Page 26

Guide Specifications

2.11.6Floor Stand

The floor stand shall be constructed of a heliarc-welded, tubular steel frame. The floor stand shall have adjustable legs with vibration isolation pads. The floor stand shall be ____ inches high.

2.11.6.1 Floor Stand Turning Vane

A factory-supplied, field-mounted turning vane shall be provided.

2.11.6.2 Smoke Sensor

The smoke sensor shall immediately shut down the environmental control system and activate the alarm system when activated. The smoke sensor shall be mounted in the electrical panel with the sensing element in the return air compartment.

2.11.6.3 Liebert SiteScan® Site Monitoring System

Provide a Liebert SiteScan monitor system with the Liebert CW. The Liebert SiteScan shall have the capability to monitor and change (at the user direction) the temperature setpoints and sensitivities of each unit. The printer shall provide the user with chronological alarm information. It shall also be capable of being programmed to print out environmental conditions or operating modes at each unit.

3.0EXECUTION

3.1Installation of Precision Cooling Units

3.1.1General

Install precision cooling units in accordance with manufacturer’s installation instructions. Install units plumb and level, firmly anchored in locations indicated, and maintain manufacturer’s recom- mended clearances.

3.1.2Electrical Wiring

Install and connect electrical devices furnished by manufacturer but not specified to be factory mounted. Furnish copy of manufacturer’s electrical connection diagram submittal to electrical con- tractor.

3.1.3Piping Connections

Install and connect devices furnished by manufacturer but not specified to be factory-mounted. Fur- nish copy of manufacturer’s piping connection diagram submittal to piping contractor.

3.2Field Quality Control

Startup mainframe coolant units in accordance with manufacturer’s startup instructions. Test con- trols and demonstrate compliance with requirements.

22

Image 26
Contents Liebert CW Page Figures Page = Forward-Curved Centrifugal Liebert CW Model Number Nomenclature= SFA Fan with Standard MotorLiebert CW Performance DATA-50 & 60 HZ Systems 80F DB, 66.8F WB 26.6C DB, 19.3C WB 50% RHReheat Section Liebert CW Performance DATA-MODELS with EC FANS, 50 & 60 HZ Connection SizesElectrical DATA-UNITS with EC Fans CW106 and CW114 Electrical Data with EC FansCW181 Electrical Data with EC Fans Models With Pre-Filters Dimensional DataDimensional Data. inches mm Net Weight Model Lb kg Dimensional Data, inches mm Net Weight Model Lb kg Unit Dimensional DataFloor Cutout Dimensions Models with PRE-FILTERSFront View Models With Rear Return Unit Dimensional DataFloor Cutout Dimensions Unit Dimensional Data Duct Connection DataFront of Unit Upflow Duct Connection Data CW026-CW084TOP- Front Supply Shown Duct Connection DataTOP-FRONT Supply Shown IR/SGH Electrical SpecificationsElectrical data-50 Hz systems Electrical data-60 Hz Systems Models / Motor Volts 208 230 460 575 CW026FLA LRA Submittals SummaryDesign Requirements Cabinet and Frame ConstructionUser Menus Shall be Defined as Follows Service Menus Shall be Defined as Follows Liebert iCOM Wall-Mount Large Graphic Display Optional Chilled Water Control Valve Frame Chilled Water Coil Flow Switch-OptionalHigh Pressure Chilled Water Control Valve-Optional Variable Speed Drive-OptionalExecution Installation of Precision Cooling UnitsField Quality Control Page Ti n Ne tIti That