Generac QT04524ANSX Specifications, Stationary Emergency Generator, Engine, Cooling System

Page 10

Specifications

SPECIFICATIONS

STATIONARY EMERGENCY GENERATOR

Type

Synchronous

Rotor Insulation

Class H

Stator Insulation

Class H

Telephone Interference Factor (TIF)

< 50

Alternator Output Leads 3-phase

4-wire

Bearings

Sealed Ball

Coupling

Flexible Disc

Load Capacity (Standby Rating)

45kW*

*NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349, ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural gas.

Excitation System

 

Direct

Generator Output Voltage/kW - 60 Hz

kW

Amp

CB Size

120/240V, 1-phase, 1.0 pf

45

188

200

120/208V, 3-phase, 0.8 pf

45

156

175

120/240V, 3-phase, 0.8 pf

45

135

150

277/480V, 3-phase, 0.8 pf

45

68

80

Generator Locked Rotor KVA Available @ Voltage Dip of 35%

Single-phase or 208, 3-phase (45kW)

 

72 KVA

480V, 3-phase (45kW)

 

80 KVA

ENGINE

Make

Generac

Model

In Line

Cylinders and Arrangement

4

Displacement

2.4 Liter

Bore

3.41 in.

Stroke

3.94 in.

Compression Ratio

9.5-to-1

Air Intake System

Naturally Aspirated

Valve Seats

Hardened

Lifter Type

Hydraulic

Spark Plug Gap

1.07-1.17mm (0.042-0.046 inch)

Engine Parameters

 

 

Rated Synchronous RPM

60 Hz, 3600

Exhaust System

 

 

Exhaust Flow at Rated Output 60 Hz (45kW)

..................... 420 cfm

Exhaust Temp. at Rated Output (45kW)

1100° F

Combustion Air Requirements (Natural Gas)

Flow at rated power, 60 Hz (45kW)

144 cfm

Governor

 

 

Type

Electronic

Frequency Regulation

Isochronous

Steady State Regulation

± 0.25%

Engine Lubrication System

Type of Oil Pump

Gear

Oil Filter

Full Flow Spin-on, Cartridge

Crankcase Oil Capacity

5.25 U.S. qts. (including filter capacity)

COOLING SYSTEM

Type

Pressurized Closed Recovery

Water Pump

Belt Driven

Fan Speed

2150 rpm

Fan Diameter

22 inches

Fan Mode

Puller

Air Flow (inlet air...........................................................including alternator and

2725 ft3/min.

combustion air)

 

Coolant Capacity

(3.0 U.S. gal.)

Heat Rejection to Coolant (45kW)

193,000 Btu/h

Maximum Operating Air Temp. on Radiator

60° C (150° F)

Maximum Ambient Temperature

50° C (140° F)

FUEL SYSTEM

Type of Fuel

Natural Gas, Propane Vapor

Carburetor

 

 

Down Draft

Secondary Fuel Regulator

 

Standard

Fuel Shut-off Solenoid

 

Standard

Operating Fuel Pressure

5 in. - 14 in. Water Column

Fuel Consumption - ft3/hr (Natural Gas/LPV)

 

Exercise

25%

50%

75%

100%

 

Cycle

Load

Load

Load

Load

45kW

65/25

210/83

380/151

545/216

730/290

ELECTRICAL SYSTEM

 

 

 

Battery Charge Alternator

12V, 30 Amp

Static Battery Charger

 

2.5 Amp

Recommended Battery

Group 26, 525CCA

System Voltage

 

 

12 Volts

Voltage Regulator

 

 

 

 

Type

 

 

 

Electronic

Sensing

 

 

Single-phase

Regulation

 

 

± 1%

Features

 

Adjustable Voltage and Gain

Power Adjustment for Ambient Conditions

 

Temperature Deration

 

 

 

3% for every 10° C above °C (45kW)

25

1.65% for every 10° above °F (45kW)

77

Altitude Deration

 

 

 

 

1% for every 100 m above m (45kW)

183

3% for every 1000 ft. above ft. (45kW)

600

Controller

 

 

Nexus

6-1

05/10 A .Rev GenSpec084

Image 10
Contents Stationary Emergency Generator Table of Contents Introduction Operation and MaintenanceHOW to Obtain Service Read this Manual ThoroughlySafety Rules General HazardsFire Hazards Identification Record Data LabelEngine OIL Recommendations Equipment DescriptionCoolant Recommendations Engine Protective Devices Natural GAS Fuel System Fuel SystemFuel Requirements Propane Vapor Withdrawal Fuel SystemEngine SpecificationsStationary Emergency Generator Cooling SystemWeather and Maintenance Kits Reconfiguring the Fuel SystemControl Panel Phase Alternators Y Configuration Alternator Power Winding ConnectionsFOUR-LEAD, SINGLE-PHASE Stator Alternator AC Lead ConnectionsStator Power Winding Connections 3-phase, 120/208V 6 Lead Activate the Generator Using the AUTO/OFF/MANUAL SwitchControl Panel Interface Display Interface MenusActivation Chart Choose Language TroubleshootingFuel Conversion Setting the Exercise TimerUser Adjustable Settings OperationAuto Start Alarm and Warning MessagesManual Start LOW Battery Alarm UNDER-FREQUENCY Shutdown AlarmMissing Crank Pulse Alarm LOW Battery WarningCommon Alarm Relay Maintenance AlertsMenu System Stationary Emergency Generator Control and Operation Operating Unit with Manual Transfer SwitchOperating Unit with Automatic Transfer Switch Engine START-UP and TransferChanging Engine OIL General MaintenanceCheck Engine OIL Cooling INTAKE/OUTLETOverload Protection for Engine DC Electrical System Engine CoolantCoolant Change Exercise SystemBattery Fluid Battery MaintenanceBattery Replacement Spark PlugsService Schedule System / Component Frequency ProcedureTroubleshooting Guide Problem Cause CorrectionWarranty Purchaser’s/Owner’s Recordkeeping Responsibilities Page Page Assy STR 390 25GD3 CPL Page Group a UL Circuit Breaker 225AF Page UL Circuit Breaker KG Page UL Circuit Breaker QN This page Left Intentionally Blank Page Weldment Frame 2.4L C2 Page Battery Tray C1 CPL Page Gasket Bosch 32 Page Weldment Radiator Support C2 Page Page Group D Harn Emissions Overlay 2.4L not Shown Page Group E Page Exhaust Elbow 2 1/4 OD 2 1/2OD Page Rear Wrap C2 CPL Page Page Page Page Page Page Page Page Page Page Page Page Page Page 04/07 a .Rev BackPg001