Emerson CW Summary, Design Requirements, Submittals, Cabinet and Frame Construction, Fan Section

Page 20

Guide Specifications

GUIDE SPECIFICATIONS

1.0GENERAL

1.1Summary

These specifications describe requirements for a precision environmental control system. The system shall be designed to maintain temperature conditions in the rooms containing electronic equipment.

The manufacturer shall design and furnish all equipment to be fully compatible with heat dissipation requirements of the room.

1.2Design Requirements

The precision environmental control system shall be a Liebert self-contained factory assembled unit with (upflow) (down-flow) air delivery. The system shall have a total cooling capacity of ____ BTU/

HR, (kW) with a sensible cooling capacity of ____ BTU/ HR (kW) based on an entering air temperature

of ____ °F (°C) dry bulb and ____ °F (°C) wet bulb. The unit is to be supplied with ____ volt ____ ph

____ Hz electrical service.

1.3Submittals

Submittals shall be provided with the proposal and shall include: Single-Line Diagrams; Dimen- sional, Electrical, and Capacity Data; Piping and Electrical Connection Drawings.

2.0PRODUCT

2.1Cabinet and Frame Construction

The frame shall be constructed of heliarc welded tubular steel. It shall be painted using the auto- phoretic coating process for maximum corrosion protection. The exterior panels shall be insulated with a minimum 1 in. (25.4mm), 1.5 lb. (0.68 kg) density fiber insulation. The main front panel shall have captive 1/4 turn fasteners. The main unit color shall be _________. The accent color shall be

_________. The exterior panels shall be powder coated.

2.2Filter Chamber

The filter chambers shall be an integral part of the system, located within the cabinet serviceable from either end of the unit. The filters shall be rated not less than ____% efficiency (based on

ASHRAE 52.1).

For models CW106 and CW114, the filters shall be serviceable from the front of the unit.

2.3Fan Section

The fan shall be the centrifugal type, double width double inlet, and shall be factory-balanced as a completed assembly. The shaft shall be heavy duty steel with self-aligning ball bearings with a mini- mum life span of 100,000 hours. The fan motor shall be ____ hp at 1750 RPM at 60 Hz (1450 RPM at

50 Hz) and mounted on an adjustable slide base. The drive package shall be two-belt, variable speed, sized for 200% of the fan motor horsepower. The fans shall be located to draw air over the A-frame coil to ensure even air distribution and maximum coil performance.

2.3Electronically Commutated (EC) Fan

The fan shall be the plug/plenum type, single inlet and shall be dynamically balanced. The fan motor shall be 4.2 hp, 1520 rpm maximum operating speed. The drive package shall be direct drive Electron- ically Commutated, variable speed. The fans shall be located to draw air over the A-frame coil to ensure even air distribution and maximum coil performance.

2.4Liebert iCOMMicroprocessor Control With Small Graphic Display

The Liebert iCOM unit control shall be factory-set for Intelligent Control which uses “fuzzy logic” and “expert systems” methods. Proportional and Tunable PID shall also be user selectable options. Inter- nal unit component control shall include the following:

16

Image 20
Contents Liebert CW Page Figures Page Liebert CW Model Number Nomenclature = SFA= Forward-Curved Centrifugal Fan with Standard MotorLiebert CW Performance DATA-50 & 60 HZ Systems 80F DB, 66.8F WB 26.6C DB, 19.3C WB 50% RHReheat Section Liebert CW Performance DATA-MODELS with EC FANS, 50 & 60 HZ Connection SizesElectrical DATA-UNITS with EC Fans CW106 and CW114 Electrical Data with EC FansCW181 Electrical Data with EC Fans Models With Pre-Filters Dimensional DataDimensional Data. inches mm Net Weight Model Lb kg Unit Dimensional Data Floor Cutout DimensionsDimensional Data, inches mm Net Weight Model Lb kg Models with PRE-FILTERSFront View Models With Rear Return Unit Dimensional DataFloor Cutout Dimensions Unit Dimensional Data Duct Connection DataUpflow Duct Connection Data CW026-CW084 TOP- Front Supply ShownFront of Unit Duct Connection DataTOP-FRONT Supply Shown IR/SGH Electrical SpecificationsElectrical data-50 Hz systems Electrical data-60 Hz Systems Models / Motor Volts 208 230 460 575 CW026FLA LRA Summary Design RequirementsSubmittals Cabinet and Frame ConstructionUser Menus Shall be Defined as Follows Service Menus Shall be Defined as Follows Liebert iCOM Wall-Mount Large Graphic Display Optional Chilled Water Control Valve Flow Switch-Optional High Pressure Chilled Water Control Valve-OptionalFrame Chilled Water Coil Variable Speed Drive-OptionalExecution Installation of Precision Cooling UnitsField Quality Control Page Ne t ItiTi n That