Emerson Xtreme Density manual Liebert XDC160 specifications

Page 70

 

 

 

 

Specifications

5.0 SPECIFICATIONS

 

 

 

 

 

 

 

 

 

Table 27 Liebert XDC160 specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

XDC160 Water /

 

XDC160 Air

Glycol

 

 

 

 

189192G3

Models

XDC160AA

 

XDC160AM

189192G5

 

 

 

 

See Tables 28, 29

Cooling Capacity, tons (kW)

46 (160)

 

37 (130)

and 30 for

 

Water/Glycol

 

 

 

 

 

 

 

 

performance data

 

 

 

 

 

The Liebert XDC’s minimum recommended operating load is 40% of

 

system nominal capacity. For example, a Liebert XDC160 60Hz

Minimum Load

system’s minimum load would be 64 kW. Loading below this value

 

can unfavorably affect system operation. Consult factory for any

 

loading below this recommendation.

 

Electrical Requirements

 

 

 

 

Input

460V-3ph-60Hz

 

380/415V-3ph-50Hz

460V-3ph-60Hz

Full Load Amps

 

 

79A

 

Minimum supply wire sizing ampacity

 

 

84A

 

Maximum fuse or circuit breaker size

 

 

100A

 

Dimensions, inches (mm)

 

 

 

 

Height - Main unit only

 

78 (1981)

 

 

 

 

 

Height - Main unit only, as shipped

 

83 (2108)

 

 

 

 

 

Width - Main unit

 

74 (1879)

 

 

 

 

 

Depth - Main unit

 

34-5/8 (879)

 

 

 

 

 

Height - Water / Glycol cooled condenser stand

 

N/A

24 (607)

 

 

 

 

Width - Water / Glycol cooled condenser stand

 

N/A

72 (1829)

Depth - Water / Glycol cooled condenser stand

 

N/A

33 (839)

Weight, lb (kg)

 

 

 

 

Main unit only

 

1800 (817)

 

Main unit only, as shipped

Domestic: 1945 (882); Export: 2093 (949)

Water / Glycol cooled condenser stand

 

N/A

1075 (488)

Water / Glycol cooled condenser stand, as shipped

 

N/A

1150 (521)

Pipe Connections, inches, O.D., Cu

 

 

 

 

Liebert XD Coolant supply to XD cooling modules

 

1-1/8

 

Liebert XD Coolant return from XD cooling modules

 

2-1/8

 

 

 

 

 

Liquid line, DX circuit

 

7/8

 

 

 

 

 

Hot gas line, DX circuit

 

1-3/8

 

 

 

 

 

 

Heat Rejection Equipment

 

 

 

 

95°F ambient air cooled condenser

1-CDL830 or 2-CSL415

N/A

 

 

 

 

 

Number of XD Cooling Units Connected, Maximum (Minimum)

 

 

 

Liebert XDCF10

 

16 (6)

 

Liebert XDH20

 

8 (4)

 

Liebert XDH32

 

5 (2)

 

Liebert XDO16

 

10 (4)

 

Liebert XDO20

 

8 (4)

 

Liebert XDV8

 

20 (8)

 

Liebert XDV10

 

16 (7)

 

Cabinet Exterior Finish

Black, matte finish, heat-fused powder coat

Maximum Ambient Operating Temperature °F(°C)

 

86 (30)

 

Agency

 

 

 

 

Approvals

CSA

 

CE

CSA

 

 

 

 

 

