Ethernet Communication Module DVPEN01-SL 
•Write the data in RTC into CR#29 ~ CR#35.
•Write “1” into CR#13 to start the data exchange.
•CR#14 = 2 refers to successful exchange. CR#14 = 3 refers to failed exchange.
5.Compile the ladder diagram for PLC_A and download it to PLC_A.
| M1013 | 
 | 
 | 
 | 
 | 
| FROM | K100 | K49 | D0 | K7 | 
| END | 
 | 
 | 
 | 
 | 
| Explanations: | 
 | 
 | 
 | 
 | 
•The received data are stored in CR#49 ~ CR#55.
•The data received every one second are written into D0 ~ D6.
6.10Application of Data Exchange (2)
Application
Network requirement
Writing the time in RTC in PLC_B into D0 ~ D6 of PLC_A by designating IP by ladder diagram.
(1)Adopting static IP.
(2)IP of PLC_A: 192.168.0.4
(3)IP of PLC_B: 192.168.0.5
(4)Update from PLC_B to PLC_A
1.See 6.1 for how to set up the communication. Compile the ladder diagram in the MPU and download it to PLC_B. See below for the program design:
| M1000 | 
 | 
 | TRD | D100 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | ||
| M1013 | M2 | M1 | SET | M1 | 
 | 
 | 
 | 
| 
 | 
 | 
 | 
 | 
 | 
 | ||
| M1 | 
 | 
 | TOP | K100 | K28 | K0 | K1 | 
| 
 | 
 | 
 | |||||
| 
 | 
 | 
 | TOP | K100 | K26 | HC0A8 | K1 | 
| 
 | 
 | 
 | TOP | K100 | K25 | H4 | K1 | 
| 
 | 
 | 
 | TOP | K100 | K29 | D100 | K7 | 
| 
 | 
 | 
 | TOP | K100 | K14 | K0 | K1 | 
| 
 | 
 | 
 | TOP | K100 | K13 | K1 | K1 | 
| 
 | 
 | 
 | SET | M2 | 
 | 
 | 
 | 
| 
 | 
 | 
 | RST | M1 | 
 | 
 | 
 | 
| M2 | 
 | 
 | 
 | 
 | 
 | 
 | 
 | 
| 
 | 
 | 
 | FROM | K100 | K14 | D14 | K1 | 
| 
 | = D14 K2 | RST | M2 | 
 | 
 | 
 | |
| 
 | = D14 K3 | RST | M2 | 
 | 
 | 
 | |
| 
 | 
 | 
 | END | 
 | 
 | 
 | 
 | 
| 47 |