Tripp Lite SU10KRT1X, SU10KRT3 Network Card, EPO Connection, RS-232 Serial Communications

Page 17

8 – Communications

Note: These connections are optional. The UPS system will function without these connections.

8-1 Network Card

The UPS system includes an internal network card that provides an Ethernet interface for remote monitoring and control of the UPS system. Refer to the network card documentation for additional information. Note: The network card must be removed in order to use the UPS system’s RS-232 port.

8-2 EPO Connection

Shorting the EPO terminals activates the EPO (emergency power off) function, which provides emergency shutdown of the UPS system.

8-3 RS-232 Serial Communications

Note: The network card must be removed in order to use the UPS system’s RS-232 port.

Use the included RS-232 (DB9) serial cable to connect the UPS system’s RS-232 serial port to a computer’s RS-232 serial port. Install the included software on the computer in order to monitor and control the UPS system. (See the software documentation for system requirements, installation instructions and additional information.)

RS-232 interface settings:

Baud Rate

2400 bps

 

 

Data Length

8 bits

 

 

Stop Bit

1 bit

 

 

Parity

None

 

 

RS-232 pin assignments:

9

8

7

6

5

4

3

2

1

Pin 3: RS-232 Rx

Pin 2: RS-232 Tx

Pin 5: Ground

17

Image 17
Contents Français EspañolIntroduction Important Safety InstructionsLocation Warnings Connection WarningsBattery Warnings Wiring WarningsExternal Battery Pack Rear Panel Rear Panel FeaturesUPS System Power Module Rear Panel UPS System Hardware Kit MountingMounting Rack PlacementPost Mounting Procedure Mounting Tower Tower Mounting ProcedureWiring Preparation WiringTerminal Block Diagram Electrical and Cable DataAC Input/Output Wiring Instructions External battery pack is required to operate the UPS system External Battery Pack ConnectionStandard Operation Control Panel FeaturesLCD Symbols Control Panel Error CodesNormal Mode Startup UPS System Settings and Measurements Battery Mode Startup Cold StartUPS System Shutdown Checking UPS System MeasurementsChanging Default Settings Settings and Special FunctionsInstallation UPS System PlacementStart-up Procedure Parallel Redundancy Operation OptionalNetwork Card CommunicationsEPO Connection RS-232 Serial CommunicationsUPS Detects Error While in Self-Test Mode TroubleshootingStorage and Service SpecificationsService StorageBattery Replacement Procedure Battery ReplacementRegulatory Compliance Identification Numbers WarrantyLimited Warranty