36 Functional description
Table 11 - Adjusting the potentiometers and switches
Potentiometers | Description |
CL ADJ | Current limit adjust ( 100 A to 210 A ) |
CUR CAL | Current reading calibration |
EQL ADJ | Equalize voltage adjust ( 0 V to − 4 V ) |
FLT ADJ | Float voltage adjust ( − 46 V to − 58 V ) |
HVSD ADJ | High voltage shutdown adjust ( − 52 V to − 60 V ) |
VOLT CAL | Voltage reading calibration |
Switches | Description |
EQL / FLT | Equalize / Float selection switch |
SLS / FS | Slope load sharing / Forced load sharing selection |
ST UP DELAY | |
VOLT / AMP | Voltage and current display selection switch |
Table 12 - Rectifier input / output signals to the controller | |
|
|
Designation | Description |
RG+ / RC− | External reference voltage across the batteries |
| measured through the controller to regulate the voltage. |
HVSD | Remote High Voltage Shutdown input activated by a |
| BAT RTN signal. |
HVSDR | Remote High Voltage Shutdown Reset input activated by |
| a BAT RTN signal. |
TR | Remote Inhibit input activated by a BAT RTN signal. |
EQL | Remote Equalize input activated by a BAT RTN signal. |
RFA | Rectifier Failure Alarm output activating a form C contact |
F ALM | Fan Failure Alarm output activating a form C contact |
SHUNT ( + ) and | Rectifier Current input / output ( 50 mV / 250 A ) |
SHUNT ( − ) |
|
CURRENT | Common Forced Current Share Mode ( |
SHARE |
|
4.2.5.Voltage / current display test and measurement
CUR CAL / VOLT CAL potentiometers
These potentiometers are used to calibrate the digital display meter for current and voltage measurements. As the two potentiometers affect each other, current calibration must be performed before voltage calibration.