Emerson Xtreme Density manual Liebert XDP Standard Features, 33-1/8 990 1067 XDP160

Page 57

Liebert XD Cooling Modules—Liebert XDO, Liebert XDV, Liebert XDH and Liebert XDCF

4.10Liebert XDP Standard Features

Heat Exchanger—Brazed plate design with interwoven circuiting constructed of stainless steel plates, copper brazed.

Pumps—Centrifugal type, end suction, internally cooled, canned rotor design.

Standard Control Processor—The standard control system is microprocessor-based with an exter- nal LCD numerical display to allow observation of specified adjustable functions. Operating con- ditions and status are indicated on the LCD panel, which is mounted either on the unit or on the wall, depending on application details (see user manual, SL-16641). The control system also mon- itors unit operation and activates an alarm when any of the specified factory preset conditions are exceeded.

Cabinet and Frame—Custom powder painted steel panels. A hinged control access panel opens to a second front panel, which is a protected enclosure for all high voltage components. Frame is con- structed of 14 gauge heliarc welded tubular steel and painted using an auto-deposition coating system.

Figure 50 Liebert XDP dimensions

C Side Panel

A B

Overall Overall

 

 

 

E

 

 

 

m

 

 

 

 

 

 

m

)

 

 

 

 

 

7

 

 

 

 

 

 

2

 

 

 

 

 

 

1

 

 

 

 

 

 

(

 

 

 

 

 

 

"

 

 

 

 

 

 

78"

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(1981mm)

1" (25mm)

 

 

 

 

 

 

 

5-1/2"

 

 

 

 

 

 

 

(140mm)

 

 

 

 

 

 

 

 

 

 

 

 

11"

 

 

 

 

(279mm)

 

Floor Cutout Dimensions

D

The shaded area indicates

Unit Base

E

a recommended clearance

Unit Base

of 36" (914mm) for component

 

access.

 

 

 

 

 

 

 

D

DPN000767

Unit Dimensional Data

Table 22 Liebert XDP dimensions

Pg. 2, Rev. 6

Model

 

Dimensional Data inches (mm)

 

Shipping Weight, lb (kg)

 

 

 

 

 

 

 

50/60Hz

A

B

C

D

E

Domestic

Export

 

 

 

 

 

 

 

 

Liebert

38 (965)

34 (864)

33-1/8 (841)

33 (838)

36 (914)

990 (449)

1067 (484)

XDP160

 

 

 

 

 

 

 

* The dimension does not include the bezel of the disconnect switch.