64

Image 70
Contents Liebert Xtreme Density Page Table of Contents Specifications XDH and Liebert XdcfIii Tables Liquid Liquid/Vapor Mix CoolFrame, XDH Liebert Heat Rejection Air Cooled or Water/Glycol Cooled Direct and Indirect System ConfigurationsEuropean Union Fluorinated Greenhouse Gas Requirements Pumped RefrigerantLiebert XDO-Overhead Cooling Module Liebert XDV-Vertical, Above-Cabinet Cooling Module Liebert XDH-Horizontal Cooling Module Liebert Xdcf Liebert Xdcf units on BladeFrame EX cabinetsLiebert XDA-Air Flow Enhancer Liebert XDP-Pumping Unit Liebert XDP Minimum LoadLiebert XDC-Refrigerant Chiller Liebert XDC Minimum LoadLiebert XD Field Piping Flexible Piping Kit Liebert XD field-installed port kits header connection sizeLiebert XD Piping Prefabricated HeadersDetermining Cooling Equipment Needs Implementing a Hot-Aisle/Cold Aisle Design Hot aisle-cold aisle arrangement with under-floor sourceDetermine Cooling Requirements and Select Liebert XD System Calculate the Heat Load to be Handled by Liebert XD SystemSelecting Liebert XD Cooling Modules Airflow Requirements for Liebert XD SolutionsConfiguring a Liebert XD System Number of Modules Supported by a Liebert XDP or Liebert XDCLiebert XDO Placement Determining Spacing of Liebert XDOs in an AisleLiebert XDO spacing-horizontal and vertical Liebert XDV is suspended From ceiling structure Liebert XDV Unit PlacementInput Information Step Results Liebert Xdcf Placement Liebert Xdcf unit mounting locationsLiebert XDH Placement Liebert XDP/Liebert XDC PlacementInterlaced piping arrangement For enhanced protectionFor enhanced Interlaced piping arrangement for enhanced protectionProtection Liebert XD Refrigerant Liebert XD Piping System DesignSupply, return pipe sizes for refrigerant loop Key to Piping Pipe Function Size / Equivalent Pipe LengthRefrigerant Pumped Liebert XD Piping SlopeBypass Flow Controllers XD CoolFrame, XDH, XDO or XDVLiebert XDP Liebert XDC Liebert XDP/Liebert XDC Pumped R-134a Circuit Volume Determining Refrigerant VolumeSystem refrigerant charge for the supply and return mains Return Line Diameter 5/8 Return Line DiameterCalculating refrigerant charge-example Liebert XDC DX R-407c Circuit Volume-Air Cooled UnitsCalculating Refrigerant Charge-Example Worksheet to calculate refrigerant chargeOutdoor condenser charge-R-407c Chilled Water PipingElectrical Indoor water/glycol cooled module R-407c refrigerant chargeLiebert XDO Standard Features Optional Features Liebert XDOLeft Side XDO 24-1/8 Rear of XDO Liebert XDO internal mounting location Liebert XDV Standard Features Liebert XDO top and front electrical access pointsOptional Features-Liebert XDV Liebert XDV dimensionsDetail Area a Detail a Power Source Liebert XDV electrical connections for CSA-approved units Suspending single Liebert XDV from Unistruts Page Liebert XDP Liebert Xdcf Standard FeaturesXD CoolFrame, XDH, XDO or XDV Liebert TM Liebert Xdcf Mechanical ConsiderationsReturn Pipe Liebert Xdcf Piping Connection Methods and Points Liebert Xdcf Installation ConsiderationsEgenera BladeFrame Optional Features-Liebert XDH Liebert XDH Standard FeaturesHeader System Liebert XDH dimensions Supply and return piping connectionsRecommended Arc Or 2-5/8 O.DRear XD Cooling Module Either 5/8 or 7/8 Refer to for detailsLiebert XD Liebert XDV CoolFrame Liebert XD Flex Pipe KitLiebert XD Flex Pipe assemblies, supply and return Liebert XDHPiping Installation Method prefabricated headers Liebert XD Piping Dimensions and FeaturesTwo-port prefabricated piping legend Four-port prefabricated piping legend Branch Piping Standard Run Long Run Four Port 186551G21Five-port prefabricated piping legend Branch Piping Standard Run Long Run Five PortTen-port prefabricated piping legend Branch Piping Standard Run Long Run Ten Port 186650G51Liebert XDP Standard Features 33-1/8 990 1067 XDP160Unit piping outlet connection sizes, inches, OD Cu Model Pipe Connection Point 50/60 HZEnclosure Cover Customer Power Liebert XDC Standard Features Liebert XDC Optional FeaturesLiebert XDC piping locations Liebert XD Chiller piping connection sizesLiebert XDC Water/Glycol Piping Connection Sizes Piping locations-floor stand and valve assembly Front view of Liebert XDC and electrical enclosures Switch Transformer Electrical handy box, factory-installed with cover Liebert XDC Extra Low Voltage field connections points Liebert XDC160 specifications Piping Connections Performance DataHeat Rejection Equipment Performance Data204 Liebert XDP160 specifications Liebert XDO16 specifications Pipe Connections without flex pipe Liebert XDO20 specificationsSides, Front and Rear Liebert XDO20 dimensions-domestic and export Liebert XDV8 specifications Liebert XDV10 specifications Liebert XDV10 dimensions-domestic and export Liebert XDV8 dimensions-domestic and exportLiebert Xdcf specifications Liebert XDH specifications Specifications Specifications Page Ti n Ne tIti That