Tripp Lite 10KVA owner manual Power ON/OFF 6kVA and 10kVA models only

Page 19

Power ON/OFF (6kVA and 10kVA models only)

1.Configure your UPS’s input and output: Put your UPS power module into setup mode by holding down both of its scroll buttons ( A and B ) at once. Scroll through the setup options (using A  or B ) and select the appropriate setting for each of the following options using the “SELECT” button B .

Input & Output Voltage: Select 200, 208 or 240 VAC.

Output Frequency: Your UPS will autoselect 50 or 60 Hz to match the input.

Economy Mode: Your UPS can provide on-line operation with zero transfer time. It can also operate in a more energy-efficient line-interactive mode. Select Economy On to put the UPS in line-interactive mode. Select Economy Off to put the UPS in on-line mode.

After you have set these options, “exit” the setup mode with the scroll button A , then exit bypass mode by holding the ON  button C down until you hear a beep.

2.Turn input to the UPS ON: If the UPS power module is connected to a transformer module, turn the tranformer module’s AC-to- UPS and Output Circuit Breakers D on. Turn the UPS power module’s Input Circuit Breaker E on. Press the UPS power module’s ON button C until you hear a beep to begin inverter operation. If your AC input is not providing power normally, you may “cold start” your UPS from battery. (Your battery must be at least partially charged for this operation to succeed.) Press and hold the ON C button until you hear a beep to start your UPS in ON BATTERY mode. Note that some electronic equipment may draw more amps during startup; when starting from battery, consider reducing the initial load on the UPS. Your UPS will perform a brief self-test and show the results on the LCD Display F . See “Startup Self-Test” in the “Operation” section for the display sequence.

3. Turn UPS output ON: Turn the UPS power module’s Output Circuit Breaker G ON. If the UPS is connected to a transformer module, turn the transformer module’s Manual Bypass Switch H from BYPASS to NORMAL and its Output Circuit Breaker ON. Your UPS will now provide power to connected equipment.

4.To turn the UPS power module and transformer module OFF: Press the UPS power module’s OFF button I until you hear a beep.

Your load will still be energized. The inverter is now off, but your UPS is not fully deactivated. The LCD Display F will show BYPASS MODE. Turn the UPS power module’s Input and Output Circuit Breakers ( E and G ) OFF. If the UPS is connected to a transformer module,

turn the transformer module’s power­ AC-to-UPS and Output Circuit Breakers D OFF. Your load will no longer be energized, and the LCD Display F will be dark.

G

 

 

E

 

 

 

G

D

D

 

E

 

 

 

 

 

H

H

 

 

6kVA Models

10kVA Models

 

 

 

F

C

A

B

I

6kVA & 10kVA Models

(Front Panel)

