For clarification and further technical assistance specific to your application, please contact Lambda EMI.
The ratings of these supplies are as follows: 500A - 500 J/s, 102A - 1000 J/s, 152A - 1500J/s,
V O L T A G E |
|
| |
| T c | T I M E | |
| T p | ||
| 1 CV 2 |
| |
Peak Charge Rate = | 2 | C - OUTPUT LOAD CAPACITOR | |
TC | |||
|
|
V - PROGRAMMED OUTPUT VOLTAGE
|
| 1 | CV 2 |
|
Average Charge Rate = |
| 2 | TC AND TP ARE SHOWN IN FIGURE | |
|
| |||
|
| Tp | ||
|
|
|
|
Figure 5.1 Output Voltage Waveform
When the capacitor or PFN is discharged, a high peak current may flow out of the power supply as a result of voltage reversal. This occurs in a system which is underdamped in order to clear the high voltage switch after each pulse. The average value of this peak current added to the normal output current may exceed the rating of the HV diodes in the power supply. This current can be measured with a current transformer as shown in Figure 5.2.
83-493-001 Revision G
5 - 1 | Applications |