Schneider Electric 750VA operation manual Using the Controllable Outlet Groups and UPS outlets

Page 12

Using the Controllable Outlet Groups and UPS outlets

The UPS outlets function as a master switch. They turn on first when power is applied, shut off last when there is a power outage and battery run-time has been exhausted.

The UPS outlets must be turned on for the Controllable Outlet Groups to turn on.

1.Connect critical equipment to the UPS outlets (except for 1500 VA models; then, connect all critical equipment to one Controllable Outlet Group.)

2.Connect peripheral equipment to the Controllable Outlet Groups.

Nonessential equipment that should shut off quickly in the event of a power outage to conserve battery runtime can be added to a short power-off delay

If equipment has dependent peripherals that must restart or shut down in a specific order, such as an ethernet switch that must restart before a connected server, connect the devices to separate groups

Equipment that needs to reboot independently from other equipment should be added to a separate group

3.Use the Configuration menus to configure how the Controllable Outlet Groups will react in the event of a power outage.

Customize the Controllable Outlet Groups and the UPS outlets

Use the Control menus to change the Controllable Outlet Groups and the UPS outlet settings.

Function

Factory Default

Options

Description

 

 

 

 

Name String

Outlet Group 1

Edit these names using an external interface, such as the Network

Outlet Group

 

 

Management Card Web interface.

 

 

UPS Name String

UPS Outlets

 

 

 

 

 

 

Turn On Delay

0 sec

0-32767 sec

The amount of time the UPS or Controllable

 

 

 

Outlet Group will wait between receiving the

 

 

 

command to turn on and the actual startup.

 

 

 

 

Turn Off Delay

0 sec

0-32767 sec

The amount of time that the UPS or

 

 

 

Controllable Outlet Group will wait between

 

 

 

receiving the command to turn off and the

 

 

 

actual shut down.

 

 

 

 

Reboot Duration

4 sec

0-32767 sec

The amount of time that the UPS or

 

 

 

Controllable Outlet Group must remain off

 

 

 

before it will restart.

 

 

 

Minimum Return 0 sec

0-32767 sec

The amount of battery runtime that must be

Time

 

 

available before the UPS or Controllable

 

 

 

Outlet Group will turn on.

 

 

 

 

Load Shed On

Disabled

• Shutdown with

When the unit switches to battery power, the

Battery

 

Delay

UPS can disconnect power to the Controllable

 

 

• Shutdown

Outlet Groups to save runtime.

 

 

immediately

Configure this delay time, use the LOAD SHED

 

 

• Turn off

 

 

immediately

TIME WHEN ON BATTERY setting.

 

 

• Turn off with

 

 

 

delay

 

 

 

• Disabled

 

Smart-UPS X-Series Operation

9

Image 12 Contents
UPS Overview Smart-UPS Factory Warranty Safety OverviewAbout the UPS Product OverviewSpecifications InstallationEnvironmental Specifications Network Management Card External Battery PackOperation Connect Equipment to the UPSBasic Connections Using the display interface Display InterfaceOverview Standard MenusAdvanced Menus Configuration UPS SettingsStart-up Settings General SettingsControllable Outlet Groups Model-specific Controllable Outlet Groups Using the Controllable Outlet Groups and UPS outlets Network Management Card Settings Emergency Power Off EPO OverviewNormally open contacts Normally closed contactsTroubleshooting UPS does not provide expected backup timeDisplay interface indicators flash sequentially UPS is emitting an audible beeping soundProblem and Possible Cause Replace battery LED is illuminatedDisplay interface has a Site Wiring Fault message Service and Support ServiceTransport the UPS APC Worldwide Customer SupportSmart-UPS Factory Warranty Limited WarrantyHarmonized Standards Applicable CouncilDirectives Type of Equipment Model Numbers990-3458-001 06/2009