Pentair NT Standard Series installation manual Installation, Indoor

Page 16

P/N 472032

INDOOR INSTALLATIONS

MINIMAX NT STANDARD VENTING GUIDELINES

Installation

vent terminated at least 24" above

any object within 10 ft.

10 ft.

Vent

Ridge

Cap

 

2 ft. min.

 

3 ft. min.

J

 

K

Detail H

L

Chimney

Vent for roof penetration installations:

Jmust extend at least 3 ft. higher than the point at which it passes through the roof, or as permitted by local code.

K must use a double-wall vent pipe through

the roof penetration.

H

E Air Supply

Ventilation

4'

Vent Hood

Air Supply

A Combustion

7'

F 1' min.

 

 

1' min.

 

Vent Hood

F

 

 

G

B

C

3'

4' D

 

 

 

 

1' min.

Vent Hood

 

above grade

G

(Indoor)

Rev

L must terminate with an approved (listed)

roof jack, storm collar, and vent/weather cap.

Vent pipe extension:

must be the same diameter as the vent connector.

must be suitable for use with category III appliances which have flue gas temperatures of less than 400 deg. F.

may use a single wall vent pipe with

Walkway

Recommended sources for

side wall Vent Hood; see page 15, Section Venting.

Vent termination for side wall installations:

Amust be not less than 7 ft. above public walkways.

Bmust be at least 3 ft. above any outside air intake located within a 10 ft. radius.

must NOT be within 3 ft. of an inside corner of the structure.

C must be at least 1 ft. above grade.

must be located the following distances away from any door, window, or gravity air inlet:

D4 ft. below

E4 ft. horizontally

F1 ft. above

. A

permanently sealed seams and joints.

Air Supply

Figure 16.

16

1-2-02

G See Air Supply Requirements Table.

(Table 2. on page 15.)

Image 16
Contents MiniMax NT Standard Series For additional free copies of this manual call 800Table of Contents MiniMax NT Standard Code RequirementsSafety Rules Warranty InformationOperation For Your Safety Read Before Lighting Operation LightingInstallation Instructions SpecificationsInstallation Electrical ELECTRICAL, for MiniMax NT Standard HeatersWire Remote TWO-WIRE or THREE-WIRE Remote HOOK-UPInstallation Remotes Three-wire remote Installation Dual Models HSI ElectronicPlumbing Water ConnectionsPlumbing Connections GAS Connections Installation Indoor Indoor VENTING-General RequirementsSee page 15 for Indoor Vent Adaptors Indoor Vent Adaptors Fits ALL Models Installation IndoorInstallation Outdoor VentilationBasic System Operation General DescriptionBasic Operation Safety Controls AIR Pressure FAN SwitchWater Pressure Switch Typical Water Pressure SwitchOperation of Ignition Module Minimax NT Standard Pentair Temperature Controller GeneralBasic Thermostat Operation Normal Operation no RemoteTime Setting To Change the Factory Temperature SettingsTemperature & Time Setting Programming Time SETTING, cont’d Time Setting ProgrammingMaintenance Instructions MaintenanceEnergy Saving Tips Spring and Fall OperationMaintenance Water Treatment Chemical BalancePool and SPA Water If pH becomes too high over alkaline, it has these effectsTroubleshooting-Normal Operation Sequence of Heater Normal Operation SequenceService CHECKS-IGNITION Module Troubleshooting-Normal Operation of HeaterTroubleshooting & Service Troubleshooting General Heater Short Cycling Rapid On and Off OperationMinimax NT Standard Heater Dual Voltage Description QTY MiniMax NT Standard Heaters Limited Warranty