Delta Electronics DVPEN01-SL manual Numbering of Left-Side Extension Modules

Page 14

Ethernet Communication Module DVPEN01-SL

CR#116: Modbus TCP Status

Explanations:

Displaying the current communication status of Modbus TCP mode. When the CR value is set as”0” Æ the data have not yet been received; when the CR value is set as “1” Æ the data exchange is in progress; when the CR value is set as “2” Æ the data exchange is successful; when the CR value is set as “3” Æ the data exchange fails.

CR value

Data exchange status

0

The data have not been received.

 

 

1

The data exchange is in progress.

 

 

2

The data exchange is successful.

 

 

3

The data exchange fails.

 

 

CR#117, 118: Modbus TCP Destination IP

Explanations:

Setting up the destination IP address in Modbus TCP mode. See explanations on CR#70 and #71 for how to set.

CR#119: Modbus TCP Data Length

Explanations:

Setting up the length of communication data in Modbus TCP mode. Length for 8-bit mode: K1

~K100; length for 16-bit mode: K1 ~ K200.

CR#120 ~ 219: Modbus TCP Data Buffer

Explanations:

Buffer for transmitted/received data in Modbus TCP mode.

CR#251: Error Code

Explanations:

Table of error code:

Bit No.

Error

b0

The network is not yet connected.

 

 

b1

Incorrect IP setting

 

 

b2

CR#13 is set as “transmitting data”, but the data exchange

is forbidden.

 

b3

CR#13 is set as “transmitting data”, but the data exchange

mode has not yet been enabled.

 

b4

NTP-Server connection fails.

 

 

b7

SMTP-Server connection fails.

 

 

b8

DHCP has not obtained the correct network parameter.

 

 

4.3Numbering of Left-Side Extension Modules

After DVPEN01-SL is installed properly, you need to compile the PLC program to control the extension modules. PLC offers FROM instrcution (for reading) and TO instrcution (for writing) to control the control

12

DVP-PLC Application Manual

Image 14
Contents DVPEN01-SL Page Table of Contents Application Examples Introduction Product Profile & Outline Installation & Wiring Control Register CR Ethernet Communication Module DVPEN01-SL „ E-mail Functions „ Data Exchange „ Network Settings CR#74, 75 Gateway Numbering of Left-Side Extension Modules Setting up Software Ethernet Communication Module DVPEN01-SL Ethernet Communication Module DVPEN01-SL Basic Settings Ethernet Communication Module DVPEN01-SL Network Settings Ethernet Communication Module DVPEN01-SL Dhcp Ethernet Communication Module DVPEN01-SL Data Exchange IP Filter Static ARP Table Setting up Password Returning to Default Setting Export & Import of DVPEN01-SL Files Recording IP Address Application Examples Ethernet Communication Module DVPEN01-SL Ethernet Communication Module DVPEN01-SL Connecting the PC with DVPEN01-SL through LAN DVPEN01 DVP-PLC Ethernet Communication Module DVPEN01-SL Ethernet Communication Module DVPEN01-SL END Setting up Password and Clearing Password Ethernet Communication Module DVPEN01-SL Ethernet Communication Module DVPEN01-SL IP Filter Protection Ethernet Communication Module DVPEN01-SL Setting up Static ARP Table Application of E-Mail Ethernet Communication Module DVPEN01-SL Explanations TRD SET TOP From K100 K86 H1064 HFF Ethernet Communication Module DVPEN01-SL Memo