5. Operation
5.1.Standard settings
The parameters of the NT5C05CA / CB / CC rectifiers are set as indicated in Table 15. For different settings refer to User Manual Voltage_level entitled Voltage Level Limits for Power Plants, Rectifiers and Controllers.
Table 15 - Standard settings for the rectifier
Parameter | Setting |
Rectifier float output voltage ( FLOAT ) | 52.1 ±0.1 V dc |
Rectifier equalize output voltage | 52.8 ±0.1 V dc |
( EQUALIZE ) |
|
Rectifier high voltage shutdown threshold | 56.5 ±0.1 V dc |
Rectifier output current limit | 205 A ±5 A |
Rectifier start delay | 4 sec |
Low ac input disconnect | 330 ±5 V ac |
Low ac input reconnect | 350 ±5 V ac |
|
|
High ac input disconnect | 475 ±5 V ac |
High ac input reconnect | 460 ±5 V ac |
Load sharing method | Slope |