Emerson 200I/48-NT5C05C Resetting the rectifier after an Hvsd high voltage shutdown, Remotely

Page 51

 

 

 

 

Maintenance 51

 

Procedure 11 - Calibrating the meter

 

 

 

 

 

 

 

Step

 

Action

 

1

Make sure the remote sense leads are disconnected by removing

 

 

the corresponding RC− fuse from the controller.

 

2

Set the VOLT/AMP switch to AMP. Set the output load of the plant

 

 

so the rectifier delivers a current of approximately 100 A. Measure

 

 

the voltage between VOUT+ and VOUT − , located on the front panel,

 

 

with a digital meter.

 

 

 

3

Convert this measured voltage to a current value ( 50 mV

 

 

corresponding to 250 A ).

 

 

 

 

current

= 250 A

 

 

voltage

50 mV

 

 

If the voltage measured is 20.2 mV :

 

 

measured current

=

250 A X ( 20.2 mV ) = 101 A

 

 

 

 

50 mV

 

 

Rotate the CUR CAL potentiometer on the display panel until this

 

 

value is displayed.

 

 

 

4

Put the VOLT / AMP switch to VOLT. Adjust the V CAL

 

 

potentiometer so that the reading displayed on the meter of the

 

 

rectifier is identical to the reading on the digital meter.

 

5

Put the rectifier to OFF and reconnect the sense leads.

 

 

end

 

6.4.Resetting the rectifier after an HVSD ( high voltage shutdown )

To reset the rectifier after an HVSD condition has occurred execute one of the steps contained in Procedure 12.

Procedure 12 - Resetting the rectifier after a high voltage shutdown

Step Action

Locally

1Toggle the ac circuit breaker on the unit itself, or the associated ac breaker in the distribution panel OFF and ON ( wait until the green ac ON LED extinguishes before toggling the breaker back to ON ).

Remotely

2Apply a ground signal at the HVSDR input of the rectifier.

end

Emerson Energy Systems

Rectifier 200I/48 NT5C05C Installation and User Manual

Image 51
Contents Helios Modular Switch Mode Rectifier 200I/48 NT5C05C Page Emerson Energy Systems Page Publication history This page is left blank intentionally Contents List of Procedures List of FiguresList of Tables Ac female plug in a 1200 a cabinet This page is left blank intentionally Purpose of this manual General informationTypical mounting in a cabinet or frame Models and mounting configurationsMechanical and electrical specifications SpecificationsOperation specifications and ambient conditions Storage conditions Ambient conditions for the rectifier OperatingConditions TransportationMechanical specifications of the NT6C43CB 1200 a cabinet Ambient conditions of a 1200 a cabinetOutput voltage Protecting the premises InstallationMounting configurations Tools and test equipmentOptimizing the life of the equipment Personal safety and protecting the equipmentPreventing damage caused by over-tightening Preventing personal injuryProtecting against electrical shocks Short circuit hazard Installing in a frameInstalling in a cabinet Procedure 1 Installing the rectifier in a frame Step ActionAnchoring the cabinet Procedure 2 Installing a rectifier in a cabinet Step ActionInstalling the rectifier Cabling and connectingConnecting the dc output terminals to the busbars Electrical connections should meet standards Connecting ac to the rectifiersHazardous potentials Cabling ac the NT5C05CA / CB rectifiers Connecting ac to the rectifier NT5C05CC Controller NT NT6C25BA or NT6C25BB Connecting the control signalsPin assignment for connectors J7 to J12 Monitoring of the shunt currentFunction Input/ Output Pin assignment for connector J13 Function Functional description Overview Input circuitOutput circuit AC breaker Monitoring and control circuitsOutput capacitors Description of the front panel Breakers DC circuit breakerFront panel controls and LEDs Switches, controls and LEDsAC on ac voltage monitoring CL current limit indicatorFAN ALM fan failure alarm Front panel LEDsHvsd high voltage shutdown RFA rectifier failure alarmSEN Fail sense fail alarm Local and remote adjustments and controlsSwitches Description Rectifier input / output signals to the controllerDesignation Description Remote equalize control EQL Volt / AMP digital meter switchSlope sharing SLS Rectifier parallel operationForced sharing FS Remote Hvsd Local and remote Hvsd resetSwitch Position Delay SEC Setting the start-up delayStart up delay DIP switch Control signals on connector P1Remote on / OFF control TR CB OFF NC This page is left blank intentionally Standard settings Standard settings for the rectifier Parameter SettingOperation Starting up and adjusting Procedure 9 Starting up the rectifier Step ActionAdjusting the high voltage shutdown Hvsd Adjusting the equalize voltage EQL Adjusting the slope shareVerifying the current limit Adjusting the forced load sharing Maintenance Replacing the air filterReplacing the fan unit Calibrating the Volt / Amp Multimeter Preventing short circuitsRe-assembling Remotely Resetting the rectifier after an Hvsd high voltage shutdownThis page is left blank intentionally Diagnosing system faults Fault symptom Possible causes TroubleshootingTroubleshooting Part Number CPC Appendix a Replacement partsAppendix a Recommended Replacement Parts Appendix B Technical service assistance Local toll-free prefixesCountry Prefix Toll-free technical assistance numbers United States Canada Europe Asia and the PacificCaribbean and Latin America Middle-East Cala Abbreviations and acronyms RFA Page Helios Modular Switch Mode Rectifier 200I/48 NT5C05C