Pentair NT Standard Series installation manual Ventilation, Installation Outdoor

Page 17

Installation (Outdoor)

17

 

 

VENTILATION

OUTDOOR INSTALLATION ONLY (Outdoor Shelter Installation in Canada, see page 14)

For outdoor installation with built in vent, the heater must be placed in a suitable area on a level, noncombustible surface. Do not install the heater under an overhang with clearances less than 3 feet from the top of the heater. The area under an overhang must be open on three sides.

IMPORTANT!

In an outdoor installation it is important to ensure water is diverted from overhanging eves with a proper gutter/drainage system. The heater must be set on a level foundation for proper drainage.

Maintain minimum clearances as indicated below. Install a minimum of 4 feet below, and 4 feet horizontally from any opening to a building, see Figure 17.

IMPORTANT!

When locating the heater, consider that high winds can roll over or deflect off adjacent buildings and walls. Normally, placing the heater at least three feet from any wall will minimize downdraft.

NOTE

This unit shall not be operated outdoors at temperatures below -20oF. for natural gas.

OUTDOOR INSTALLATION

MINIMAX NT VENTING GUIDELINES

Walkway

 

A

 

D

1'

B

3'

 

 

 

4'

C

4'

4'

Property Line

E

ECheck local building codes for setback requirements.

Figure 17.

Vent Termination:

Must be not less than 7 ft. above public walkways.

AMust be at least 3 ft. above any forced air inlet located within a 10 ft. radius.

Must be located the following distances away from any door, window, or gravity air inlet:

B4 ft. below, or

C4 ft. horizontally, or

D1 ft. above

Rev. A 1-2-02

P/N 472032

Image 17
Contents For additional free copies of this manual call 800 MiniMax NT Standard SeriesTable of Contents Code Requirements MiniMax NT StandardOperation Warranty InformationSafety Rules Operation Lighting For Your Safety Read Before LightingSpecifications Installation InstructionsELECTRICAL, for MiniMax NT Standard Heaters Installation ElectricalInstallation Remotes TWO-WIRE or THREE-WIRE Remote HOOK-UPWire Remote Three-wire remote Models HSI Electronic Installation DualPlumbing Connections Water ConnectionsPlumbing GAS Connections Indoor VENTING-General Requirements Installation IndoorSee page 15 for Indoor Vent Adaptors Indoor Vent Adaptors Fits ALL Models Indoor InstallationVentilation Installation OutdoorBasic Operation General DescriptionBasic System Operation AIR Pressure FAN Switch Safety ControlsWater Pressure Switch Typical Water Pressure SwitchOperation of Ignition Module General Minimax NT Standard Pentair Temperature ControllerBasic Thermostat Operation Normal Operation no RemoteTemperature & Time Setting Programming To Change the Factory Temperature SettingsTime Setting Time Setting Programming Time SETTING, cont’dMaintenance Maintenance InstructionsEnergy Saving Tips Spring and Fall OperationChemical Balance Maintenance Water TreatmentPool and SPA Water If pH becomes too high over alkaline, it has these effectsNormal Operation Sequence Troubleshooting-Normal Operation Sequence of HeaterTroubleshooting-Normal Operation of Heater Service CHECKS-IGNITION ModuleTroubleshooting & Service Heater Short Cycling Rapid On and Off Operation Troubleshooting GeneralMinimax NT Standard Heater Dual Voltage Description QTY MiniMax NT Standard Heaters Limited Warranty