Emerson manual Liebert CW Performance DATA-MODELS with EC FANS, 50 & 60 HZ, Connection Sizes

Page 8

Liebert CW Performance Data—Models with EC Fans, 50 & 60 Hz

2.0LIEBERT CW PERFORMANCE DATA—MODELS WITH EC FANS, 50 & 60 HZ

 

CW106D

CW114D

 

CW181D

 

 

 

 

 

Capacity Data BTU/Hr (kW) {Based on 45°F (7.2°C) Entering Water. 10°F Water Rise}

 

75°F DB, 62.5°F WB (23.9°C DB, 16.9°C WB) 50% RH *

 

 

 

Total -kBTUH (kw)

435 (127.5)

552 (161.7)

 

813 (238.2)

Sensible - kBTUH (kw)

362 (106.1)

423 (123.9)

 

612 (179.3)

Flow Rate-GPM (Vs)

92.1 (5.8)

116.3 (7.4)

 

179.3 (11.4)

Press. Drop- ft (kPa)

27.8 (83.0)

50.2 (149.8)

 

40.0 (119.4)

75°F DB, 61°F WB (23.9°C DB, 16.1 °C WB) 45°% RH *

 

 

 

Total -kBTUH (kw)

395 (115.7)

494 (144.7)

 

725 (212.4)

Sensible - kBTUH (kw)

368 (107.8)

427 (125.1)

 

617 (180.8)

Flow Rate-GPM (Vs)

84.0 (5.8)

104.8 (6.6)

 

153.4 (9.7)

Press. Drop- ft (kPa)

23.5 (70.1)

41.5 (123.8)

 

29.3 (87.4)

72°F DB, 60°F WB (22.2°C DB, 15.5°C WB) 50% RH *

 

 

 

Total -kBTUH (kw)

341 (99.9)

435 (127.5)

 

642 (188.0)

Sensible - kBTUH (kw)

316 (92.6)

371 (108.7)

 

537 (157.3)

Flow Rate-GPM (Vs)

73.4 (4.6)

93.2 (5.9)

 

136.8 (8.7)

Press. Drop- ft (kPa)

18.3 (54.6)

33.4 (99.7)

 

23.3 (69.5)

72°F DB, 58.6°F WB (22.2°C DB, 14.8°C WB) 45% RH *

 

 

 

Total -kBTUH (kw)

323 (94.6)

395 (115.7)

 

586 (171.7)

Sensible - kBTUH (kw)

323 (94.6)

378 (110.8)

 

546 (160.0)

Flow Rate-GPM (Vs)

69.6 (4.4)

85.2 (5.4)

 

125.7 (8.0)

Press. Drop- ft (kPa)

16.6 (49.5)

28.3 (84.4)

 

19.7 (58.7)

Fan Data

 

 

 

 

Air Volume CFM (CMH)

17,600 (29,920)

17,360 (29,512)

 

24,000 (40,800)

Fan Motor hp Max, (kW), ea, qty 3

4.2 (3.4)

4.2 (3.4)

 

5.2 (4.3)

Ext. Static Press. in. of water (Pa)

0.2 (50)

0.2 (50)

 

0.2 (50)

Chilled Water Coil

 

 

 

 

Face Area sq. ft. (m2)

36.3 (3.4)

36.3 (3.4)

 

71.2 (6.6)

No. of Rows

4

6

 

6

Face Velocity FPM (m/s)

471 (2.3)

471 (2.3)

 

337 (1.6)

Valve Cv

46.2

46.2

 

46.2 qty2

Valve Size - inches

2

2

 

2

Electric Reheat - Three (3) Stage, Fin Tube

 

 

 

 

Capacity BTU/HR (kW)

102,390 (30)

102,390 (30)

 

102,390 (30)

Infrared Humidifier

 

 

 

 

Capacity-Lb. Per Hr. (kg/h)

22.1 (10.0)

22.1 (10.0)

 

22.1 (10.0)

kW

9.6

9.6

 

9.6

FILTER SECTION - DISPOSABLE TYPE - Nominal Sizes and Quantities, MERV7 or MERV11 (option)

Nominal Size, in

24"x31"

24"x31"

21-1/2" x 24"

Quantity

5

5

10

CONNECTION SIZES

 

 

 

Chilled Water-O.D. Copper

2-1/8

2-5/8

3-1/8

Infrared Humidifier-O.D. Copper

1/4

1/4

1/4

Condensate Drain-FPT

1-1/4

 

 

Weight-lb (kg)- Installed

1950 (885)

2090 (949)

2800 (1271)

* Unit capacity data is “net,” and is certified to ASHRAE 127-2007 rating standard

4

Image 8
Contents Liebert CW Page Figures Page Liebert CW Model Number Nomenclature = SFA= Forward-Curved Centrifugal Fan with Standard MotorLiebert CW Performance DATA-50 & 60 HZ Systems 80F DB, 66.8F WB 26.6C DB, 19.3C WB 50% RHReheat Section Liebert CW Performance DATA-MODELS with EC FANS, 50 & 60 HZ Connection SizesElectrical DATA-UNITS with EC Fans CW106 and CW114 Electrical Data with EC FansCW181 Electrical Data with EC Fans Models With Pre-Filters Dimensional DataDimensional Data. inches mm Net Weight Model Lb kg Unit Dimensional Data Floor Cutout DimensionsDimensional Data, inches mm Net Weight Model Lb kg Models with PRE-FILTERSFront View Models With Rear Return Unit Dimensional DataFloor Cutout Dimensions Unit Dimensional Data Duct Connection DataUpflow Duct Connection Data CW026-CW084 TOP- Front Supply ShownFront of Unit Duct Connection DataTOP-FRONT Supply Shown IR/SGH Electrical SpecificationsElectrical data-50 Hz systems Electrical data-60 Hz Systems Models / Motor Volts 208 230 460 575 CW026FLA LRA Summary Design RequirementsSubmittals Cabinet and Frame ConstructionUser Menus Shall be Defined as Follows Service Menus Shall be Defined as Follows Liebert iCOM Wall-Mount Large Graphic Display Optional Chilled Water Control Valve Flow Switch-Optional High Pressure Chilled Water Control Valve-OptionalFrame Chilled Water Coil Variable Speed Drive-OptionalExecution Installation of Precision Cooling UnitsField Quality Control Page Ne t ItiTi n That