Emerson CW manual Service Menus Shall be Defined as Follows

Page 22

Guide Specifications

The Service Menus Shall be Defined as Follows

Setpoints: Menu shall allow setpoints within the following ranges:

Temperature Setpoint 65-85ºF (18-29ºC)*

Temperature Sensitivity +1-10ºF (0.6-5.6ºC)

Humidity Setpoint 20-80% RH*

Humidity Sensitivity 1-30% RH

High Temperature Alarm 35-90ºF (2-32ºC)

Low Temperature Alarm 35-90ºF (2-32ºC)

High Humidity Alarm 15-85% RH

Low Humidity Alarm 15-85% RH

*The microprocessor may be set within these ranges, however, the unit may not be able to control to extreme combinations of temperature and humidity.

Standby Settings/Lead-Lag: Menu shall allow planned rotation or emergency rotation of operating and standby units.

Timers/Sleep Mode: Menu shall allow various customer settings for turning on/off unit.

Alarm Setup: Menu shall allow customer settings for alarm notification (audible/local/remote). The following alarms shall be available:

High Temperature

Low Temperature

High Humidity

Low Humidity

Main Fan Overload (Optional)

Humidifier Problem

Change Filter

Fan Failure

Unit Off

Audible Alarm: The audible alarm shall annunciate any alarm that is enabled by the operator.

Common Alarm: A programmable common alarm shall be provided to interface user selected alarms with a remote alarm device.

Remote Monitoring: All alarms shall be communicated to the Liebert monitoring system with the

following information: Date and time of occurrence, unit number and present temperature and humidity.

Sensor Calibration: Menu shall allow unit sensors to be calibrated with external sensors.

Maintenance/Wellness Settings: Menu shall allow reporting of potential component problems before they occur.

Options Setup: Menu shall provide operation settings for the installed components.

System/Network Setup: Menu shall allow Unit-to-Unit (U2U) communication and setup for team- work modes of operation (up to 32 units).

Teamwork Modes of Operation: Saves energy by preventing operation of units in opposite modes multiple units.

Auxiliary Boards: Menu shall allow setup of optional expansion boards.

Diagnostics/Service Mode: The Liebert iCOM control shall be provided with self-diagnostics to aid in troubleshooting. The microcontroller board shall be diagnosed and reported as pass/not pass. Con- trol inputs shall be indicated as on or off at the front display. Control outputs shall be able to be turned on or off from the front display without using jumpers or a service terminal. Each control out- put shall be indicated by an LED on a circuit board.

18

Image 22
Contents Liebert CW Page Figures Page = Forward-Curved Centrifugal Liebert CW Model Number Nomenclature= SFA Fan with Standard MotorLiebert CW Performance DATA-50 & 60 HZ Systems 80F DB, 66.8F WB 26.6C DB, 19.3C WB 50% RHReheat Section Liebert CW Performance DATA-MODELS with EC FANS, 50 & 60 HZ Connection SizesCW181 Electrical Data with EC Fans CW106 and CW114 Electrical Data with EC FansElectrical DATA-UNITS with EC Fans Dimensional Data. inches mm Net Weight Model Lb kg Dimensional DataModels With Pre-Filters Dimensional Data, inches mm Net Weight Model Lb kg Unit Dimensional DataFloor Cutout Dimensions Models with PRE-FILTERSFront View Floor Cutout Dimensions Unit Dimensional DataModels With Rear Return Unit Dimensional Data Duct Connection DataFront of Unit Upflow Duct Connection Data CW026-CW084TOP- Front Supply Shown Duct Connection DataTOP-FRONT Supply Shown Electrical data-50 Hz systems Electrical SpecificationsIR/SGH Electrical data-60 Hz Systems Models / Motor Volts 208 230 460 575 CW026FLA LRA Submittals SummaryDesign Requirements Cabinet and Frame ConstructionUser Menus Shall be Defined as Follows Service Menus Shall be Defined as Follows Liebert iCOM Wall-Mount Large Graphic Display Optional Chilled Water Control Valve Frame Chilled Water Coil Flow Switch-OptionalHigh Pressure Chilled Water Control Valve-Optional Variable Speed Drive-OptionalField Quality Control Installation of Precision Cooling UnitsExecution Page Ti n Ne tIti That