Emerson Xtreme Density manual Liebert XDH specifications

Page 80

 

 

 

 

 

 

Specifications

Table 41 Liebert XDH specifications

 

 

 

 

 

 

 

 

 

 

 

 

 

XDH20DKP-0

XDH32DKP-0

 

XDH20DSP-0

 

XDH32DSP-0

 

XDH20DK--0

XDH32DK--0

 

XDH20DS--0

 

XDH32DS--0

 

XDH20BKP-0

XDH32BKP-0

 

XDH20BSP-0

 

XDH32BSP-0

 

XDH20BK--0

XDH32BK--0

 

XDH20BS--0

 

XDH32BS--0

 

XDH20DKPE0

XDH32DKPE0

 

XDH20DSPE0

 

XDH32DSPE0

 

XDH20DK-E0

XDH32DK-E0

 

XDH20DS-E0

 

XDH32DS-E0

 

XDH20BKPE0

XDH32BKPE0

 

XDH20BSPE0

 

XDH32BSPE0

 

XDH20BK-E0

XDH32BK-E0

 

XDH20BS-E0

 

XDH32BS-E0

Models

(60Hz)

(60Hz)

 

(50/60Hz)

 

(50/60Hz)

 

XDH20, 60Hz Nominal (98ºF [37°C] EAT): 22kW/6.3 Tons

 

 

XDH20, 60Hz Maximum(105ºF [40°C] EAT): 25.5kW/7.3 Tons

 

 

XDH20, 50Hz Nominal (98ºF [37°C] EAT): 19kW / 5.4 Tons

 

Cooling Capacity

XDH20, 50Hz Maximum(116ºF [47°C] EAT): 25.5kW/7.3 Tons

 

XDH32, 60Hz Nominal (98ºF [37°C] EAT): 30kW/8.5 Tons

 

 

 

 

XDH32, 60Hz Maximum(105ºF [40°C] EAT): 34.5kW/7.3 Tons

 

 

XDH32, 50Hz Nominal (98ºF [37°C] EAT): 27kW / 7.7 Tons

 

 

XDH32, 50Hz Maximum(108ºF [42°C] EAT): 34.5kW/7.3 Tons

 

Conditions

Capacity rating is @ 55ºF (13ºC) Entering Fluid Temperature and 50ºF (10ºC) or lower dew

 

 

point

 

 

 

 

 

Electrical Requirements

 

 

 

 

 

 

Input

120V-1ph-60Hz

 

220-240V-1ph-50Hz, CE /

 

208-240V-1ph-60Hz, CSA

 

 

 

 

Input Power Connections

Two IEC320-C14 power inlets and two IEC

 

Two IEC320-C14 power inlets and two IEC

power cords with NEMA 5-15P connectors

 

power cords with IEC320-C14 receptacles

 

 

Full Load Amps

5

10

 

2.5

 

5

Power Consumption,

600

1200

 

575

 

1150

Nominal, Watts

 

 

 

 

 

 

 

 

Dimensions, inches (mm)

 

 

 

 

 

 

Height—Unit Only

 

78 (1981)

 

 

 

 

 

 

 

 

 

Height—Including

 

80 (2032)

 

 

Pipe Connections

 

 

 

 

 

 

 

 

 

Width

 

12 (305)

 

 

 

 

 

 

 

Depth

 

42 (1067)

 

 

 

 

 

 

 

 

 

Weight, lb (kg)

 

 

 

 

 

 

Unit Only

233 (106)

246 (112)

 

233 (106)

 

246 (112)

 

 

 

 

 

 

 

Shipping Weight

317 (144)

330 (150)

 

317 (144)

 

330 (150)

 

 

 

 

 

 

 

Number of Fans

 

 

6

 

 

Airflow, Nominal,

2500 (4248)

4000 (6796)

 

2428 (4125)

 

3850 (6541)

ft3/min (m3/hr)

 

 

 

 

 

 

 

 

Audible Noise,

81 dBa

86 dBa

 

81 dBa

 

86 dBa

Sound Power

 

 

 

 

 

 

 

 

Pipe Connections

 

 

 

 

 

 

Refrigerant Supply

1/2" OD,

Cu (optional 1/2" threaded one-shot coupling on the unit)

 

 

 

Refrigerant Return

7/8" OD,

Cu (optional 7/8" threaded one-shot coupling on the unit)

 

 

 

 

Serviceable Parts

 

Fans and electrical components

 

Cabinet Exterior Finish

 

Black, matte finish, heat-fused powder coat

 

 

 

Condensate Sensing (factory-installed)

 

Options

Dry contact outgoing signal (24VAC - 1A maximum)

 

 

One-shot style flex pipe connections

 

 

 

 

 

 

 

 

 

 

Uni-directional or bi-directional air diffusers

 

 

 

 

 

 

 

 

Agency

 

 

 

 

 

 

Approvals

CSA 60Hz

 

CE 50Hz, CSA 50/60Hz

 

 

 

 

 

 

 

