Emerson 200I/48-NT5C05C user manual Ambient conditions for the rectifier Operating, Conditions

Page 15

 

 

 

 

Specifications 15

 

 

Table 4 - Ambient conditions for the rectifier

 

 

 

 

 

 

 

Operating

A minimum airflow clearance of 2 inches ( 5 cm ) is

 

 

conditions

required at the rear of the rectifier.

 

 

 

The rectifier will operate properly under the following

 

 

 

conditions.

 

 

 

 

 

Temperature:

32°F to 122°F

( 0°C to +50°C )

 

 

 

 

32°F to 104°F

( 0°C to +40°C ) with air

 

 

 

 

filters

 

 

 

 

Humidity:

0 to 95% RH ( non-condensing ) at 4

 

 

 

 

kPa max. equiv. to 7,000 ft. ( 2,100 m )

 

 

 

 

above sea level

 

 

Transportation

During transportation, the rectifier can be subjected to

 

 

conditions

the following conditions without sustaining damage.

 

 

 

Temperature:

–67°F ( –55°C ) for 16 hours

 

 

 

 

140°F ( +60°C ) dry heat

 

 

 

Humidity:

0 to 95% RH ( non-condensing ) at

 

 

 

 

4 kPa max.

 

 

 

 

Vibration:

38 mm / s max. ( 10 Hz to 30 Hz )

 

 

 

 

sinusoidal, 18-inch ( 457 mm ) drop

 

 

 

 

when packaged

 

 

 

Pressure:

12 kPa min. equiv. to 49,212 ft.

 

 

 

 

( 15,000 m above sea level)

 

 

 

Temperature shock : − 58°F to 140°F ( − 50°C to 60°C )

 

 

Storage conditions

During storage, the rectifier may be subjected to the

 

 

 

following conditions without damage :

 

 

 

Temperature:

–67°F ( –55°C ) for 16 hours to 140°F

 

 

 

 

( +60°C ) dry heat

 

 

 

Humidity:

0 to 95% RH ( non-condensing ) at

 

 

 

 

4 kPa maximum

 

 

 

The rectifier contains aluminum electrolytic capacitors

 

 

 

that have a shelf life of five years or greater at the

 

 

 

maximum rated storage temperature.

 

Emerson Energy Systems

Rectifier 200I/48 NT5C05C Installation and User Manual

Image 15
Contents Helios Modular Switch Mode Rectifier 200I/48 NT5C05C Page Emerson Energy Systems Page Publication history This page is left blank intentionally Contents List of Procedures List of FiguresList of Tables Ac female plug in a 1200 a cabinet This page is left blank intentionally Purpose of this manual General informationTypical mounting in a cabinet or frame Models and mounting configurationsMechanical and electrical specifications SpecificationsOperation specifications and ambient conditions Storage conditions Ambient conditions for the rectifier OperatingConditions TransportationMechanical specifications of the NT6C43CB 1200 a cabinet Ambient conditions of a 1200 a cabinetOutput voltage Protecting the premises InstallationMounting configurations Tools and test equipmentOptimizing the life of the equipment Personal safety and protecting the equipmentPreventing damage caused by over-tightening Preventing personal injuryProtecting against electrical shocks Short circuit hazard Installing in a frameInstalling in a cabinet Procedure 1 Installing the rectifier in a frame Step ActionAnchoring the cabinet Procedure 2 Installing a rectifier in a cabinet Step ActionInstalling the rectifier Cabling and connectingConnecting the dc output terminals to the busbars Electrical connections should meet standards Connecting ac to the rectifiersHazardous potentials Cabling ac the NT5C05CA / CB rectifiers Connecting ac to the rectifier NT5C05CC Controller NT NT6C25BA or NT6C25BB Connecting the control signalsPin assignment for connectors J7 to J12 Monitoring of the shunt currentFunction Input/ Output Pin assignment for connector J13 Function Functional description Overview Input circuitOutput circuit AC breaker Monitoring and control circuitsOutput capacitors Description of the front panel Breakers DC circuit breakerFront panel controls and LEDs Switches, controls and LEDsAC on ac voltage monitoring CL current limit indicatorFAN ALM fan failure alarm Front panel LEDsHvsd high voltage shutdown RFA rectifier failure alarmSEN Fail sense fail alarm Local and remote adjustments and controlsSwitches Description Rectifier input / output signals to the controllerDesignation Description Remote equalize control EQL Volt / AMP digital meter switchSlope sharing SLS Rectifier parallel operationForced sharing FS Remote Hvsd Local and remote Hvsd resetSwitch Position Delay SEC Setting the start-up delayStart up delay DIP switch Control signals on connector P1Remote on / OFF control TR CB OFF NC This page is left blank intentionally Standard settings Standard settings for the rectifier Parameter SettingOperation Starting up and adjusting Procedure 9 Starting up the rectifier Step ActionAdjusting the high voltage shutdown Hvsd Adjusting the equalize voltage EQL Adjusting the slope shareVerifying the current limit Adjusting the forced load sharing Maintenance Replacing the air filterReplacing the fan unit Calibrating the Volt / Amp Multimeter Preventing short circuitsRe-assembling Remotely Resetting the rectifier after an Hvsd high voltage shutdownThis page is left blank intentionally Diagnosing system faults Fault symptom Possible causes TroubleshootingTroubleshooting Part Number CPC Appendix a Replacement partsAppendix a Recommended Replacement Parts Appendix B Technical service assistance Local toll-free prefixesCountry Prefix Toll-free technical assistance numbers United States Canada Europe Asia and the PacificCaribbean and Latin America Middle-East Cala Abbreviations and acronyms RFA Page Helios Modular Switch Mode Rectifier 200I/48 NT5C05C