Installation 29
Procedure 8 - Connecting an NT5C05CC rectifier directly to a controller
Step | Action |
1If an NT6C43PB interconnect board is not available, each rectifier must be connected directly to the controller with the following cables :
•P0723784, P0723785 or P0723786 ( for conventional controllers )
•P0723708, P0723709 or P0723210 ( for front access controllers )
end
For controllers not manufactured by Emerson Energy Systems see Table
12 in the " Functional Description " chapter describing the pin assignments of the rectifier. Refer to Table 8 for the pin assignments of connectors J7 to J12 on board NT6C43PB.
| Note: | The alarm and control signals in Table 8 are all ground | |
|
| signals except for the RC– signal that is a | |
|
| battery signal. |
|
Table 8 - Pin assignment for connectors J7 to J12 |
| ||
|
|
|
|
Pin | Label | Function | Input/ Output |
1 | EQL | Equalize | Input |
2 | RG+ | Remote sense | Input |
3 | RC– | Remote sense | Input |
4 | FAN ALM | Fan fail alarm | Output |
5 | HVSDR | High voltage shutdown reset | Input |
6 | HVSD | High voltage shutdown | Input |
7 | RFA | Rectifier failure alarm | Output |
8 | TR | Temporary release | Input |
3.7.1.Monitoring of the shunt current
A
Emerson Energy Systems | Rectifier 200I/48 NT5C05C Installation and User Manual |