Wiring and Installation
!To receive 455 kHz, position the jumper (both jumpers on the receivers) on the left two pins, pins 1 and 2, away from the edge of the circuit boards, to receive 455 kHz. (This is the default setting.)
!To receive 38 kHz, position the jumper (both jumpers on the receivers) on the right two pins, pins 2 and 3, near the edge of the circuit boards, to receive 38 kHz.
|
|
|
|
|
| IR SNSR |
|
|
|
|
|
| IR SNSR |
|
|
|
|
|
| 38/455 |
|
|
|
|
|
| 38/455 |
|
|
|
|
|
| kHz |
|
|
|
|
|
| kHz |
|
|
|
|
|
|
|
|
|
|
| |||
Setting for 455 kHz | Setting for 38 kHz (default) |
FIG. 10 Receive frequency jumper settings
2.Go on to the next procedure:
!If you are installing a receiver, go on to Configuring the Receivers.
!If you are installing an IR sensor, refer to Sensor IR validation level in Configuring the Receivers before going on to Installation.
Configuring the Receivers
To configure the receivers, set the AXlink device number and the IR validation level.
AXlink Device DIP switch
IR validation jumper pins
AXlink connector
FIG. 11 IR receiver AXlink device DIP switches, IR validation jumper pins, AXlink connector, and receive frequency jumper pin locations
Setting the AXlink Device Number
Perform the following steps to set the receiver's AXlink device number:
1.Locate the
2.Set the DIP switch according to the DIP switch values shown in FIG. 12.
The device number is set by the total value of DIP switch positions that are ON (down). The Axcess software program in your system typically uses device numbers 128 through 255 for the panels.
Switch | 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
Value 1 2 4 8 16 32 64 128
| 8 | IR Sensors and Receivers |
|
|
|