5.4.3Modbus Plus Port Status Indicators

The green MODBUS PLUS indicator shows the overall communication status at the BM￿￿ node. Two red indicators for ERROR CHANNEL A and ERROR CHANNEL B identify errors on the two Modbus Plus cable paths.

If the ERROR CHANNEL A or ERROR CHANNEL B indicator blinks momentarily, it indicates that a message error was detected on the Modbus Plus cable path. A steady ON state indicates a hard fault exists, either in the cable or in a node device connected to it. If communication is lost on one cable path, the other path continues normally.

The MODBUS PLUS indicator flashes repetitive patterns to show the BM￿￿ node's communication status on the Modbus Plus network. The patterns are:

Six Flashes per Second

This is the BM￿￿ node's normal operating state. All nodes on the network should be flashing this pattern. If the indicator is OFF continuously, the BM￿￿ is not transmitting on the network.

One Flash per Second

The BM￿￿ node is offline after just being powered up, or after hearing a message from another node with the same network address (duplicate addresses are not allowed). In this state, the node monitors the network and builds a table of active nodes. It remains in this state for five seconds, then attempts to go to its normal operating state.

Two Flashes, then OFF for Two Seconds

The BM￿￿ node is hearing the token being passed among other nodes, but is never receiving the token. Check the network link for an open or short circuit, or defective termination.

Three Flashes, then OFF for 1.7 Seconds

The BM￿￿ node is not hearing any other nodes. It is claiming the token, but finding no other node to which to pass it. Check the network link for an open or short circuit, or defective termination.

Four Flashes, then OFF for 1.4 Seconds

The BM￿￿ node has heard a valid message from another node that is using the same address as this node. The BM￿￿ node remains offline in this state as long as it continues to hear the duplicate address. If the duplicate address is not heard for five seconds, the node then changes to the pattern of one flash every second.