51

Image 57
Contents Liebert Xtreme Density Page Table of Contents XDH and Liebert Xdcf SpecificationsIii Tables Liquid Liquid/Vapor Mix CoolFrame, XDH European Union Fluorinated Greenhouse Gas Requirements Direct and Indirect System ConfigurationsLiebert Heat Rejection Air Cooled or Water/Glycol Cooled Pumped RefrigerantLiebert XDO-Overhead Cooling Module Liebert XDV-Vertical, Above-Cabinet Cooling Module Liebert XDH-Horizontal Cooling Module Liebert Xdcf units on BladeFrame EX cabinets Liebert XdcfLiebert XDA-Air Flow Enhancer Liebert XDP Minimum Load Liebert XDP-Pumping UnitLiebert XDC Minimum Load Liebert XDC-Refrigerant ChillerLiebert XD Piping Liebert XD field-installed port kits header connection sizeLiebert XD Field Piping Flexible Piping Kit Prefabricated HeadersDetermining Cooling Equipment Needs Hot aisle-cold aisle arrangement with under-floor source Implementing a Hot-Aisle/Cold Aisle DesignCalculate the Heat Load to be Handled by Liebert XD System Determine Cooling Requirements and Select Liebert XD SystemConfiguring a Liebert XD System Airflow Requirements for Liebert XD SolutionsSelecting Liebert XD Cooling Modules Number of Modules Supported by a Liebert XDP or Liebert XDCDetermining Spacing of Liebert XDOs in an Aisle Liebert XDO PlacementLiebert XDO spacing-horizontal and vertical Liebert XDV Unit Placement Liebert XDV is suspended From ceiling structureInput Information Step Results Liebert Xdcf unit mounting locations Liebert Xdcf PlacementLiebert XDP/Liebert XDC Placement Liebert XDH PlacementFor enhanced protection Interlaced piping arrangementInterlaced piping arrangement for enhanced protection For enhancedProtection Liebert XD Piping System Design Liebert XD RefrigerantKey to Piping Pipe Function Size / Equivalent Pipe Length Supply, return pipe sizes for refrigerant loopBypass Flow Controllers Liebert XD Piping SlopeRefrigerant Pumped XD CoolFrame, XDH, XDO or XDVLiebert XDP Liebert XDC Determining Refrigerant Volume Liebert XDP/Liebert XDC Pumped R-134a Circuit VolumeSystem refrigerant charge for the supply and return mains Return Line Diameter Return Line Diameter 5/8Calculating Refrigerant Charge-Example Liebert XDC DX R-407c Circuit Volume-Air Cooled UnitsCalculating refrigerant charge-example Worksheet to calculate refrigerant chargeElectrical Chilled Water PipingOutdoor condenser charge-R-407c Indoor water/glycol cooled module R-407c refrigerant chargeOptional Features Liebert XDO Liebert XDO Standard FeaturesLeft Side XDO 24-1/8 Rear of XDO Liebert XDO internal mounting location Liebert XDO top and front electrical access points Liebert XDV Standard FeaturesLiebert XDV dimensions Optional Features-Liebert XDVDetail Area a Detail a Power Source Liebert XDV electrical connections for CSA-approved units Suspending single Liebert XDV from Unistruts Page Liebert Xdcf Standard Features Liebert XDPXD CoolFrame, XDH, XDO or XDV Liebert Xdcf Mechanical Considerations Liebert TMReturn Pipe Liebert Xdcf Installation Considerations Liebert Xdcf Piping Connection Methods and PointsEgenera BladeFrame Liebert XDH Standard Features Optional Features-Liebert XDHHeader System Supply and return piping connections Liebert XDH dimensionsRear XD Cooling Module Either 5/8 or 7/8 Or 2-5/8 O.DRecommended Arc Refer to for detailsLiebert XD Flex Pipe assemblies, supply and return Liebert XD Flex Pipe KitLiebert XD Liebert XDV CoolFrame Liebert XDHLiebert XD Piping Dimensions and Features Piping Installation Method prefabricated headersTwo-port prefabricated piping legend Branch Piping Standard Run Long Run Four Port 186551G21 Four-port prefabricated piping legendBranch Piping Standard Run Long Run Five Port Five-port prefabricated piping legendBranch Piping Standard Run Long Run Ten Port 186650G51 Ten-port prefabricated piping legend33-1/8 990 1067 XDP160 Liebert XDP Standard FeaturesModel Pipe Connection Point 50/60 HZ Unit piping outlet connection sizes, inches, OD CuEnclosure Cover Customer Power Liebert XDC Optional Features Liebert XDC Standard FeaturesLiebert XD Chiller piping connection sizes Liebert XDC piping locationsLiebert XDC Water/Glycol Piping Connection Sizes Piping locations-floor stand and valve assembly Front view of Liebert XDC and electrical enclosures Switch Transformer Electrical handy box, factory-installed with cover Liebert XDC Extra Low Voltage field connections points Liebert XDC160 specifications Heat Rejection Equipment Performance DataPiping Connections Performance Data204 Liebert XDP160 specifications Liebert XDO16 specifications Liebert XDO20 specifications Pipe Connections without flex pipeSides, Front and Rear Liebert XDO20 dimensions-domestic and export Liebert XDV8 specifications Liebert XDV10 specifications Liebert XDV8 dimensions-domestic and export Liebert XDV10 dimensions-domestic and exportLiebert Xdcf specifications Liebert XDH specifications Specifications Specifications Page Iti Ne tTi n That