Schneider Electric 750VA Configuration, UPS Settings, Start-up Settings, General Settings

Page 9

Configuration

UPS Settings

Start-up Settings

Configure these settings at initial start-up, using the display interface or APC PowerChute® software.

Note: During start-up, use the display interface to configure these settings. If nothing is selected, the until will use the default settings.

Function

Factory Default

Options

Description

 

 

 

 

Language

English

• English

The language for the display interface.

 

 

• French*

*Language options will vary by model.

 

 

• German*

 

 

• Spanish*

 

 

 

• Italian*

 

 

 

 

 

Local power

Good

• Good

Select the quality of input utility power.

quality

 

• Fair

• If Good is selected, the unit will go on battery

 

 

• Poor

power more often to provide the cleanest power

 

 

 

supply to the connected equipment.

 

 

 

• If Poor is selected, the UPS will tolerate more

 

 

 

fluctuations in power and will go on battery power

 

 

 

less often.

 

 

 

If unsure of the local power quality, select Good.

 

 

 

 

Menu Type

Standard

Standard or

The advanced menus include all parameters. The

 

 

Advanced

Standard menus display a limited set of menus and

 

 

 

options.

 

 

 

 

Display

Always On

Always On or

The display may be always on or may be set to

Mode

 

Power Saving

automatically turn on only when using the

 

 

 

configuration buttons or if an event occurs.

General Settings

Configure these settings at any time, using the display interface or APC PowerChute software.

Function

Factory Default Options

Description

High transfer

120 V: 140 VAC

120 V: 140-150 VAC

point

 

 

230 V: 280 VAC

230 V: 280-300 VAC

To avoid unnecessary battery usage, set the transfer point higher if the utility voltage is chronically high and the connected equipment is known to work under this condition. This setting may also be adjusted using the power quality setting.

Low Transfer

120 V: 75 VAC

120 V: 75-85 VAC

Point

 

 

230 V: 170 VAC

230 V: 150-170 VAC

Set the transfer point lower if the utility voltage is chronically low and the connected equipment can tolerate this condition.This setting may also be adjusted using the power quality setting.

6

Smart-UPS X-Series Operation

Image 9 Contents
UPS Overview Smart-UPS Factory Warranty Overview SafetyAbout the UPS Product OverviewInstallation SpecificationsEnvironmental Specifications Network Management Card External Battery PackOperation Connect Equipment to the UPSBasic Connections Display Interface Using the display interfaceOverview Standard MenusAdvanced Menus UPS Settings ConfigurationStart-up Settings General SettingsControllable Outlet Groups Model-specific Controllable Outlet Groups Using the Controllable Outlet Groups and UPS outlets Network Management Card Settings EPO Overview Emergency Power OffNormally open contacts Normally closed contactsUPS does not provide expected backup time TroubleshootingDisplay interface indicators flash sequentially UPS is emitting an audible beeping soundProblem and Possible Cause Replace battery LED is illuminatedDisplay interface has a Site Wiring Fault message Service Service and SupportTransport the UPS APC Worldwide Customer SupportLimited Warranty Smart-UPS Factory WarrantyApplicable Council Harmonized StandardsDirectives Type of Equipment Model Numbers990-3458-001 06/2009