7.6Installing Line Cards
This procedure describes how to install one line card as part of a replacement operation. If you are installing more than one line card, repeat the procedure for each line card. Alternatively, refer to the Sun Datacenter Switch 3456 Installation Guide.
▼Installing a Line Card
Installing the line card is a
1.Extend the antitilt bar from the bottom of the switch chassis.
2.Unwrap the line card from its antistatic packaging.
3.Inspect the connectors and retainers. See:
■“Inspecting the Line Card iTRAC Connectors” on page
■“Inspecting the Line Card iPASS Connectors” on page
■“Inspecting the Retainers” on page
4.Place a line card on a work surface, with the retainers facing the two installers.
5.Using a 17 mm socket and ratchet, turn each retainer drive screw fully
6.Rotate both the retainer drive screws clockwise, 1/4 turn.
Caution – If you are preparing a new line card as a replacement operation, stop here and refer to: “Removing a Line Card” on page
7.Remove the filler panel for where the line card is to install.
a.Grasp the locking levers at each end of the filler panel.
See FIGURE
Chapter 7 Line Card Service Procedures