19

Image 19
Contents SmartOnline Single-Phase 5kVA, 6kVA & 10kVA Important Safety Warnings Post Mounting Mounting RackPost Telecom Mounting Mounting Tower Power Module Front Panel Controls FeaturesFeatures Rear Panel see page 9 for feature descriptions Features Rear Panel see page 9 for feature descriptions Features Rear Panel see page 9 for feature descriptions Power Module Feature Description Features Rear PanelConnection Battery Module Feature DescriptionPlug the power module into a wall receptacle Plug your equipment into the power moduleConnect the battery module to the power module Plug your equipment into the power module Transfer module Plug the transformer module into the power moduleHardwire the power module to a utility power source Hardwire the power module to your equipmentHardwire the transformer module to your equipment Connect the power module to the transformer moduleHardwire the transformer module to a utility Power source Select the transformer module’s input voltage Hardwire the power module to the transformer moduleConnection RS-232 Serial Communication Connection Optional ConnectionPower ON/OFF 5kVA models only Power ON/OFF 6kVA and 10kVA models only Manual Bypass Operation Startup Self-Test OperationFailed Self-Test Normal Operation On Battery AlarmOverload Messages Shutdown Messages Bypass MessagesRegulatory Compliance Identification Numbers ServiceYear Limited Warranty StorageSU6000RT3UXR SU10KRT3UHV* & SU10KRT3U SpecificationsManual del propietario Advertencias de seguridad importantes Montaje de 4 postes Montaje BastidorMontaje de 2 postes Telecomunicaciones Montaje en torre Controles del panel frontal del módulo de potencia CaracterísticasPage Módulo de batería para modelo de 6 kVA Módulo de potencia de 6 kVA Módulo de transformador de 6 kVAPage Descripción de características del módulo de potencia Características Panel continuaciónDescripción de características del módulo del transformador Descripción de características del módulo de batería ConexiónConecte el módulo de batería al módulo de potencia Conecte su equipo en el módulo de potenciaConecte el módulo de transformador en el módulo de potencia Cablee el módulo de potencia a su equipo Cablee el módulo de transformador a su equipo Conecte el módulo de potencia al módulo De transformadorCablee el módulo de potencia al módulo de transformador Seleccione el voltaje de entrada del módulo De transformadorEntrada Interruptor de Interruptores/pantalla Conexión de comunicación serie RS-232 Conexión opcionalEncendido y apagado sólo en modelos de 5 kVA Encendido y apagado Sólo en modelos de 6 kVA y 10 kVA Modelos de 6 kVA y 10 kVA Panel frontal Auto-prueba de arranque OperaciónFallo durante la auto-prueba Operación normal Alarma On BatteryMensajes de sobrecarga Mensajes de apagado Mensajes BypassGarantía limitada de 2 años Almacenamiento, Servicio y GarantíaAlmacenamiento ServicioLos paquetes incluyen EspecificacionesManuel de lutilisateur Avertissements pour Connexion de lEquipement Consignes de Sécurité ImportantesMontage à 4 supports Montage BaieMontage à 2 supports Telecom Montage Tour Caractéristiques Commandes de Panneau Avant de Module dAlimentation2524 Page Page Description des Caractéristiques de Module dAlimentation Caractéristiques Panneau Arrière suiteDescription des Caractéristiques de Module de Batterie ConnexionBranchez le module à piles au module dalimentation Connexion suiteBranchez votre équipement dans le module dalimentation Branchez le module dalimentation dans une prise muraleConnexion suite Soit 6kVA ou 10kVA + Modules de Batterie Câbler le module du transformateur à votre équipement Sélectionner la tension dentrée du module du Transformateur Sélectionner la tension dentrée du module du transformateur Connexion Communication Série RS-232 Connexion en OptionAlimentation en Marche/Arrêtée modèles 5kVA seulement Alimentation ON/OFF Modèles 6kVA et 10kVA seulement Opération Bypass Manuelle Modèles 6kVA et 10kVA seulement Autotest de Démarrage FonctionnementEchec de lAutotest Messages de Surcharge Alarme Sur BatterieFonctionnement suite Fonctionnement NormalMessages de Fermeture Messages de BypassGarantie Limitée à 2 Ans Entreposage, Entretien, Garantie et AssuranceEntreposage EntretienInformation sur le modèle Nos de modèle Spécifications                                                                                                       200907004 932407-RU

10KVA specifications

The Tripp Lite 10KVA is a highly versatile and robust uninterruptible power supply (UPS) system designed to provide seamless power protection for critical applications. This unit is ideal for data centers, telecommunications equipment, and industrial applications where power stability is paramount. With a rated capacity of 10,000 VA, it ensures that your equipment remains operational during power outages or fluctuations.

One of the key features of the Tripp Lite 10KVA is its advanced battery management system. This technology not only prolongs the life of the batteries but also optimizes their performance. The UPS comes equipped with high-capacity batteries, allowing for extended backup times and ensuring that connected devices can function uninterrupted during emergencies.

Another notable feature is the inverter efficiency, which allows the UPS to convert stored battery power into reliable AC output with minimal loss. This is critical in high-demand scenarios where energy efficiency is essential. The Tripp Lite 10KVA also boasts a wide input voltage range and frequency compatibility, making it suitable for various electrical environments.

The unit incorporates multiple outlets, providing the flexibility to connect diverse devices simultaneously. Additionally, the Tripp Lite 10KVA includes an LCD display, offering real-time data on battery status, load levels, and operating conditions, which aids in proactive management of power resources.

For enhanced safety, the UPS is equipped with numerous protection features, including surge suppression, which protects sensitive equipment from voltage spikes. It also includes built-in circuit breakers to prevent overloads and short circuits, ensuring the safety of both the UPS and connected devices.

Networking capabilities are another standout characteristic of the Tripp Lite 10KVA. With optional SNMP support, users can monitor the UPS remotely, allowing for effective management and troubleshooting from virtually anywhere. This feature enhances system reliability and contributes to a more efficient operational workflow.

In conclusion, the Tripp Lite 10KVA is a powerful and reliable UPS solution that combines advanced technologies with thoughtful features to deliver unmatched performance. Its robust design, efficiency, and extensive safety measures make it a vital component for any organization looking to safeguard their critical power infrastructure. Whether for business continuity or equipment protection, the Tripp Lite 10KVA stands out as a premier choice in the UPS market.