Using the Controllable Outlet Groups and UPS outlets
The UPS outlets function as a master switch. They turn on first when power is applied, shut off last when there is a power outage and battery
The UPS outlets must be turned on for the Controllable Outlet Groups to turn on.
1.Connect critical equipment to the UPS outlets (except for 1500 VA models; then, connect all critical equipment to one Controllable Outlet Group.)
2.Connect peripheral equipment to the Controllable Outlet Groups.
–Nonessential equipment that should shut off quickly in the event of a power outage to conserve battery runtime can be added to a short
–If equipment has dependent peripherals that must restart or shut down in a specific order, such as an ethernet switch that must restart before a connected server, connect the devices to separate groups
–Equipment that needs to reboot independently from other equipment should be added to a separate group
3.Use the Configuration menus to configure how the Controllable Outlet Groups will react in the event of a power outage.
Customize the Controllable Outlet Groups and the UPS outlets
Use the Control menus to change the Controllable Outlet Groups and the UPS outlet settings.
Function | Factory Default | Options | Description | |
|
|
|
| |
Name String | Outlet Group 1 | Edit these names using an external interface, such as the Network | ||
Outlet Group |
| |||
| Management Card Web interface. | |||
|
| |||
UPS Name String | UPS Outlets | |||
|
| |||
|
|
|
| |
Turn On Delay | 0 sec | The amount of time the UPS or Controllable | ||
|
|
| Outlet Group will wait between receiving the | |
|
|
| command to turn on and the actual startup. | |
|
|
|
| |
Turn Off Delay | 0 sec | The amount of time that the UPS or | ||
|
|
| Controllable Outlet Group will wait between | |
|
|
| receiving the command to turn off and the | |
|
|
| actual shut down. | |
|
|
|
| |
Reboot Duration | 4 sec | The amount of time that the UPS or | ||
|
|
| Controllable Outlet Group must remain off | |
|
|
| before it will restart. | |
|
|
| ||
Minimum Return 0 sec | The amount of battery runtime that must be | |||
Time |
|
| available before the UPS or Controllable | |
|
|
| Outlet Group will turn on. | |
|
|
|
| |
Load Shed On | Disabled | • Shutdown with | When the unit switches to battery power, the | |
Battery |
| Delay | UPS can disconnect power to the Controllable | |
|
| • Shutdown | Outlet Groups to save runtime. | |
|
| immediately | Configure this delay time, use the LOAD SHED | |
|
| • Turn off | ||
|
| immediately | TIME WHEN ON BATTERY setting. | |
|
| • Turn off with |
| |
|
| delay |
| |
|
| • Disabled |
|
9 |