General Information
ALTERNATOR AC LEAD
CONNECTIONS
The electrical wires in the unit’s AC connection (lower) panel should be installed according to the number of leads and the voltage/phase required for the application. The voltage and phase are described on the generator data label. The number of lead wires can be identified using the Specifications section and the power output rating on the generator data label. For example, if the generator produces 130kW, 277/480 Volt,
FOUR-LEAD, SINGLE-PHASE STATOR
The rated voltage between each circuit breaker terminal is 240V. The rated voltage between each circuit breaker terminal and the neutral point 00 is 120V.
Figure 7.1 — Four-lead, Single-phase Stator
ALTERNATOR POWER WINDING CONNECTIONS
3-PHASE ALTERNATORS ("Y" CONFIGURATION)
The Stationary Emergency Generator is designed to supply
The rated voltage between circuit breaker terminals
The rated voltage between each circuit breaker terminal and the neutral point 00 is 277V, 120V, or 346V depending on the model.
Figure 7.2 — Stator Power Winding
Connections - 3-phase, 277/480V (6 Lead)
E1
S1
INTERNAL
CONNECTIONS
L - L
| S6 | S4 |
|
| 00 (NEUTRAL) |
| |
|
|
| |
|
| S5 |
|
S3 |
|
| S2 |
|
|
| |
E3 |
| L - N | E2 |
|
|
|
Figure 7.3 — Stator Power Winding
Connections - 3-phase, 277/480V (12 Lead)
| E1 |
|
|
S1 |
|
| |
| S4 |
|
|
| S7 |
|
|
|
|
| L - L |
S12 | S10 |
|
|
S9 | S11 | S8 |
|
S6 |
| S5 |
|
S3 |
|
| S2 |
|
|
| |
E3 |
| L - N | E2 |
|
|
| |
|
| 05/10 | B .Rev ACConn007 |