Generac QT 5.4L owner manual Repair Parts, ‹ Battery Maintenance, ‹ Battery Replacement

Page 20

Standby Generator Sets

Maintenance

Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are excessively low, the generator may require drying.

‹BATTERY

All lead-acid storage batteries discharge when not in use. Refer to specific instructions and warnings that accompany the battery. If such information is not available, observe the following precautions when handling a battery:

DO NOT use jumper cables and a booster battery to crank or start the generator engine.

DO NOT recharge a weak battery while it is installed in the generator. Remove battery from generator and recharge in a well-ventilated area, away from fuel vapors, sparks, heat or flames.

Battery electrolyte fluid is an extremely caustic sulfuric solution that can cause severe burns. DO NOT permit fluid to contact eyes, skin, clothing, painted surfaces, wiring insulation, etc. If any bat- tery fluid is spilled, flush the affected area with clear water immediately.

Always wear safety glasses, rubber apron and gloves when handling a battery.

Batteries give off explosive hydrogen gas while charging. The gas can form an explosive mixture around the battery for several hours after charging. Any spark, heat or flames can ignite the gas and cause an explosion which can shatter the battery, causing blindness or other serious injury.

‹BATTERY MAINTENANCE

The battery should be inspected per the “Service Schedule” section. The following procedure should be followed for inspection:

1.Inspect the battery posts and cables for tightness and corrosion. Tighten and clean as necessary.

2.Check the battery fluid level of unsealed batteries and, if necessary, fill with DISTILLED WATER ONLY. DO NOT USE TAP WATER IN BATTER- IES.

DANGER

Storage batteries give off explosive hydrogen gas. This gas can form an explosive mixture around the battery for several hours after charg- ing. The slightest spark can ignite the gas and cause an explosion. Such an explosion can shat- ter the battery and cause blindness or other injury. Any area that houses a storage battery must be properly ventilated. Do not allow smok- ing, open flame, sparks or any spark producing tools or equipment near the battery.

Battery electrolyte fluid is an extremely caus- tic sulfuric acid solution that can cause severe burns. Do not permit fluid to contact eyes, skin, clothing, painted surfaces, etc. Wear protective goggles, protective clothing and gloves when handling a battery. If the fluid is spilled, flush the affected area immediately with clear water.

Do not use any jumper cables or booster battery to crank and start the generator engine. If the battery has completely discharged, remove it from the generator for recharging.

Be sure the AUTO/OFF/MANUAL switch is set to the OFF position before connecting the battery cables. If the switch is set to AUTO or MANUAL, the generator can crank and start as soon as the battery cables are connected.

Be sure the 120VAC power supply to the battery is turned OFF, or sparking may occur at the bat- tery posts as the cables are attached and cause an explosion.

‹BATTERY REPLACEMENT

When replacing batteries, use the same number and the type of battery that follows:

 

BCI Group No.

CCA

 

 

24F-6

525 @ 0 deg. F

 

 

 

 

 

3.Have the state of charge and condition checked. This should be done with an automotive-type bat- tery hydrometer.

NOTE:

The BCI number should be located directly on the battery.

REPAIR PARTS

The latter portion of this manual consists of exploded views, parts lists and electrical data pertaining to this generator set. The parts lists consist of (a) an item number, (b) a part number, (c) the quantity required, and (d) a description of the part. The item number corresponds to an identical number on the exploded view drawing.

08/05

0 .Rev Maint003

10-4

Image 20
Contents QT 5.4L 100kW Models Standby Generator Sets Table of Contents  Warning   Electrical Hazards  ‹ Operation and Maintenance ‹ HOW to Obtain ServiceAuthorized Service Dealer Location IntroductionIdentification Record ‹ Data LabelCoolant Recommendations Equipment DescriptionEngine OIL Recommendations Engine Protective Devices Fuel System ‹ Fuel Requirements‹ Natural GAS Fuel System ‹ LP Fuel SystemSpecifications ‹ Cold Weather KIT Interconnections‹ Ignition POWER-UP Input 56 Line Input ‹ Ignition Shutdown on Loss of Crank or CAM Signals‹ Ignition Enable 14 Line Input 4L & 6.8L Ignition DescriptionAlternator Power Winding Connections ‹ FOUR-LEAD, SINGLE-PHASE Stator‹ 3-PHASE Alternators Generator AC Lead ConnectionsInitial Inspection for QT Genset Startup InstallationPreparation Before START-UP ‹ START-UP Inspection START-UP Checklist‹ Preparation for START-UP Operating Unit with Manual Transfer Switch Generator Control Operation‹ Engine START-UP and Transfer ‹ Retransfer and ShutdownCooling System Checking Fluid LevelsMaintenance Owner Operator can Perform Miscellaneous Maintenance ‹ Changing the Engine AIR Cleaner‹ Cleaning the Generator ‹ Spark PlugsRepair Parts ‹ Battery‹ Battery Maintenance ‹ Battery ReplacementService Schedule KW 150 KW Standby GAS Engine Driven Generator SetsMaintenance Level 11-3 11-4 Troubleshooting Guide Problem Cause CorrectionStandby Generator Sets Standby Generator Sets Page Assy Rotor 2390 80KB3 CPL Page Panel CB Conn BOX Page UL Circuit Breaker 225AF Page STAND, RH Control CPL C5 Page Washer Lock M10 Page MTG Base CP 5.4L 100KW DD Page Tray Battery Page Components Included in 0F1826E Page Pipe EXH Manifold 4.6L LH Page AIR Clnr BTM PLT W/CPLR 8.1L Page Tube Heater Water Page Starter 12 Volt Page Support NAT GAS Solenoid Page Support NAT GAS Solenoid Page Rear Wrap C5 Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Page Standby Generator Sets Warranty