Installation (Indoor) | 15 |
|
|
NOTE
The heater requires two uninterrupted air supply openings; one for ventilation and one to supply oxygen for proper gas combustion. The air supply
b)Construct a
openings should be sized according to Table 2.
Air supply requirements below apply to all MiniMax NT Standard heaters*.
| REQUIRED AIR SUPPLY | |
|
|
|
Model | Air for Combustion | Air Ventilation |
| Sq. In. | Sq. In. |
|
|
|
200 | 200 | 200 |
|
|
|
250 | 250 | 250 |
|
|
|
300 | 300 | 300 |
BASE FOR USE ON COMBUSTIBLE FLOORS
SHEET METAL
BLOCKS
Figure 14.
| . |
| in |
" | M |
| |
6 |
|
. in M 6"
HOLLOW MASONARY BLOCKS, NOT LESS THAN 4" THICK (LAID WITH ENDS UNSEALED AND JOINTS MATCHED FOR AIR CIRCULATION). COVER BLOCKS WITH
24 GA. (MIN.) GALVANIZED SHEET METAL.
400 | 400 | 400 |
Table 2.
*NOTE
The openings listed in Table 2. are free open vent
INSTALLATION ON FLOORS CONSTRUCTED OF COMBUSTIBLE MATERIALS
The heater may be placed on a “combustible floor” using either of the two methods listed below:
a)Use Listed Factory
Model | |
|
|
200 | 471961 |
|
|
250 | 460509 |
|
|
300 | 471960 |
|
|
400 | 460508 |
|
|
CAUTION
Chemicals should not be stored near the heater installation. Combustion air can be contaminated by corrosive chemical fumes which can void the warranty.
INDOOR VENT ADAPTORS (FITS ALL MODELS)
The proper draft hood and adapter must be installed on the heater as shown below and on pages 13 and 14:
Part No. | Vent Dia. |
|
|
460506 | 4 in. |
|
|
460507 | 5 in. |
|
|
Indoor Vent
Adaptor
Figure 15.
Rev. A | P/N 472032 |