Fluke pmn instruction manual      %, Input AC Power Connection NON-PFC Version

Page 14

The PFC version connection is shown in Figure 3-2. Connect the input voltage line wires to L2 and COM terminals.

WARNING: 152A and 202A PFC Models are only available with 220 VAC

Nominal. For 152A Models Suffix 110 at 110-120 VAC must be operated

with the internal fuses F1 and F2 (on the Inverter Board) replaced by

copper bus provided with the supply. Use external 30A UL/VDC Approved

Fuse/Circuit Breaker. NOTE: For Application At less than 10 Hz Please see section 5.7.

TB1

110 VAC

L1

COM

220 VAC

L2

Figure 3-1 Input AC Power Connection NON-PFC Version

TB1

L1

COM

VAC

L2

Figure 3-2 Input AC Power Connection, PFC Version

     %

Use wire with minimum .064 inches (1.6 mm) diameter and 600 V insulation.

83-493-001 Revision G

3 - 2

Installation

Image 14
Contents    Introduction SpecificationsInstallation ESDMaintenance and Calibration Applications                 #            !     #           Specifications Specifications Specifications Specifications     $          Input AC Power Connection NON-PFC Version      %           Grounding of Input Line Output Ground Connection         Eample Of Interface Connection Revision G Operations Fault   &                      Output Current Measurement                    !            Long Charge Time Operation Revision G Applications