSpeed Select Ramp Select PS2 PS1Parameter 21 Operating Mode = 4 or Parameter 21 Operating Mode = Wire Run/Stop, Electronic Potentiometer ConnectionsRelay Output MOL Terminal Connections 77-External Trip SelectAnalog Meter Installation Check of Motors/Couplings Pre-Operation ChecksCheck of Electrical Items Pre-Operation Check List Temporary Application of PowerInstallation Keypad Key Functions Section OperationOperation Status Indication Operating Condition Keypad Status IndicatorDescription of Keypad Displays Run Mode Symbol DescriptionStop Mode Security Access/Lockout Control Operation AdjustmentProgram Mode Level One Parameter Adjustments Start Control Type of Control Parameter 21-Operating Mode ValueCommand Control Terminals Description FWD REV PS1 PS2 Operation Operation Parameter 71-ANALOG Output Select Parameter 75-RELAY Output Select Value Description Level Two Parameter AdjustmentsOperation Operation Parameter 41-ACCEL/DECEL/COAST Select Value Description Operation Parameter 41-Parameter 47-DC Brake Time Braking Action / Function DC Braking DisabledLinear Volts/Hertz Profiles50% Square LawOperation Operation Description / Function Parameter 77-External Trip SelectParameter 81-Factory Settings Value Description Parameter 82-Start Options Value Description Command is given at the Control Terminal Strip Operation Diagnostic Displays Section TroubleshootingFault Codes Fault Code Description Troubleshooting MaintenanceIndication Possible Cause Corrective Action Motor overloadedOverload AdjustedSpeeds Input voltage too high Troubleshooting Illustrations Illustrations HP Nema 230 & 460VAC Illustrations Parameter List Appendix a ParametersParameter List ± Param Parameter Description Adj Factory User Range Setting Baldor Electric Company MN710 98 C&J2500 Box Fort Smith, AR 72902±2400 501 646±4711 Fax 501 648±5792Form 1099A

ID101F50-E specifications

The Baldor ID101F50-E is an advanced industrial electric motor designed for a variety of heavy-duty applications. Known for its robust construction and high efficiency, this motor is a preferred choice in manufacturing, conveyor systems, and automated machinery where reliability and performance are critical.

One of the primary features of the ID101F50-E is its outstanding efficiency rating. With high efficiency levels, it helps reduce energy consumption, which not only lowers operating costs but also aligns with modern demands for sustainability in industrial practices. The motor's efficiency contributes to a reduced carbon footprint, making it a more environmentally friendly option.

Another significant characteristic of the Baldor ID101F50-E is its high power output. This motor can deliver substantial torque, making it suitable for applications requiring heavy lifting and durable operation. Its design allows for continuous operation at high loads without overheating, which is essential for industries that rely on uninterrupted functionality.

In terms of construction, the ID101F50-E is built with high-quality materials that ensure durability and longevity. The robust housing and premium internal components assist in protecting the motor from harsh environmental conditions, making it well-suited for demanding industrial environments. Its rugged construction means it can withstand vibration, extreme temperatures, and exposure to contaminants.

The motor also incorporates advanced technologies that enhance its performance. For instance, it employs precision engineering techniques in its rotor and stator designs, which minimize losses during operation. This contributes to its overall high performance and reliability. Additionally, the ID101F50-E features advanced cooling mechanisms to maintain optimal operating temperatures, ensuring stability and longevity.

Further enhancing its usability, the Baldor ID101F50-E is designed for easy installation and maintenance. Its standard mounting configurations allow for straightforward integration into existing systems. Maintenance access is simplified, which reduces downtime and helps keep production schedules on track.

In conclusion, the Baldor ID101F50-E is a powerful electric motor that strikes an excellent balance between performance, efficiency, and durability. Its high efficiency, significant power output, robust construction, and advanced technologies make it an ideal choice for various industrial applications, standing as a testament to Baldor's commitment to innovation and quality in electric motor design.