74

Image 80
Contents Liebert Xtreme Density Page Table of Contents Specifications XDH and Liebert XdcfIii Tables Liquid Liquid/Vapor Mix CoolFrame, XDH Direct and Indirect System Configurations European Union Fluorinated Greenhouse Gas RequirementsLiebert Heat Rejection Air Cooled or Water/Glycol Cooled Pumped RefrigerantLiebert XDO-Overhead Cooling Module Liebert XDV-Vertical, Above-Cabinet Cooling Module Liebert XDH-Horizontal Cooling Module Liebert Xdcf Liebert Xdcf units on BladeFrame EX cabinetsLiebert XDA-Air Flow Enhancer Liebert XDP-Pumping Unit Liebert XDP Minimum LoadLiebert XDC-Refrigerant Chiller Liebert XDC Minimum LoadLiebert XD field-installed port kits header connection size Liebert XD PipingLiebert XD Field Piping Flexible Piping Kit Prefabricated HeadersDetermining Cooling Equipment Needs Implementing a Hot-Aisle/Cold Aisle Design Hot aisle-cold aisle arrangement with under-floor sourceDetermine Cooling Requirements and Select Liebert XD System Calculate the Heat Load to be Handled by Liebert XD SystemAirflow Requirements for Liebert XD Solutions Configuring a Liebert XD SystemSelecting Liebert XD Cooling Modules Number of Modules Supported by a Liebert XDP or Liebert XDCLiebert XDO Placement Determining Spacing of Liebert XDOs in an AisleLiebert XDO spacing-horizontal and vertical Input Information Step Results Liebert XDV Unit PlacementLiebert XDV is suspended From ceiling structure Liebert Xdcf Placement Liebert Xdcf unit mounting locationsLiebert XDH Placement Liebert XDP/Liebert XDC PlacementInterlaced piping arrangement For enhanced protectionProtection Interlaced piping arrangement for enhanced protectionFor enhanced Liebert XD Refrigerant Liebert XD Piping System DesignSupply, return pipe sizes for refrigerant loop Key to Piping Pipe Function Size / Equivalent Pipe LengthLiebert XD Piping Slope Bypass Flow ControllersRefrigerant Pumped XD CoolFrame, XDH, XDO or XDVLiebert XDP Liebert XDC System refrigerant charge for the supply and return mains Determining Refrigerant VolumeLiebert XDP/Liebert XDC Pumped R-134a Circuit Volume Return Line Diameter 5/8 Return Line DiameterLiebert XDC DX R-407c Circuit Volume-Air Cooled Units Calculating Refrigerant Charge-ExampleCalculating refrigerant charge-example Worksheet to calculate refrigerant chargeChilled Water Piping ElectricalOutdoor condenser charge-R-407c Indoor water/glycol cooled module R-407c refrigerant chargeLiebert XDO Standard Features Optional Features Liebert XDOLeft Side XDO 24-1/8 Rear of XDO Liebert XDO internal mounting location Liebert XDV Standard Features Liebert XDO top and front electrical access pointsOptional Features-Liebert XDV Liebert XDV dimensionsDetail Area a Detail a Power Source Liebert XDV electrical connections for CSA-approved units Suspending single Liebert XDV from Unistruts Page XD CoolFrame, XDH, XDO or XDV Liebert Xdcf Standard FeaturesLiebert XDP Return Pipe Liebert Xdcf Mechanical ConsiderationsLiebert TM Egenera BladeFrame Liebert Xdcf Installation ConsiderationsLiebert Xdcf Piping Connection Methods and Points Header System Liebert XDH Standard FeaturesOptional Features-Liebert XDH Liebert XDH dimensions Supply and return piping connectionsOr 2-5/8 O.D Rear XD Cooling Module Either 5/8 or 7/8Recommended Arc Refer to for detailsLiebert XD Flex Pipe Kit Liebert XD Flex Pipe assemblies, supply and returnLiebert XD Liebert XDV CoolFrame Liebert XDHTwo-port prefabricated piping legend Liebert XD Piping Dimensions and FeaturesPiping Installation Method prefabricated headers Four-port prefabricated piping legend Branch Piping Standard Run Long Run Four Port 186551G21Five-port prefabricated piping legend Branch Piping Standard Run Long Run Five PortTen-port prefabricated piping legend Branch Piping Standard Run Long Run Ten Port 186650G51Liebert XDP Standard Features 33-1/8 990 1067 XDP160Unit piping outlet connection sizes, inches, OD Cu Model Pipe Connection Point 50/60 HZEnclosure Cover Customer Power Liebert XDC Standard Features Liebert XDC Optional FeaturesLiebert XDC piping locations Liebert XD Chiller piping connection sizesLiebert XDC Water/Glycol Piping Connection Sizes Piping locations-floor stand and valve assembly Front view of Liebert XDC and electrical enclosures Switch Transformer Electrical handy box, factory-installed with cover Liebert XDC Extra Low Voltage field connections points Liebert XDC160 specifications Performance Data Heat Rejection EquipmentPiping Connections Performance Data204 Liebert XDP160 specifications Liebert XDO16 specifications Sides, Front and Rear Liebert XDO20 specificationsPipe Connections without flex pipe Liebert XDO20 dimensions-domestic and export Liebert XDV8 specifications Liebert XDV10 specifications Liebert Xdcf specifications Liebert XDV8 dimensions-domestic and exportLiebert XDV10 dimensions-domestic and export Liebert XDH specifications Specifications Specifications Page Ne t ItiTi n That