Generac QT 5.4L owner manual Maintenance Owner Operator can Perform

Page 18

Standby Generator Sets

Maintenance

‹ENGINE COOLANT

Check coolant level in coolant recovery bottle. See the “Specifications” section.

Add recommended coolant mixture as necessary.

Periodically remove radiator pressure cap to make sure the coolant recovery system is functioning properly. Coolant should be at bottom of radiator filler neck. If coolant level is low, inspect gasket in radiator pressure cap. Replace cap, if necessary. To have pressure cap tested, contact an Authorized Service Dealer. Inspect cooling system and coolant recovery system for leaks.

MAINTENANCE OWNER/

OPERATOR CAN PERFORM

‹CHECK ENGINE OIL LEVEL

Refer to the “Checking Fluid Levels” section.

‹CHECK BATTERY

Check battery fluid level each week as outlined under “Check Fluid Levels”.

Check battery cables for condition, tightness, cor- rosion or damage. Clean, tighten or replace as necessary.

‹EXERCISE SYSTEM

Start the generator engine at least once every seven days and let it run at least 20 minutes. See the “Weekly Exercise Cycle” section.

‹CHECK FAN BELT

Inspect fan belts every three months. Replace any damaged, deteriorated, worn or otherwise defec- tive belt.

Check fan belt tension. Thumb pressure, exerted midway between pulleys, should deflect about 3/8 to 5/8 inch. Adjust belt tension as required.

‹INSPECT ENGINE GOVERNOR

Visually inspect electronic governor.

DANGER

Do not attempt to adjust the governor. Only qualified service facilities should adjust the governor. Excessively high operating speeds are dangerous and increase the risk of personal injury. Low speeds impose a heavy load on the engine when adequate engine power is not available and may shorten engine life. Correct rated frequency and voltage are supplied only at the proper governed speed. Some connected electrical load devices may be damaged by incor- rect frequency and/or voltage. Only qualified service technicians should adjust the governed speed.

‹CHANGING ENGINE OIL

Refer to maintenance performed by authorized ser- vice facilities for engine oil and filter change frequen- cies.

Drain the oil while the engine is still warm from run- ning. This means warm up the engine, shut it down and drain immediately as follows:

‹INSPECT COOLING SYSTEM

Inspect engine cooling system at least once each month.

Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.

Check hose clamps for tightness.

‹CHECK ENGINE COOLANT LEVEL

See the “Checking Fluid Levels” section.

‹PERFORM VISUAL INSPECTION

Complete a thorough visual inspection of the entire engine-generator monthly. Look for obvious damage, loose, missing or corroded nuts, bolts and other fas- teners. Look for fuel, oil or coolant leaks.

1.Remove OIL DRAIN HOSE from its retaining clip.

2.Loosen and remove OIL DRAIN HOSE CAP. Drain oil completely into suitable container.

3.When all oil has drained, install and tighten OIL DRAIN HOSE CAP, and re-install into its retaining clip.

4.Turn OIL FILTER (Figure 10.2) counterclockwise and remove. Dispose of old filter.

5.Apply light coating of new engine oil to seal of new oil filter.-Install FILTER and tighten by hand only.

DO NOT OVERTIGHTEN.

6.Remove OIL FILL CAP. Add recommended oil (see

SPECIFICATIONS). DO NOT FILL ABOVE THE DIPSTICK “FULL” MARK. Crankcase oil capacity is listed in the “Specifications”.

‹INSPECT EXHAUST SYSTEM

Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.

08/05

0 .Rev Maint003

After refilling the crankcase with oil, always check oil level on dipstick. NEVER OPERATE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK.

10-2

Image 18
Contents QT 5.4L 100kW Models Standby Generator Sets Table of Contents  Warning   Electrical Hazards  Authorized Service Dealer Location ‹ Operation and Maintenance‹ HOW to Obtain Service IntroductionIdentification Record ‹ Data LabelEquipment Description Engine OIL RecommendationsCoolant Recommendations Engine Protective Devices ‹ Natural GAS Fuel System Fuel System‹ Fuel Requirements ‹ LP Fuel SystemSpecifications ‹ Cold Weather KIT Interconnections‹ Ignition Enable 14 Line Input ‹ Ignition POWER-UP Input 56 Line Input‹ Ignition Shutdown on Loss of Crank or CAM Signals 4L & 6.8L Ignition Description‹ 3-PHASE Alternators Alternator Power Winding Connections‹ FOUR-LEAD, SINGLE-PHASE Stator Generator AC Lead ConnectionsInstallation Preparation Before START-UPInitial Inspection for QT Genset Startup START-UP Checklist ‹ Preparation for START-UP‹ START-UP Inspection ‹ Engine START-UP and Transfer Operating Unit with Manual Transfer SwitchGenerator Control Operation ‹ Retransfer and ShutdownCooling System Checking Fluid LevelsMaintenance Owner Operator can Perform ‹ Cleaning the Generator Miscellaneous Maintenance‹ Changing the Engine AIR Cleaner ‹ Spark Plugs‹ Battery Maintenance Repair Parts‹ Battery ‹ Battery ReplacementService Schedule KW 150 KW Standby GAS Engine Driven Generator SetsMaintenance Level 11-3 11-4 Troubleshooting Guide Problem Cause CorrectionStandby Generator Sets Standby Generator Sets Page Assy Rotor 2390 80KB3 CPL Page Panel CB Conn BOX Page UL Circuit Breaker 225AF Page STAND, RH Control CPL C5 Page Washer Lock M10 Page MTG Base CP 5.4L 100KW DD Page Tray Battery Page Components Included in 0F1826E Page Pipe EXH Manifold 4.6L LH Page AIR Clnr BTM PLT W/CPLR 8.1L Page Tube Heater Water Page Starter 12 Volt Page Support NAT GAS Solenoid Page Support NAT GAS Solenoid Page Rear Wrap C5 Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Standby Generator Sets Warranty