Maintenance

GENERAL MAINTENANCE

Before working on the Stationary Emergency

Generator, ensure the following:

The AUTO/OFF/MANUAL switch is in the OFF position.

The control panel fuse has been removed from the control box.

The 120VAC supply to the battery charger is switched OFF.

The negative battery cable has been removed.

CHECK ENGINE OIL

Check engine crankcase oil level (Figure 10.1) according to the Service Schedule.

Remove oil dipstick and wipe dry with a clean, lint-free cloth.

Install oil dipstick, then remove again.

Oil should be between FULL and ADD marks.

If oil level is below the dipstick ADD mark, remove oil fill cap-. Add the recommended oil to bring oil level up to the FULL mark. DO NOT FILL ABOVE THE “FULL” MARK. See “Engine Oil Recommendations” for recommended oils.

Figure 10.1 - Oil Dipstick and Oil Fill Cap

Oil Fill Cap

Oil

Dipstick

Oil Filter

CHANGING ENGINE OIL

nHot oil may cause burns. Allow engine to cool before draining oil. Avoid prolonged or repeat- ed skin exposure with used oil. Thoroughly wash exposed areas with soap.

Refer to the Service Schedule for engine oil and filter change fre- quencies.

Drain the oil while the engine is still warm from running. This means warm up the engine, shut it down and drain immediately as follows:

1.Remove the drain hose from its retaining clip or cut the zip-tie securing the oil drain hose.

2.Loosen and remove OIL DRAIN HOSE CAP. Drain oil com- pletely into suitable container.

3.When all oil has drained, install and tighten OIL DRAIN HOSE CAP and secure drain hose with a new zip-tie, or place the hose in its retaining clip.

4.Turn OIL FILTER (Figure 10.1) counterclockwise and remove. Properly dispose of old filter.

5.Apply light coating of new engine oil to seal of new oil filter.-Install FILTER and tighten by hand only. DO NOT OVER TIGHTEN.

6.Remove OIL FILL CAP and add recommended oil. Crankcase oil capacity is listed in the "Specifications" section.

nAfter refilling the crankcase with oil, always check oil level on dipstick. NEVER OPERATE ENGINE WITH OIL BELOW THE DIPSTICK “ADD” MARK.

7.Start engine and check for oil leaks.

8.Shut OFF engine and wait 10 minutes for the oil to settle down into the oil pan. Recheck oil level on dipstick. DO NOT fill above the dipstick "FULL" mark.

9.Dispose of used oil at a proper collection center.

COOLING INTAKE/OUTLET

Air intake and outlet openings in the generator compartment must be open and unobstructed for continued proper operation. This includes such obstructions as high grass, weeds, brush, leaves and snow.

Without sufficient cooling and ventilating air flow, the engine/gen- erator quickly overheats, which causes it to shut down. (See the installation diagram.)

The exhaust system parts from this product get extremely hot and remains hot after shutdown. High grass, weeds, brush, leaves, etc. must remain clear of the exhaust. Such materials may ignite and burn from the heat of the exhaust system.

INSPECT COOLING SYSTEM

Inspect engine cooling system. See the Service Schedule.

Check hoses for damage, deterioration, leaks, etc. Correct any discrepancies found.

Check hose clamps for tightness.

10-1

04/10 A .Rev Maint024

Image 22
Contents Stationary Emergency Generator Table of Contents Introduction Operation and MaintenanceHOW to Obtain Service Read this Manual ThoroughlySafety Rules General HazardsFire Hazards Identification Record Data LabelEngine OIL Recommendations Equipment DescriptionCoolant Recommendations Engine Protective Devices Natural GAS Fuel System Fuel SystemFuel Requirements Propane Vapor Withdrawal Fuel SystemEngine SpecificationsStationary Emergency Generator Cooling SystemWeather and Maintenance Kits Reconfiguring the Fuel SystemControl Panel Phase Alternators Y Configuration Alternator Power Winding ConnectionsFOUR-LEAD, SINGLE-PHASE Stator Alternator AC Lead ConnectionsStator Power Winding Connections 3-phase, 120/208V 6 Lead Activate the Generator Using the AUTO/OFF/MANUAL SwitchControl Panel Interface Display Interface MenusActivation Chart Choose Language TroubleshootingFuel Conversion Setting the Exercise TimerUser Adjustable Settings OperationAuto Start Alarm and Warning MessagesManual Start LOW Battery Alarm UNDER-FREQUENCY Shutdown AlarmMissing Crank Pulse Alarm LOW Battery WarningCommon Alarm Relay Maintenance AlertsMenu System Stationary Emergency Generator Control and Operation Operating Unit with Manual Transfer SwitchOperating Unit with Automatic Transfer Switch Engine START-UP and TransferChanging Engine OIL General MaintenanceCheck Engine OIL Cooling INTAKE/OUTLETOverload Protection for Engine DC Electrical System Engine CoolantCoolant Change Exercise SystemBattery Fluid Battery MaintenanceBattery Replacement Spark PlugsService Schedule System / Component Frequency ProcedureTroubleshooting Guide Problem Cause CorrectionWarranty Purchaser’s/Owner’s Recordkeeping Responsibilities Page Page Assy STR 390 25GD3 CPL Page Group a UL Circuit Breaker 225AF Page UL Circuit Breaker KG Page UL Circuit Breaker QN This page Left Intentionally Blank Page Weldment Frame 2.4L C2 Page Battery Tray C1 CPL Page Gasket Bosch 32 Page Weldment Radiator Support C2 Page Page Group D Harn Emissions Overlay 2.4L not Shown Page Group E Page Exhaust Elbow 2 1/4 OD 2 1/2OD Page Rear Wrap C2 CPL Page Page Page Page Page Page Page Page Page Page Page Page Page Page 04/07 a .Rev BackPg001