Tripp Lite SU10KRT3 Parallel Redundancy Operation Optional, UPS System Placement, Installation

Page 16

7 – Parallel Redundancy Operation (Optional)

DANGER! LETHAL HIGH VOLTAGE HAZARD!

All wiring should be performed by a qualified electrician, in accordance with the warnings in this manual and all applicable electrical and safety codes. Incorrect wiring may cause serious personal injury and property damage. Read, study and understand the warnings listed in Section 2 – Important Safety Instructions before proceeding.

Unpacking the Parallel Kit

 

T1

The parallel kit should include these parts:

• 2

RJ45 Parallel Communication Cables

 

,

 

 

C1

C1

C2

 

 

 

• 1

Parallel Communication Bracket

 

 

 

 

 

 

 

B1

 

 

 

 

 

 

 

 

 

C2

• 1

Cable Tie

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B1

UPS System Placement

In order to minimize the possibility of damage to the UPS system and maximize its operational lifespan, follow the location warnings listed in Section 2 – Important Safety Instructions. Remember to keep at least 30 cm clearance from the rear panel of the UPS system to the wall and do not block any of the UPS system’s front or rear ventilation openings.

Warning: The UPS system is very heavy—be careful when moving or lifting it.

Installation

1.To avoid noise interference, install each wire and cable separately to the input, output and battery.

2.Keep all input, output and battery wires and cables away from all connecting wires for parallel functions and control signals, including RJ45, RS-232, RS-485, USB and EPO. If this is not possible, set them at 90° angles or at least 20 cm apart.

3.Warning: The UPS system includes an EMI filter. To prevent potential leakage of hazardous current, confirm that the AC supply circuit is securely grounded.

Start-up Procedure

1.Position the UPS systems as specified above.

2.Connect the parallel communication cables C1 , C2 to the “Ring” loop at a maximum length of 7 m. Secure the cables with the parallel communication brackets B1 .

3.Arrange the power cables and the control signal cables according to UPS type. Make sure that all circuit breakers at the input and output ends are set to OFF.

4.For maintenance purposes, you may wish to purchase a manual bypass master panel (optional).

5.Set the terminal resistors of only two parallel UPS systems to the ON position. (For three units in parallel, switch on the terminal resistors of UPS #1 and #3 only. For four units in parallel, switch on the terminal resistors of UPS #1 and #4 only.)

6.Turn on the utility input breaker. Configure each UPS system’s operating mode to parallel mode (P 02) and set the IDs (e.g. UPS 1, ID=1) of the respective UPS systems. (See Section 6-6 – UPS System Settings and Measurements.) All parallel UPS system parameters except ID number must be same, including the number and type of connected battery packs.

7.If an external manual bypass master panel (optional) is installed, make sure the switch is in the “Bypass” position. Check to see if the UPS system is in bypass mode with output voltage available.

8.Turn on the output breaker and ensure that the connected loads are supplied with power via the manual bypass master panel.

9.Turn on the output breaker of the UPS and turn the switch of the manual bypass master panel to “UPS” position. The connected loads will be supplied with power via the UPS bypass loop.

10.Turn on each UPS system individually and make sure it is in inverter supply (normal) mode. Installation is now complete.

16

Image 16
Contents Español FrançaisImportant Safety Instructions IntroductionLocation Warnings Connection WarningsWiring Warnings Battery WarningsUPS System Power Module Rear Panel Rear Panel FeaturesExternal Battery Pack Rear Panel Mounting UPS System Hardware KitPost Mounting Procedure PlacementMounting Rack Tower Mounting Procedure Mounting TowerWiring Wiring PreparationTerminal Block Diagram Electrical and Cable DataAC Input/Output Wiring Instructions External Battery Pack Connection External battery pack is required to operate the UPS systemControl Panel Features Standard OperationControl Panel Error Codes LCD SymbolsNormal Mode Startup Battery Mode Startup Cold Start UPS System Settings and MeasurementsUPS System Shutdown Checking UPS System MeasurementsSettings and Special Functions Changing Default SettingsUPS System Placement InstallationStart-up Procedure Parallel Redundancy Operation OptionalCommunications Network CardEPO Connection RS-232 Serial CommunicationsTroubleshooting UPS Detects Error While in Self-Test ModeSpecifications Storage and ServiceService StorageBattery Replacement Battery Replacement ProcedureLimited Warranty WarrantyRegulatory Compliance Identification Numbers