Emerson Xtreme Density Or 2-5/8 O.D, Rear XD Cooling Module Either 5/8 or 7/8, Recommended Arc

Page 51

Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF

4.7.2Piping Connections to Liebert XDP or Liebert XDC Piping Installation for Hard Piped System

The assembly and connection means for piping in the Liebert XD system are similar to those used for conventional refrigeration systems. All piping should be installed with high-temperature brazed joints. Soft solder is not recommended. During brazing, the lines must be filled with flowing dry nitro- gen to prevent excessive oxidation and scale formation inside the piping. Prevailing good refrigeration practices must be employed for piping supports, leak testing, dehydration and charging. Failure to use good system practices may result in damage to the system. Refer to the ASHRAE refrigeration handbook for general good-practice refrigeration piping.

Follow all guidelines in 3.13 - Liebert XD Piping System Design and 3.14 - Liebert XD Piping Slope during installation.

Figure 45 Hard-pipe connection diagram for Liebert XDV, Liebert XDO and Liebert XDH cooling modules

Return Main

 

(seen from end )

 

2-1/8" O.D.

Recommended Arc

Or 2-5/8" O.D.

 

Acceptable Arc

 

Supply Main (seen from end ) 1-1/8" O.D.

or 1-3/8" O.D.

1/2” Refrigerant -Grade Full-Port Ball Valve Field-Supplied and Field Installed

Supply to Cooling Module

Refer to Table 5 for details.

Rear of

XD Cooling

Module

Either 5/8” or 7/8"

Refrigerant -Grade Full-Port Ball Valve Field-Supplied and Field Installed

Copper Tubing

Total length of each line from XD cooling module (XDH, XDO, XDV) to Main; not to exceed 72" (1829mm)

Return from Cooling Module

Top of XD Cooling Module

45

Image 51
Contents Liebert Xtreme Density Page Table of Contents XDH and Liebert Xdcf SpecificationsIii Tables Liquid Liquid/Vapor Mix CoolFrame, XDH Pumped Refrigerant Direct and Indirect System ConfigurationsEuropean Union Fluorinated Greenhouse Gas Requirements Liebert Heat Rejection Air Cooled or Water/Glycol CooledLiebert XDO-Overhead Cooling Module Liebert XDV-Vertical, Above-Cabinet Cooling Module Liebert XDH-Horizontal Cooling Module Liebert Xdcf units on BladeFrame EX cabinets Liebert XdcfLiebert XDA-Air Flow Enhancer Liebert XDP Minimum Load Liebert XDP-Pumping UnitLiebert XDC Minimum Load Liebert XDC-Refrigerant ChillerPrefabricated Headers Liebert XD field-installed port kits header connection sizeLiebert XD Piping Liebert XD Field Piping Flexible Piping KitDetermining Cooling Equipment Needs Hot aisle-cold aisle arrangement with under-floor source Implementing a Hot-Aisle/Cold Aisle DesignCalculate the Heat Load to be Handled by Liebert XD System Determine Cooling Requirements and Select Liebert XD SystemNumber of Modules Supported by a Liebert XDP or Liebert XDC Airflow Requirements for Liebert XD SolutionsConfiguring a Liebert XD System Selecting Liebert XD Cooling ModulesDetermining Spacing of Liebert XDOs in an Aisle Liebert XDO PlacementLiebert XDO spacing-horizontal and vertical Liebert XDV Unit Placement Liebert XDV is suspended From ceiling structureInput Information Step Results Liebert Xdcf unit mounting locations Liebert Xdcf PlacementLiebert XDP/Liebert XDC Placement Liebert XDH PlacementFor enhanced protection Interlaced piping arrangementInterlaced piping arrangement for enhanced protection For enhancedProtection Liebert XD Piping System Design Liebert XD RefrigerantKey to Piping Pipe Function Size / Equivalent Pipe Length Supply, return pipe sizes for refrigerant loopXD CoolFrame, XDH, XDO or XDV Liebert XD Piping SlopeBypass Flow Controllers Refrigerant PumpedLiebert XDP Liebert XDC Determining Refrigerant Volume Liebert XDP/Liebert XDC Pumped R-134a Circuit VolumeSystem refrigerant charge for the supply and return mains Return Line Diameter Return Line Diameter 5/8Worksheet to calculate refrigerant charge Liebert XDC DX R-407c Circuit Volume-Air Cooled UnitsCalculating Refrigerant Charge-Example Calculating refrigerant charge-exampleIndoor water/glycol cooled module R-407c refrigerant charge Chilled Water PipingElectrical Outdoor condenser charge-R-407cOptional Features Liebert XDO Liebert XDO Standard FeaturesLeft Side XDO 24-1/8 Rear of XDO Liebert XDO internal mounting location Liebert XDO top and front electrical access points Liebert XDV Standard FeaturesLiebert XDV dimensions Optional Features-Liebert XDVDetail Area a Detail a Power Source Liebert XDV electrical connections for CSA-approved units Suspending single Liebert XDV from Unistruts Page Liebert Xdcf Standard Features Liebert XDPXD CoolFrame, XDH, XDO or XDV Liebert Xdcf Mechanical Considerations Liebert TMReturn Pipe Liebert Xdcf Installation Considerations Liebert Xdcf Piping Connection Methods and PointsEgenera BladeFrame Liebert XDH Standard Features Optional Features-Liebert XDHHeader System Supply and return piping connections Liebert XDH dimensionsRefer to for details Or 2-5/8 O.DRear XD Cooling Module Either 5/8 or 7/8 Recommended ArcLiebert XDH Liebert XD Flex Pipe KitLiebert XD Flex Pipe assemblies, supply and return Liebert XD Liebert XDV CoolFrameLiebert XD Piping Dimensions and Features Piping Installation Method prefabricated headersTwo-port prefabricated piping legend Branch Piping Standard Run Long Run Four Port 186551G21 Four-port prefabricated piping legendBranch Piping Standard Run Long Run Five Port Five-port prefabricated piping legendBranch Piping Standard Run Long Run Ten Port 186650G51 Ten-port prefabricated piping legend33-1/8 990 1067 XDP160 Liebert XDP Standard FeaturesModel Pipe Connection Point 50/60 HZ Unit piping outlet connection sizes, inches, OD CuEnclosure Cover Customer Power Liebert XDC Optional Features Liebert XDC Standard FeaturesLiebert XD Chiller piping connection sizes Liebert XDC piping locationsLiebert XDC Water/Glycol Piping Connection Sizes Piping locations-floor stand and valve assembly Front view of Liebert XDC and electrical enclosures Switch Transformer Electrical handy box, factory-installed with cover Liebert XDC Extra Low Voltage field connections points Liebert XDC160 specifications Performance Data Performance DataHeat Rejection Equipment Piping Connections204 Liebert XDP160 specifications Liebert XDO16 specifications Liebert XDO20 specifications Pipe Connections without flex pipeSides, Front and Rear Liebert XDO20 dimensions-domestic and export Liebert XDV8 specifications Liebert XDV10 specifications Liebert XDV8 dimensions-domestic and export Liebert XDV10 dimensions-domestic and exportLiebert Xdcf specifications Liebert XDH specifications Specifications Specifications Page That Ne tIti Ti n