Emerson CW manual User Menus Shall be Defined as Follows

Page 21

Guide Specifications

System Auto Restart - The auto restart feature will automatically restart the system after a power failure. Time delay is programmable.

Sequential Load Activation - On initial startup or restart after power failure, each operational load is sequenced with a minimum of one second delay to minimize total inrush current.

Hot Water Flush Cycles - Hot water reheat coils and Econ-O-Coils are periodically flushed to pre- vent a buildup of contaminants.

Predictive Humidity Control - calculates the moisture content in the room and prevents unneces- sary humidification and dehumidification cycles by responding to changes in dew point temperature.

The Liebert iCOM control shall be compatible with Liebert remote monitoring and control devices. Options are available for BMS interface via MODbus, Jbus, BACNet, Profibus and SNMP.

The Liebert iCOM control processor shall be microprocessor based with a 128x64 dot matrix graphic front monitor display and control keys for user inputs mounted in an ergonomic, aesthetically pleas- ing housing. The display & housing shall be viewable while the unit panels are open or closed. The controls shall be menu driven. The display shall be organized into three main sections: User Menus, Service Menus and Advanced Menus. The system shall display user menus for: active alarms, event log, graphic data, unit view/status overview (including the monitoring of room conditions, operational status in % of each function, date and time), total run hours, various sensors, display setup and ser- vice contacts. A password shall be required to make system changes within the service menus. Service menus shall include: setpoints, standby settings (lead/lag), timers/sleep mode, alarm setup, sensor calibration, maintenance/wellness settings, options setup, system/network setup, auxiliary boards and diagnostics/service mode. A password shall be required to access the advanced menus which include the factory settings and password menus.

The User Menus Shall be Defined as Follows

Active Alarms: Unit memory shall hold the 200 most recent alarms with time and date stamp for each alarm.

Event Log: Unit memory shall hold the 400 most recent events with ID number, time and date stamp for each event.

Graphic Data View: Eight graphic records shall be available: return air temperature, return air humidity, supply air temperature, outdoor temperature and four custom graphs.

Unit View: Status Overview: Simple or Graphical Unit Viewsummary displays shall include tem- perature and humidity values, active functions (and percent of operation) and any alarms of the host unit.

Total Run Hours: Menu shall display accumulative component operating hours for major compo- nents including fan motor, humidifier and reheat.

Various Sensors: Menu shall allow setup and display of optional custom sensors. The control shall include four customer accessible analog inputs for sensors provided by others. The analog inputs shall accept a 4 to 20mA signal. The user shall be able to change the input to 0 to 5VDC or 0 to 10VDC if desired. The gains for each analog input shall be programmable from the front display. The analog inputs shall be able to be monitored from the front display.

Display Setup: Customer shall pre-select the desired grouping of display languages at the time of the order from the following choices:

Group 1: English, French, Italian, Spanish, German

Group 2: English, Russian, Greek

Group 3: English, Japanese, Chinese, Arabic

Service Contacts: Menu shall allow display of local service contact name and phone number.

17

Image 21
Contents Liebert CW Page Figures Page = SFA Liebert CW Model Number Nomenclature= Forward-Curved Centrifugal Fan with Standard Motor80F DB, 66.8F WB 26.6C DB, 19.3C WB 50% RH Liebert CW Performance DATA-50 & 60 HZ SystemsReheat Section Connection Sizes Liebert CW Performance DATA-MODELS with EC FANS, 50 & 60 HZCW106 and CW114 Electrical Data with EC Fans CW181 Electrical Data with EC FansElectrical DATA-UNITS with EC Fans Dimensional Data Dimensional Data. inches mm Net Weight Model Lb kgModels With Pre-Filters Floor Cutout Dimensions Unit Dimensional DataDimensional Data, inches mm Net Weight Model Lb kg Models with PRE-FILTERSFront View Unit Dimensional Data Floor Cutout DimensionsModels With Rear Return Duct Connection Data Unit Dimensional DataTOP- Front Supply Shown Upflow Duct Connection Data CW026-CW084Front of Unit Duct Connection DataTOP-FRONT Supply Shown Electrical Specifications Electrical data-50 Hz systemsIR/SGH Models / Motor Volts 208 230 460 575 CW026 Electrical data-60 Hz SystemsFLA LRA Design Requirements SummarySubmittals Cabinet and Frame ConstructionUser Menus Shall be Defined as Follows Service Menus Shall be Defined as Follows Liebert iCOM Wall-Mount Large Graphic Display Optional Chilled Water Control Valve High Pressure Chilled Water Control Valve-Optional Flow Switch-OptionalFrame Chilled Water Coil Variable Speed Drive-OptionalInstallation of Precision Cooling Units Field Quality ControlExecution Page Iti Ne tTi n That