Function | Factory Default | Options | Description |
|
|
|
|
Load Shed Time | Disabled | The amount of time the outlets will function on | |
when On Battery |
|
| battery power before they will turn off. |
|
|
|
|
Load Shed On | Disabled | • Shutdown with | When the battery runtime falls below the |
Runtime |
| delay | specified value, the Controllable Outlet Group |
|
| • Shutdown | will turn off. |
|
| immediately | Configure this time using the LOAD SHED |
|
| • Turn off | |
|
| immediately | RUNTIME REMAINING setting. |
|
| • Turn off with |
|
|
| delay |
|
|
| • Disabled |
|
|
|
|
|
Load Shed On | Disabled | When the remaining runtime reaches this level, | |
Runtime |
|
| the Controllable Outlet Group will turn off. |
Remaining |
|
|
|
|
|
|
|
Load Shed on | Disabled | • Disabled | (Applicable only for Controllable Outlet |
Overload |
| • Enabled | Groups, not the UPS outlets.) When enabled, |
|
|
| the Controllable Outlet Group will turn off |
|
|
| immediately in the event of a power outage |
|
|
| and will have to be manually restarted. |
Network Management Card Settings
These settings are available only on units that have a Network Management Card (NMC) and are set in the factory. These settings can only be modified using an external interface, like the NMC web interface.
•NMC IP Address Mode
•NMC IP Address
•NMC Subnet Mask
•NMC Default Gateway
10 |