Installation (Indoor)

15

 

 

NOTE

The heater requires two uninterrupted air supply openings; one for ventilation and one to supply oxygen for proper gas combustion. The air supply

b)Construct a non-combustible base from masonry blocks as illustrated, see Figure 14.

openings should be sized according to Table 2.

Air supply requirements below apply to all MiniMax NT Standard heaters*.

 

REQUIRED AIR SUPPLY

 

 

 

Model

Air for Combustion

Air Ventilation

 

Sq. In.

Sq. In.

 

 

 

200

200

200

 

 

 

250

250

250

 

 

 

300

300

300

BASE FOR USE ON COMBUSTIBLE FLOORS

SHEET METAL

BLOCKS

Figure 14.

 

.

 

in

"

M

 

6

 

. in M 6"

HOLLOW MASONARY BLOCKS, NOT LESS THAN 4" THICK (LAID WITH ENDS UNSEALED AND JOINTS MATCHED FOR AIR CIRCULATION). COVER BLOCKS WITH

24 GA. (MIN.) GALVANIZED SHEET METAL.

400

400

400

Table 2.

*NOTE

The openings listed in Table 2. are free open vent area—if the vents incorporate restrictive louvers, the vent openings must be increased to compensate for the area blocked by the louvers (or grills).

INSTALLATION ON FLOORS CONSTRUCTED OF COMBUSTIBLE MATERIALS

The heater may be placed on a “combustible floor” using either of the two methods listed below:

a)Use Listed Factory Non-combustible Base Kit for use on combustible floors.

Model

Non-Combustible Base Kit

 

 

200

471961

 

 

250

460509

 

 

300

471960

 

 

400

460508

 

 

CAUTION

Chemicals should not be stored near the heater installation. Combustion air can be contaminated by corrosive chemical fumes which can void the warranty.

INDOOR VENT ADAPTORS (FITS ALL MODELS)

The proper draft hood and adapter must be installed on the heater as shown below and on pages 13 and 14:

Part No.

Vent Dia.

 

 

460506

4 in.

 

 

460507

5 in.

 

 

Indoor Vent

Adaptor

Figure 15.

Rev. A 1-2-02

P/N 472032

Image 15
Contents For additional free copies of this manual call 800 MiniMax NT Standard SeriesTable of Contents Code Requirements MiniMax NT StandardWarranty Information Safety RulesOperation Operation Lighting For Your Safety Read Before LightingSpecifications Installation InstructionsELECTRICAL, for MiniMax NT Standard Heaters Installation ElectricalTWO-WIRE or THREE-WIRE Remote HOOK-UP Wire RemoteInstallation Remotes Three-wire remote Models HSI Electronic Installation DualWater Connections PlumbingPlumbing Connections GAS Connections Indoor VENTING-General Requirements Installation IndoorSee page 15 for Indoor Vent Adaptors Indoor Vent Adaptors Fits ALL Models Indoor InstallationVentilation Installation OutdoorGeneral Description Basic System OperationBasic Operation Typical Water Pressure Switch Safety ControlsAIR Pressure FAN Switch Water Pressure SwitchOperation of Ignition Module Normal Operation no Remote Minimax NT Standard Pentair Temperature ControllerGeneral Basic Thermostat OperationTo Change the Factory Temperature Settings Time SettingTemperature & Time Setting Programming Time Setting Programming Time SETTING, cont’dSpring and Fall Operation Maintenance InstructionsMaintenance Energy Saving TipsIf pH becomes too high over alkaline, it has these effects Maintenance Water TreatmentChemical Balance Pool and SPA WaterNormal Operation Sequence Troubleshooting-Normal Operation Sequence of HeaterTroubleshooting-Normal Operation of Heater Service CHECKS-IGNITION ModuleTroubleshooting & Service Heater Short Cycling Rapid On and Off Operation Troubleshooting GeneralMinimax NT Standard Heater Dual Voltage Description QTY MiniMax NT Standard Heaters Limited Warranty