Xantrex Technology XDC 300-20SL, XDC 6000, XDC 80-75SL manual Typical 31 kHz 62 kHz output ripple

Page 31

TM-XDSL-01XN.book Page 29 Tuesday, November 5, 2002 3:22 PM

Specifications and Characteristics

Output Performance Specifications

8 Hour Drift Temperature Stability1

Voltage

0.02% of Vmax

 

 

Current

0.04% of Imax

 

 

Power

0.1% of Pmax

 

 

Temperature Coefficients

Remote Digital Interface

Voltage Programming

0.04% of Vmax/°C

Current Programming

0.06% of Imax/°C

Power Programming

0.1% of Pmax/°C

Voltage Readback

0.04% of Vmax/°C

Current Readback

0.06% of Imax/°C

Power Readback

0.1% of Pmax/°C

 

 

Switching Frequency

Typical 31 kHz; 62 kHz output ripple

Rise Time

5 to 95% step in output voltage.

Load Condition

Time (Max)

 

 

No Load

100 ms

 

 

Full Load

100 ms

 

 

Fall Time

For a programmed 95% to 5% step in output voltage.

Load Condition

Time (Max)

 

 

No Load 1

3 s

Full Load

50 ms

 

 

1. Fall time is 4s for 300 V and 600 V units.

Time Delay From Power On Until Output Stable

5 s maximum

(Within regulation envelope)

1. At 25°C ±5°C after 30 minutes full load operation

Release 1.0

29

Image 31
Contents XDC 6000 Watt Series Slave Power Supply TM-XDSL-01XN.book Page ii Tuesday, November 5, 2002 322 PM XDC 6000 Watt Series Limited Warranty What does this warranty not cover? Disclaimer Product Release Release 1.0 Information About Your Power SupplyPower Supply Safety Unit complies with Canadian EMC requirements of ICES-001 Approvals CE MarkViii Revisions Who Should Use This ManualAbout This Manual Table of Contents Table of Contents Xii Overview FeaturesSlave Front Panel Front PanelAC Input Power AC Input Wire AC Input ConnectorAC Wire Input Connection Attaching the AC Input Wires Overview Current SharingSetup Current Share Configuration Setup Sharing Network Operation SpecificationsAppendix A. Specifications and Characteristics Electrical Specifications-Summary Table A.3Specifications for 80V to 600V Models AC Line Input Voltage Operating Ranges AC Line Input SpecificationsProgramming Range for Voltage, Current, and Power Output Performance SpecificationsTypical Measurement Resolution Typical 31 kHz 62 kHz output ripple Minimum 4 ms at full load International Approvals Environmental SpecificationFigure A.1 Power Supply Dimensions Mechanical SpecificationTM-XDSL-01XN.book Page 33 Tuesday, November 5, 2002 322 PM Xantrex Technology Inc