Schneider Electric 750VA Troubleshooting, UPS is emitting an audible beeping sound

Page 15

Troubleshooting

Problem and Possible Cause

Solution

 

The UPS will not turn on or there is no output

 

 

The unit has not been turned on.

Press the ON button once to turn on the UPS.

 

 

The UPS is not connected to utility

Ensure that the power cable is securely connected to the unit and to the utility

power.

power supply.

 

 

The input circuit breaker has tripped.

Reduce the load to the UPS, disconnect nonessential equipment and reset the

 

circuit breaker.

The unit shows very low or no input utility voltage.

Check the AC power supply to the UPS by plugging in a table lamp. If the light is very dim, check the utility voltage.

The battery connector plug is not securely Ensure that all battery connections are secure. connected.

There is an internal UPS fault.

Do not attempt to use the UPS. Unplug the UPS and have it serviced immediately.

The UPS is operating on battery, while connected to input utility power

The input circuit breaker has tripped.

Reduce the load to the UPS, disconnect nonessential equipment and reset the circuit breaker.

There is very high, very low, or distorted input line voltage.

Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display. If acceptable to the connected equipment, reduce the UPS sensitivity.

UPS is emitting an audible beeping sound

The UPS is in normal operation.

None. The UPS is protecting the connected equipment.

UPS does not provide expected backup time

The UPS battery is weak due to a recent outage or is near the end of its service life.

Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery LED indicator is not yet illuminated.

The UPS is overloaded.

Check the UPS load display. Unplug unnecessary equipment, such as printers.

 

Display interface indicators flash sequentially

 

 

The UPS has been shut down remotely

None. The UPS will restart automatically when utility power returns.

through software or an optional accessory

 

card.

 

 

All indicators are lit and the UPS emits a constant beeping sound

 

 

Internal UPS fault.

The fault LED is illuminated and the unit displays a fault message. Do not

 

attempt to use the UPS. Turn the UPS off and have it serviced immediately.

 

 

12

Smart-UPS X-Series Operation

Image 15 Contents
UPS Overview Smart-UPS Factory Warranty Product Overview SafetyOverview About the UPSNetwork Management Card External Battery Pack SpecificationsInstallation Environmental SpecificationsOperation Connect Equipment to the UPSBasic Connections Standard Menus Using the display interfaceDisplay Interface OverviewAdvanced Menus General Settings ConfigurationUPS Settings Start-up SettingsControllable Outlet Groups Model-specific Controllable Outlet Groups Using the Controllable Outlet Groups and UPS outlets Network Management Card Settings Normally closed contacts Emergency Power OffEPO Overview Normally open contactsUPS is emitting an audible beeping sound TroubleshootingUPS does not provide expected backup time Display interface indicators flash sequentiallyProblem and Possible Cause Replace battery LED is illuminatedDisplay interface has a Site Wiring Fault message APC Worldwide Customer Support Service and SupportService Transport the UPSLimited Warranty Smart-UPS Factory WarrantyModel Numbers Harmonized StandardsApplicable Council Directives Type of Equipment990-3458-001 06/2009