Pentair NT Standard Series installation manual Normal Operation Sequence

Page 26

Troubleshooting—Normal Operation Sequence of Heater

26

 

 

NORMAL OPERATION SEQUENCE

(Refer to Figure 20 of Pentair Temperature Controller 7800 keyboard)

The heater features a fully automated firing start-up and shutdown sequence under the control of the MiniMax NT Standard Pentair Temperature Controller 7800.

Now that the heater has been properly installed and wired for either remote operation or local operation, and you have setup the Pentair Temperature Controller 7800 temperature setpoints as described earlier in manual in Thermostat section, the following is the normal operating sequence when the heater turns on the and the thermostat calls for heat for the pool or spa.

1.The fan will start beginning the heater’s safety prepurging cycle which lasts for 1 minute. If at anytime during the prepurge cycle the Pentair Temperature Controller 7800 detects that a safety control is not working due to either a safety control malfunction or other unsafe condition the firing sequence will stop until the unsafe condition is removed— “the fault icon related to the problem will illuminate”.

2.After proper completion of the prepurge cycle, the hot surface ignitor (glow coil) will turn on (preheat) for 40 seconds. Once the 40 seconds is passed, the main gas valve will open and the heater will fire. At this time, if flame is not safely established as detected by the flame sensing circuit, the ignition module and Pentair Temperature Controller 7800 will shut down and will display an ignition fault and luminate the red service light. Please note that on initial firing of heater when gas supply piping is full of air or after long period of non-operation of the heater it is normal for the first ignition attempt to not complete. To clear the fault condition power to the Pentair Temperature Controller 7800 must be cycled to reset system. If heater continues to fail to light have heater inspected by a qualified service person before placing heater back in service.

Insufficient waterflow (pump icon displays), excessive water temperature (high limit icon) cause a “soft-lockout” of the firing sequence—which means if the cause of the problem clears by itself (or with human intervention ie., turning on pump, etc.) such as a slow to prime water pump finally pumping adequate waterflow causing the water pressure (safety) switch to close, the ignition sequence automatically restarts again.

The other category of fault conditions lead to a “hard lockout” of the firing sequence which require a qualified service person to correct before the heater is returned to service. In “hard lockout” the heater must be manually reset (by toggling power to Pentair Temperature Controller 7800) after correction of the fault condition.

3.After normal firing of the heater (main burners) the heater will continue to operate until the temperature setpoint is reached (thermostat satisfied). As the pool/spa loses heat the heater will refire and continue to operate cycling automatically to maintain the selected temperature setpoint for either the pool or spa. If at anytime during the firing of the heater an unsafe condition is detected the heater will stop firing and an automatic safe shutdown sequence will begin. Investigate and have corrected the cause of the abnormal firing termination before placing heater back in operation.

Please Note: During the firing of the heater, you decide to change to the pool or spa selection by depressing the selector key for “POOL” or “SPA”, the heater will first acknowledge the new selection by flashing the new selection’s corresponding selection LED “POOL” or “SPA”, however, the heater will first complete a safe shutdown sequence before automatically switching to the new selected setting and safely initiating a new firing sequence using the new temperature setpoint. During this automatic crossover sequence the keyboard on the Pentair Temperature Controller 7800 will not accept any further keying until the cycle completes—the exception is you may still stop the heater with the “OFF” key.

P/N 472032

Rev. A 1-2-02

Image 26
Contents MiniMax NT Standard Series For additional free copies of this manual call 800Table of Contents MiniMax NT Standard Code RequirementsOperation Warranty InformationSafety Rules For Your Safety Read Before Lighting Operation LightingInstallation Instructions SpecificationsInstallation Electrical ELECTRICAL, for MiniMax NT Standard HeatersInstallation Remotes TWO-WIRE or THREE-WIRE Remote HOOK-UPWire Remote Three-wire remote Installation Dual Models HSI ElectronicPlumbing Connections Water ConnectionsPlumbing GAS Connections Installation Indoor Indoor VENTING-General RequirementsSee page 15 for Indoor Vent Adaptors Indoor Vent Adaptors Fits ALL Models Installation IndoorInstallation Outdoor VentilationBasic Operation General DescriptionBasic System Operation Water Pressure Switch Safety ControlsAIR Pressure FAN Switch Typical Water Pressure SwitchOperation of Ignition Module Basic Thermostat Operation Minimax NT Standard Pentair Temperature ControllerGeneral Normal Operation no RemoteTemperature & Time Setting Programming To Change the Factory Temperature SettingsTime Setting Time SETTING, cont’d Time Setting ProgrammingEnergy Saving Tips Maintenance InstructionsMaintenance Spring and Fall OperationPool and SPA Water Maintenance Water TreatmentChemical Balance If pH becomes too high over alkaline, it has these effectsTroubleshooting-Normal Operation Sequence of Heater Normal Operation SequenceService CHECKS-IGNITION Module Troubleshooting-Normal Operation of HeaterTroubleshooting & Service Troubleshooting General Heater Short Cycling Rapid On and Off OperationMinimax NT Standard Heater Dual Voltage Description QTY MiniMax NT Standard Heaters Limited Warranty