Guide Specifications

2.5.1.4Alarms

The Liebert iCOM control shall activate an audible and visual alarm in event of any of the following conditions:

High Temperature

Low Temperature

High Humidity

Low Humidity

Main Fan Overload (opt)

Change Filters

Loss of Air Flow

Loss of Power

Custom Alarm (#1 to #4)

Custom alarms are four customer accessible alarm inputs to be indicated on the front panel. Custom alarms can be identified with prepared (programmed) labels for the following frequently used inputs:

Leak Under Floor

Smoke Detected

Loss of Water Flow

Standby Unit On

User customized text can be entered for two of the four custom alarms.

Each alarm (unit and custom) can be separately enabled or disabled, selected to activate the common alarm, and programmed for a time delay of 0 to 255 seconds.

2.5.1.5Audible Alarm

The audible alarm shall annunciate any alarm that is enabled by the operator.

2.5.1.6Common Alarm

A programmable common alarm shall be provided to interface user selected alarms with a remote alarm device.

2.5.1.7Remote Monitoring

All alarms shall be communicated to the Liebert site monitoring system with the following informa- tion: date and time of occurrence, unit number and current temperature and humidity.

2.5.1.8Diagnostics

The control system and electronic circuitry shall be provided with self-diagnostics to aid in trouble- shooting. The microcontroller board shall be diagnosed and reported as pass/not pass. Control inputs shall be indicated as on or off at the front monitor panel. Control outputs shall be able to be turned On or Off from the front monitor panel without using jumpers or a service terminal.

2.5.1.9Data Collection

The control system shall maintain accumulative operating hours of compressors, fan motor and Econ- O-Coil. The 10 most recent alarms shall be retained.

2.5.1.10 Communication

The Liebert iCOM control shall be compatible with Liebert remote monitoring and control devices.

2.6Chilled Water Control Valve

The water circuit shall include a 3-way (2-way) modulating valve. The Liebert iCOM positions the valve in response to room conditions. Cooling capacity will be controlled by bypassing chilled water around the coil.

20

Image 24
Contents Liebert CW Page Figures Page Liebert CW Model Number Nomenclature = SFA= Forward-Curved Centrifugal Fan with Standard MotorLiebert CW Performance DATA-50 & 60 HZ Systems 80F DB, 66.8F WB 26.6C DB, 19.3C WB 50% RHReheat Section Liebert CW Performance DATA-MODELS with EC FANS, 50 & 60 HZ Connection SizesCW106 and CW114 Electrical Data with EC Fans CW181 Electrical Data with EC FansElectrical DATA-UNITS with EC Fans Dimensional Data Dimensional Data. inches mm Net Weight Model Lb kgModels With Pre-Filters Unit Dimensional Data Floor Cutout DimensionsDimensional Data, inches mm Net Weight Model Lb kg Models with PRE-FILTERSFront View Unit Dimensional Data Floor Cutout DimensionsModels With Rear Return Unit Dimensional Data Duct Connection DataUpflow Duct Connection Data CW026-CW084 TOP- Front Supply ShownFront of Unit Duct Connection DataTOP-FRONT Supply Shown Electrical Specifications Electrical data-50 Hz systemsIR/SGH Electrical data-60 Hz Systems Models / Motor Volts 208 230 460 575 CW026FLA LRA Summary Design RequirementsSubmittals Cabinet and Frame ConstructionUser Menus Shall be Defined as Follows Service Menus Shall be Defined as Follows Liebert iCOM Wall-Mount Large Graphic Display Optional Chilled Water Control Valve Flow Switch-Optional High Pressure Chilled Water Control Valve-OptionalFrame Chilled Water Coil Variable Speed Drive-OptionalInstallation of Precision Cooling Units Field Quality ControlExecution Page Ne t ItiTi n That