31007492

Installing the BM85 79

Image 89
Contents February Page Preface PrefacePage Contents 2e.2ie3 +f 0he C+*fig1.a0i+* .+ce Chapter Configuring the Modbus ModelsContents Vii Chapter Configuring the Programmable ModelsAppendix a Compatible Devices and Cables Chapter Installing the BM85Viii Contents Figures Glossary IndexPage Introducing the BM85 Bridge/Multiplexers Chapter Introducing the BM85 Bridge/MultiplexersBM85 on Modbus Plus Bridge/Multiplexers on Modbus PlusModbus Plus Network BM85 Bridge/Multiplexers on Modbus Plus Mounting Methods Overview of BM85 ModelsAvailable Models Configuration Methods Operating PowerProgrammable Port Models BM85 With Typical RS232/485 Devices Downloading the Application Configuring the Programmable ModelsDeveloping the Application Part Number Description Software Development Tool KitContact Telephone Modbus Port Models BM85 With Typical Modbus Devices Bridge/Multiplexer Models for AC/DC Power Specifications AC/DC Power ModelsDevelopment Requirement Supplied by Customer Bridge/Multiplexer Models for DC/DC Power Specifications DC/DC Power ModelsSoftware Development Tool Kit Page Device Addressing and Message Routing Chapter Device Addressing Message RoutingRouting to Programmable Controllers Modbus Plus Message Routing PathsRouting to BM85 Bridge/Multiplexers Routing to Host Based Network AdaptersRouting to Serial Ports on BM85 Programmable Models Routing to a Single Slave Device on BM85 Modbus ModelsModbus Port Models Modbus Address ConversionProgrammable Port Models Silent Master Port Addressing Routing Examples Routing ExamplesFrom Address Routing Method From Routing PathPage Configuring the Modbus Models Chapter Configuring Modbus ModelsModels Covered in This Chapter An Overview of the Configuration ProcessBefore You Start Required Equipment Configuration Checklist Information You Will Need Modbus Port ParametersMaster Port TypeSlave NetworkSlave Device Address Setting the ParameterCommunication Parameters Port PriorityLink Timeout Timeout Examples How the Parameter Applies to the BM85 Modem BoosterModem Booster Example Table Location Modbus Address Five±Byte Routing Path Modbus Address MapIf a Match is Not Found Configuring the Modbus Models Silent Master Port Considerations Setting the Switches Configuring the Modbus PortsConnecting Power for the Configuration Connecting the Terminal Command Action Range Your Configuration CommandsParameter Port Default ConfigurationHelp Screens V5, V6, V7 Your Configuration ScreensEntering Commands Into Your Screens Saving the Configuration Printing the ConfigurationYour V1 Screen Layout Your V1 ScreenExample Using the V1 ScreenYour V2 or V3 Screen Layout Your V2 and V3 ScreensUsing the V2 or V3 Screen Your V4 Screen Layout Your V4 ScreenEnter Using the V4 ScreenBM85 Modbus Models Modbus Plus Address Switches Setting the Modbus Plus AddressHow to Set the RUN Mode Setting the RUN ModeWhen to Set the RUN Mode Hardware Error Codes 11 .. Hex Modbus Port Indicator CodesModbus Driver Error Codes 24 .. E Hex Indicators Pattern Hexadecimal DigitLLC Layer Error Codes 81 ... A3 Hex Modbus Plus Processor Interface Error Codes 34 .. HexPage Configuring the Programmable Models Chapter Configuring Programmable ModelsBefore You Start Equipment For Downloading the Application Program Equipment for Writing the Application ProgramDevelopment Software Files Overview of the Development SoftwareREADME.DOC Information File File Name PurposeTest and Demonstration Source Files Using the Test and Demonstration Source FilesMultitasking in Your Application Key Sequence PurposeInstallation Steps Installing the Development SoftwareDefault Parameters Key Sequence Purpose Alt±C Project close Preparing the BM85 for Downloading BM85 Programmable Models Configuration Switches Setting the Configuration SwitchesBM85 Programmable Models Modbus Plus Address Switches Error Codes Indicator Codes During DownloadingError Code Hexadecimal Meaning Normal Download CodesSetting the RUN Mode Installing the BM85 Chapter Installing the BM85Shelf/Panel Mounted Models Installing the BM85 HardwareMounting the BM85 Horizontal Mounting Rack Mounted ModelsVertical Mounting Part Number Mounting MethodRear Panel View 31007492OP View Mounting Dimensions Rack Mount ModelsConnecting DC Power Connecting the Power CablesConnecting AC Power BM85-000 Rear Panel PV02 or earlier BM85000 Connecting the Network and Serial CablesConnecting Dual Network Cables Connecting a Single Network CableConnecting Dual-Cable Units on Single-Cable Networks Connecting Serial Port CablesModbus and Serial Port Indicators Reading the IndicatorsPower and Ready Indicators Modbus Plus Port Status Indicators Modbus Plus Port Label Attaching Identification LabelsSerial Port Parameters Label Serial Port Parameters LabelPage Compatible Devices and Cables Appendix a Compatible Devices CablesAbbreviations Compatible Devices and CablesMaking `Quick Connections Modicon Devices and CablesCables for Modbus Master Devices Devices and Cables for Configuring Modbus PortsCables for Modbus Slave Devices Device Cable and Adapter CombinationModbus/RS232 Cable Wiring Diagrams Modbus/RS232 Cable Wiring DiagramsSerial Ports Pinout ± Modbus/RS232 BM85 Direction Purpose Modbus/RS232 Ports PinoutSerial Ports Pinout ± RS485 BM85 Direction Purpose RS485 Ports PinoutAddress AcknowledgementBaud rate BitBroadband Bridge PlusBus CarrierbandDistributed I/O DIO Drop AdapterDownload Drop cableGlobal Input Frame descriptorGlobal Output Host computerMedium LayerModbus Modbus PlusNetwork Option Module ModemNode OSI ModelPhysical Layer Peer-to-peer communicationPort ProtocolSerial port SegmentSlot time Specific InputTap SystemTerminator TokenPage Index IndexIndex