AC Input Power

AC Input Connector

AC Input Connector

The AC input connector is a standard wire clamp terminal block with 3-phase connectors and a chassis ground connector. The safety ground wire, alternatively, may be connected to the chassis using a ring tongue on the ground stud as shown in Figure 2.1.

Ground Connection

3-Phase Terminal Block Connectors

Figure 2.1 AC Input Connector

AC Input Wire

The manufacturer recommends the AC input wire specified in Table 2.1. This must be permanently connected to an approved AC distribution box with suitably rated over-current protection. If you require a special cord, contact the manufacturer.

Table 2.1 AC Wire Specification for 6000 Watt units

AC Input Voltage Range

Wire

 

 

190–242Vac, 47–63Hz,

4 x 10 AWG (3 wire plus safety ground), stranded

3-phase, 4 wire (standard)

copper, 60°C minimum, 300V, 0.800 in. maximum

 

cable diameter, rated for 25A.

 

 

342–500Vac, 47–63Hz,

4 x 14 AWG (3 wire plus safety ground), stranded

3-phase, 4 wire (HV-Input)

copper, 60°C minimum, 600V, 0.800 in. maximum

 

cable diameter, rated for 13A.

 

 

16

Operating Manual for XDC Series Slave Power Supply

Image 18
Contents XDC 6000 Watt Series Slave Power Supply TM-XDSL-01XN.book Page ii Tuesday, November 5, 2002 322 PM XDC 6000 Watt Series Limited Warranty What does this warranty not cover? Disclaimer Product Information About Your Power Supply Release Release 1.0Power Supply Safety Approvals CE Mark Unit complies with Canadian EMC requirements of ICES-001Viii Who Should Use This Manual RevisionsAbout This Manual Table of Contents Table of Contents Xii Features OverviewFront Panel Slave Front PanelAC Input Power AC Input Connector AC Input WireAC Wire Input Connection Attaching the AC Input Wires Current Sharing OverviewSetup Current Share Configuration Setup Sharing Network Specifications OperationAppendix A. Specifications and Characteristics Electrical Specifications-Summary Table A.3Specifications for 80V to 600V Models AC Line Input Specifications AC Line Input Voltage Operating RangesOutput Performance Specifications Programming Range for Voltage, Current, and PowerTypical Measurement Resolution Typical 31 kHz 62 kHz output ripple Minimum 4 ms at full load Environmental Specification International ApprovalsMechanical Specification Figure A.1 Power Supply DimensionsTM-XDSL-01XN.book Page 33 Tuesday, November 5, 2002 322 PM Xantrex Technology Inc