MULTITASKER
2.Connect Input 1 to Output 1
Starting from the
4Select the CONNECT menu
1Select SELECT INPUT
01Set input 01
2Select SELECT OUTPUT
01Set output 01
3Select SWITCH to make connection The Main Menu is redisplayed.
3.Verify signal on Input 1 and Output 64
Starting from the
5Select SIGNAL DETECT
1Select SELECT INPUT
01Enter input number 1
The card checks for a signal and updates the value displayed in parentheses.
2Select SELECT OUTPUT
64Enter output number 64
The card checks for a signal and updates the value displayed in parentheses.
3 Select CHECK SIGNAL
Each time 3 is pressed, the card checks for the signals and redisplays the status.
ESC Return to the Main Menu
4. Turn off all outputs.
Starting from the
3Select OUT ON/OFF menu
2Select ALL OUTPUTS OFF The Main Menu is redisplayed.
TROUBLESHOOTING GUIDE | 8 |
We have carefully tested and have found no problems in the supplied
8.1 LED IS NOT LIT
Cause 1: The card cage is not plugged in.
Solution: Plug in the card cage. If the LED lights, the problem is solved. If the LED is still not on, see Cause 2.
Cause 2: The card is not plugged in all the way.
Solution: Push the card in all the way. If the LED is still not on, see Cause 3.
Cause 3: The card cage slot has a problem.
Solution 1: Test the card in other slots. If the slot was damaged, the card may work in other slots. If other slots work and the LED lights, the problem is the card cage slot and it may require service. Call ALTINEX at (714)
Solution 2: Take any other known good card with an LED and verify that the slot used is good by seeing if the other card’s LED lights in that slot. If it lights, then the original card may be the source of the problem. Call ALTINEX at (714)
8.2 LED IS BLINKING RED
Cause 1: The CPU on the card is not working properly.
Solution 1: Look at the card and verify that there is no damage. If there is no damage, see Solution 2.
Solution 2: Verify that all ICs are seated in their sockets. If the LED is still blinking red, see Cause 2.
26 |