Tripp Lite PDUMNV20 owner manual None

Page 6

Installation continued

4-2Configure Terminal Emulation Program: Open a VT100-compatible terminal emulation

program (such as the HyperTerminal program bundled with Microsoft® Windows®) on a computer with an available DB9 serial port. (A notebook computer may be the most convenient choice.) Set the terminal emulation program to use the COM port that corresponds to the computer’s DB9 serial port. Specify the parameters required to communicate with the PDU terminal interface:

Bits per second:

9600

Stop bits:

1

Data bits:

8

Flow control:

None

Parity:

None

 

 

If the terminal emulation program supports multiple emulation modes, you may also need to specify VT100 emulation.

4-3Connect PDU to Computer: Use the RJ-45 to DB9 serial cable (part number 73-1243) included with the PDU to connect the PDU to the computer. The RJ-45 connector A at one end of the cable attaches to the CONFIG port B on the PDU. The DB9 connector C at the other end of the cable connects to the computer's serial port D .

4-4Connect PDU to Network: While the PDU is powered, connect a standard Ethernet patch cable to the RJ-45 Ethernet port A on the PDU.

Note: This port is not compatible with PoE (Power over Ethernet) applications.

B

 

 

D

A

 

 

4-3

 

C

 

LINK

STATUS

 

RESET

CONFIG

4-4

ENVIROSENSE

ACCY

A

4-5Configure PDU in Terminal Mode: After a brief pause, an initialization page should appear in the terminal emulation program. Press any key on the keyboard within 10 seconds to change the PDU settings. (If the 10-second period has elapsed, you can reboot the PDU by pressing the SNMP reset switch.)

Follow the sequence of responses below

in order to assign an IP address to the 4-5PDU. The default terminal mode root

password is TrippLite. Sample IP settings are shown - supply your own IP information when you configure your PDU.

6

201112142 933151.indb 6

1/24/2012 2:09:55 PM

Image 6
Contents Monitored Rack PDU Important Safety Instructions Monitored Rack PDU FeaturesSwitched Rack PDU Features Installation Mounting the PDUConnecting the PDU Power cord connectionNetworking the PDU Dynamic IP Address AssignmentStatic IP Address Assignment None Testing Network Connection Network Interface ParametersFeatures IEC 309 3-Pole Input Plug Available on select modelsAccy Port The port is reserved for future expansion Configuration and Operation Remote Monitoring and ControlWarranty and Warranty Registration Limited Warranty201112142 933151-EN Manual del propietario Instrucciones de seguridad importantes Características de la PDU Monitoreada para RackCaracterísticas alternas de la PDU para Rack Instalación Montaje del PDUInstalación continuación Conexión del PDUConectando Su PDU a la Red Asignación de una Dirección IP DinámicaAsignación de una Dirección IP Estática 5Configure el PDU en Modo Terminal Probando la Conexión de Red Características Características continuación Los modelos de 20-amp presentan un Interruptor paraPower over Ethernet / Energía sobre la Ethernet Configuración y operación Control y monitoreo remotoGarantía Garantía LimitadaManuel du propriétaire Importantes consignes de sécurité Caractéristiques de la PDU en bâti surveilléeCaractéristiques de la PDU en bâti à liaison commutée Montage de lunité de distribution dalimentation PDUInstallation suite Connexion de lunité de distribution dalimentation PDUMise en réseau de lunité de distribution Affectation dune adresse IP dynamiqueAffectation dune adresse IP statique 3Connecter la PDU à lordinateur Test de la connexion réseau Caractéristiques Caractéristiques suite PoE Power Over Ethernet Configuration et fonctionnement Surveillance et commande à distanceGarantie Garantie Limitée